SICK SENSICK WSE27-3 Operating instructions

Type
Operating instructions
English
Through-beam photoelectric sensor
Operating instructions
Safety notes
Read the operating instructions before commissioning.
Connection, mounting and setting may only be performed by trained
specialists.
Not a safety component in accordance with the EU Machinery Directive.
UL: Only for use in applications in accordance with NFPA 79. Adapters
listed by UL with connection cables are available.
Enclosure type 1.
When commissioning, protect the device from moisture and contamination.
These operating instructions contain information required during the life
cycle of the sensor.
Correct use
The WSE27-3 is an opto-electronic through-beam photoelectric sensor
(referred to as sensor in the following) for the optical, non-contact de-
tection of objects, animals and persons. A sender (WS) and a receiver (WE)
are required for operation. If the product is used for any other purpose or
modied in any way, any warranty claim against SICK AG shall become void.
The WSE27-3R /- 3S sensor is a class A product. In household environ-
ments, devices of this kind can cause radio interference. The user should
take appropriate measures as required.
Commissioning
1 Observe the application conditions: Adjust the distance between the
sender and the receiver according to the corresponding diagram
(x = sensing range, y = operating reserve).
If several through-beam photoelectric sensors which are installed next
to one another are to be used, we recommend swapping the sender /
receiver arrangement at every second through-beam photoelectric
sensor and ensuring that there is sucient distance between the
through-beam photoelectric sensors. By doing this, mutual interfer-
ence can be prevented [cf. F].
2 Mount sensors (sender and receiver) using suitable mounting brackets
(see the SICK range of accessories). Align the sender and receiver with
each other.
Note the sensor's maximum permissible tightening torque of 1.3 Nm.
3 The sensors must be connected in a voltage-free state. The information
in the graphics [B] must be observed, depending on the connection
type:
Male connector connection: pin assignment
Cable (0.25 mm
2
): core color
Only apply voltage / switch on the power supply once all electrical
connections have been completed. The green LED indicator lights up
on the sensor.
Explanations of the connection graphic (graphic B):
Switching outputs Q and / Q (according to graphic B):
WSE27-3P / -3F (PNP: load -> M)
WSE27-3N / -3E (NPN: load -> L+)
Alarm = Alarm output (see Additional functions)
TI = test input (see Additional functions)
WSE27-3R / -3S (relay output)
Q: light switching, object will not be detected, relay active
4 WSE27-xxx3x and WSE27-xxx5x: Align the sender with the receiver.
Select the position so that the red emitted light beam hits the receiver.
Tip: Use white paper or a reector as an alignment aid. The sender
must have a clear view of the receiver, with no object in the path of the
beam [see E]. You must ensure that the optical openings (front screen)
of the sensors are completely clear.
WSE27-xxx1x: Align the sender with the receiver. Select the position
so that the infrared light (not visible) hits the receiver. The correct
alignment can only be detected via the LED indicators. Please refer to
graphics C and E in relation to this. The sender must have a clear view
of the receiver, and no object may be in the optical path. You must
ensure that the optical openings (front screen) of the sensors
are completely clear.
5 Sensor which it is not possible to set for the WSE27-xxxx0: The sensor
is adjusted and ready for operation.
Refer to graphics C and G to check the function. If the switching output
fails to behave in accordance with graphic C, check application condi-
tions. See section Fault diagnosis.
Sensor with WSE27-xxxx1 potentiometer:
The sensitivity is adjusted with the potentiometer (type: 270°). Clock-
wise rotation: operating reserve increased; counterclockwise rotation:
operating reserve reduced. We recommend setting the potentiometer
to Maximum”.
The sensor is adjusted and ready for operation. Refer to graphics C
and G to check the function. If the switching output fails to behave in
accordance with graphic C, check application conditions. See section
Fault diagnosis.
Additional functions
Alarm output: The sensor (WSE27-3) features a pre-failure notication
output (Alarm in connection diagram [B]), which issues a notication if
the sensor is only ready for operation to a limited extent.
Possible causes: Sensor is contaminated, sensor is out of alignment.
WSE27-F2631: PNP: Alarm → M signal reserve > 50 % LOW, -3E2631: NPN:
Alarm → L+ signal reserve > 50 % HIGH. The LED indicator ashes in this case.
Time types: WSE27-3 F, -3E, -3R: t0 = no time delay, t1 = time delay, t2 = time
delay; for -3R: 0 = relay deactivated, 1 = relay active.
Time stage selector
switch can be set on the device according to A.
Time stages: WSE27-3F: < 0.5 s: 0.02 ... 0.5 s or
> 0.5 s: 0.5 ... 10 s can be set.
WSE27-3R: 0.5 to 10 s can be set.
Test input: The WSE27-3 sensor features a test input (TI on the connection
graphic [B]), which can be used to check that the sensor is functioning
correctly: If female cable connectors with LED indicators are used, you must
ensure that the TI is assigned accordingly.
There must be no object between the sender and receiver; activate the test
input (see the connection graphic [B], TI at 0 V). The send LED is shut down
or the detection of an object is simulated. Refer to graphics C and G to
check the function. If the switching output fails to behave in accordance with
graphic C, check application conditions. See section Fault diagnosis.
WSE27-3xxx5x: with static front-screen heating for use in environments with
gradual temperature changes within the +5 °C ... +15 °C range.
Devices with special features
WSE27-3P2430S01: without test input
WSE27-3F2431S04: max. sensing range 0 ... 30 m, t1 = 30 ms or 70 ms
can be set, switching frequency: 2,500 Hz, response time ≤ 200 μs, through
holes with metal sleeves.
WSE27-3P2410S03: max. sensing range 0 ... 45 m, switching frequency:
300 Hz, response time ≤ 1.7 ms, light spot diameter approx. 3.7 m in 25 m.
Fault diagnosis
Table I indicates which measures are to be taken if the sensor stops working.
Disassembly and disposal
The sensor must be disposed of according to the applicable country-specic
regulations. Eorts should be made during the disposal process to recycle
the constituent materials (particularly precious metals).
dark switching light switching
2 1 t = 1
1 2 t = 2
Maintenance
SICK sensors are maintenance-free.
We recommend doing the following regularly:
– Clean the external lens surfaces
– Check the screw connections and plug-in connections
No modications may be made to devices.
Subject to change without notice. Specied product properties and
technical data are not written guarantees.
-3x24xx / -3x34xx -3x26xx DC
-3x37xx DC
-3x26xx AC / DC
WSE27-3
24.6
(0.97)
54 (2.13)
40 (1.57)
50 (1.97)
5.2
(0.20)
45 (1.77)
10
(0.39)
8.4
(0.33)
12.2
(0.48)
80.6 (3.17)
70 (2.76)
49.4 (1.94)
46.2 (1.82)
23
(0.91)
1
2
3
8
7
6
45 45
Q (PNP)
L
1
0
1
0
L
D
D
t0 t1 t0 t2
Q (NPN)
(PNP)
(NPN)
Deutsch
Einweg-Lichtschranke
Betriebsanleitung
Sicherheitshinweise
Vor der Inbetriebnahme die Betriebsanleitung lesen.
Anschluss, Montage und Einstellung nur durch Fachpersonal.
Kein Sicherheitsbauteil gemäß EU-Maschinenrichtlinie.
UL: Nur zur Verwendung in Anwendungen gemäß NFPA 79.
Von UL gelistete Adapter mit Anschlusskabeln sind verfügbar.
Enclosure type 1.
Gerät bei Inbetriebnahme vor Feuchte und Verunreinigung schützen.
Diese Betriebsanleitung enthält Informationen, die während des
Lebenszyklus des Sensors notwendig sind.
Bestimmungsgemäße Verwendung
Die WSE27-3 ist eine optoelektronische Einweg-Lichtschranke (im Folgenden
Sensor genannt) und wird zum optischen, berührungslosen Erfassen von
Objekten, Tieren und Personen eingesetzt. Zum Betrieb ist ein Sender (WS)
und ein Empfänger (WE) erforderlich. Bei jeder anderen Verwendung und
bei Veränderungen am Produkt verfällt jeglicher Gewährleistungsanspruch
gegenüber der SICK AG.
Die WSE27-3R und WSE27-3S sind Produkte der Klasse A. In Haushaltsumge-
bungen können diese Geräte Rundfunktstörungen verursachen, weshalb der
Anwender gegebenenfalls geeignete Maßnahmen ergreifen muss.
Inbetriebnahme
1 Einsatzbedingungen beachten: Distanz zwischen Sender und Empfänger
mit dem zugehörigen Diagramm [vgl. H] abgleichen
(x = Schaltabstand, y = Funktionsreserve).
Beim Einsatz von mehreren Einweg-Lichtschranken, die nebeneinander
installiert werden, empfehlen wir, bei jeder zweiten Einweg-Lichtschranke
die Anordnung von Sender und Empfänger zu tauschen, bzw. genügend
Abstand zwischen den Einweg-Lichtschranken einzuhalten. Damit
können gegenseitige Beeinussungen vermieden werden [vgl. F].
2 Sensoren (Sender und Empfänger) an geeignete Befestigungswinkel
montieren (siehe SICK-Zubehör-Programm). Sender und Empfänger
zueinander ausrichten.
Maximal zulässiges Anzugsdrehmoment des Sensors von 1,3 Nm
beachten.
3 Anschluss der Sensoren muss spannungsfrei erfolgen.
Je nach Anschlussart sind die Informationen in den Graken [vgl. B]
zu beachten:
Steckeranschluss: Pinbelegung
Leitung (0,25 mm
2
): Adernfarbe
Erst nach Anschluss aller elektrischen Verbindungen die Span-
nungsversorgung anlegen bzw. einschalten. Am Sensor leuchtet die
grüne Anzeige-LED.
Erläuterungen zum Anschlussschema (Grak B):
Schaltausgänge Q bzw. Q / (gemäß Grak B):
WSE27-3P / -3F (PNP: Last -> M)
WSE27-3N / -3E (NPN: Last -> L+)
Alarm = Alarmausgang (siehe Zusatzfunktionen)
TE = Testeingang (siehe Zusatzfunktionen)
WSE27-3R / -3S (Ausgang Relais)
Q: hellschaltend, Objekt wird nicht erkannt, Relais aktiv
4 WSE27-xxx3x und WSE27-xxx5x: Sender auf Empfänger ausrichten.
Positionierung so wählen, dass der rote Sendelichtstrahl auf den
Empfänger auftrit. Tipp: weißes Papier oder Reektor als Ausrichthilfe
verwenden. Der Sender muss freie Sicht auf den Empfänger haben, es
darf sich kein Objekt im Strahlengang benden [vgl. E]. Es ist darauf zu
achten, dass die optischen Önungen (Frontscheiben) der Sensoren
vollständig frei sind.
WSE27-xxx1x: Sender auf Empfänger ausrichten. Positionierung so
wählen, dass das Infrarotlicht (nicht sichtbar) auf den Empfänger
auftrit. Die korrekte Ausrichtung kann nur über die Anzeige-LEDs
erkannt werden. Siehe dazu Graken C und E. Der Sender muss freie
Sicht auf den Empfänger haben, es darf sich kein Objekt im Strahlen-
gang benden. Es ist darauf zu achten, dass die optischen Önungen
(Frontscheiben) der Sensoren vollständig frei sind.
5 Sensor ohne Einstellmöglichkeit WSE27-xxxx0: Sensor ist eingestellt
und betriebsbereit.
Zur Überprüfung der Funktion Grak C und G heranziehen. Verhält sich
der Schaltausgang nicht gemäß Grak C, Einsatzbedingungen prüfen.
Siehe Abschnitt Fehlerdiagnose.
Sensor mit Potentiometer WSE27-xxxx1:
Mit dem Potentiometer (Art: 270°) wird die Empndlichkeit eingestellt.
Drehung nach rechts: Erhöhung der Funktionsreserve, Drehung nach
links: Verringerung der Funktionsreserve. Wir empfehlen, das Potentio-
meter auf Maximal zu stellen.
Sensor ist eingestellt und betriebsbereit. Zur Überprüfung der Funktion
Grak C und G heranziehen. Verhält sich der Schaltausgang nicht
gemäß Grak C, Einsatzbedingungen prüfen.
Siehe Abschnitt Fehlerdiagnose.
Zusatzfunktionen
Alarmausgang: Der Sensor (WSE27-3) verfügt über einen Vorausfall-
meldeausgang (Alarm im Anschlussschema [B]), der meldet, wenn der
Sensor nur noch eingeschränkt betriebsbereit ist.
Mögliche Ursachen: Verschmutzung des Sensors, Sensor ist dejustiert.
WSE27-F2631: PNP: Alarm → M Signalreserve > 50% LOW, -3E2631: NPN:
Alarm → L+ Signalreserve > 50% HIGH. Dabei blinkt die Anzeige-LED.
Zeitarten: WSE27-3F, E, R: t0 = keine Zeitverzögerung, t1 = Zeitverzögerung,
t2 = Zeitverzögerung; für -3R gilt: 0 = Relais inaktiv, 1 = Relais aktiv. Zeit-
stufen-Wahlschalter, einstellbar am Gerät gemäß A.
Zeitstufen: WSE27-3F: < 0,5 s: 0,02 ... 0,5 s oder
> 0,5 s: 0,5 ... 10 s einstellbar.
WSE27-3R: 0,5 bis 10 s einstellbar.
Testeingang: Der Sensor WSE27-3 verfügt über einen Testeingang („TE“ im
Anschlussschema [B]), mit dem die ordnungsgemäße Funktion des Sensors
überprüft werden kann: Bei Verwendung von Leitungsdosen mit LED-Anzei-
gen ist darauf zu achten, dass der TE entsprechend belegt ist.
Es darf sich kein Objekt zwischen Sender und Empfänger benden, Test-
eingang aktivieren (siehe Anschlussschema [B], TE nach 0 V). Sende-LED
wird abgeschaltet, bzw. es wird simuliert, dass ein Objekt erkannt wird.
Zur Überprüfung der Funktion Grak C und G heranziehen. Verhält sich der
Schaltausgang nicht gemäß Grak C, Einsatzbedingungen prüfen. Siehe
Abschnitt Fehlerdiagnose.
WSE27-3xxx5x: Mit statischer Frontscheibenheizung für den Einsatz bei
langsamen Temperaturänderungen im Bereich von +5 °C ... +15 °C.
Geräte mit besonderen Merkmalen
WSE27-3P2430S01: Ohne Testeingang.
WSE27-3F2431S04: Schaltabstand max. 0 ... 30 m, t1 = 30 ms oder 70 ms
einstellbar, Schaltfrequenz: 2.500 Hz, Ansprechzeit ≤ 200 μs, Durchgangs-
bohrungen mit Metallhülsen.
WSE27-3P2410S03: Schaltabstand max. 0 ... 45 m, Schaltfrequenz: 300 Hz,
Ansprechzeit ≤ 1,7 ms, Lichteckdurchmesser ca. 3,7 m in 25 m.
Fehlerdiagnose
Tabelle I zeigt, welche Maßnahmen durchzuführen sind, wenn die Funktion
des Sensors nicht mehr gegeben ist.
Demontage und Entsorgung
Die Entsorgung des Sensors hat gemäß den länderspezisch anwendbaren
Vorschriften zu erfolgen. Für die enthaltenen Wertstoe (insbesondere
Edelmetalle) ist im Rahmen der Entsorgung eine Verwertung anzustreben.
Wartung
SICK-Sensoren sind wartungsfrei.
Wir empfehlen, in regelmäßigen Abständen
– die optischen Grenzächen zu reinigen
– Verschraubungen und Steckverbindungen zu überprüfen
Veränderungen an Geräten dürfen nicht vorgenommen werden.
Irrtümer und Änderungen vorbehalten. Angegebene Produkteigenschaften
und technische Daten stellen keine Garantieerklärung dar.
dunkelschaltend hellschaltend
2 1 t = 1
1 2 t = 2
+ (L+)
not connected
- (M)
brn
wht
blu
1
2
3
Test
blk
4
+ (L+)
Q
- (M)
brn
wht
blu
blk
1
2
3
Q
4
+ (L+)
- (M)
not connected
1
2
3
not connected
4
not connected
5
Test
6
brn
blu
gra
+ (L+)
- (M)
not connecte
d
1
2
3
Q
4
Q
5
Alarm
6
brn
blu
blk
wht
gra
+ (L+)
- (M)
not connected
1
2
3
not connected
4
not connected
5
Test
6
not connected
7
+ (L+)
- (M)
not connecte
d
1
2
3
Q
4
Q
5
not connecte
d
6
not connecte
d
7
1
2
L1
N
not connected
1
2
3
not connected
4
not connected
5
not connected
6
brn
blu
L1
N
brn
blu
gra
blk
wht
1
2
not connected
6
3
4
5
1000
10000
100
10
1
Sensing range
Sensing range typ. max.
m
(feet)
5
(16.40)
10
(32.81)
15
(49.21)
20
(65.62)
25
(82.02)
30
(98.43)
35
(114.83)
40
(131.23)
Distance in m (feet)
operating reserve
y
x
Anzeige-LED / Fehlerbild /
LED indicator / fault pattern
Ursache /
Cause
Maßnahme /
Measures
grüne LED leuchtet nicht /
green LED does not light up
keine Spannung oder Spannung unterhalb der
Grenzwerte /
No voltage or voltage below the limit values
Spannungsversorgung prüfen, den gesamten
elektrischen Anschluss prüfen (Leitungen und
Steckerverbindungen) /
Check the power supply, check all electrical
connections (cables and plug connections)
grüne LED leuchtet nicht /
green LED does not light up
Spannungsunterbrechungen /
Voltage interruptions
Sicherstellen einer stabilen Spannungsversorgung ohne Unter
-
brechungen /
Ensure there is a stable power supply without interruptions
grüne LED leuchtet nicht /
green LED does not light up
Sensor ist defekt /
Sensor is faulty
Wenn Spannungsversorgung in Ordnung ist, dann Sensor
austauschen /
If the power supply is OK, replace the sensor
grüne LED leuchtet, kein Ausgangssignal bei
Objektdetektion /
green LED lights up, no output signal when object
is detected
Testeingang (TE) ist nicht korrekt angeschlossen /
Test input (TI) is not connected properly
Siehe Hinweis für Anschluss des TE /
See the note on connecting the TI
gelbe LED blinkt, wenn Alarm vorhanden dann
entsprechendes Ausgangssignal beachten /
Yellow LED flashes; if Alarm is present then take
note of the corresponding output signal
Sensor ist noch betriebsbereit, aber die Betriebs
-
be–dingungen sind nicht optimal /
Sensor is still ready for operation, but the opera-
ting conditions are not ideal
Betriebsbedingungen prüfen: Lichtstrahl (Lichtfleck) vollstän-
dig auf den Empfänger ausrichten / Reinigung der optischen
Flächen / Empfindlichkeit (Potentiometer) neu einstellen / falls Po-
tentiometer auf max. Schalt–abstand eingestellt: Abstand zwischen
Sender und Empfänger verringern und mit Grafik H überprüfen /
Schaltabstand überprüfen und ggf. anpassen, siehe Grafik H.
/
Check the operating conditions: Fully align the beam of light (light
spot) with the receiver. / Clean the optical surfaces. / Readjust
the sensitivity (potentiometer) /
If the potentiometer is set to the max. sensing range: Reduce the
distance between the sender and the receiver, and check against
graphic H. / Check sensing range and adjust if necessary; see
graphic H.
gelbe LED leuchtet, kein Objekt im Strahlengang /
yellow LED lights up, no object in the path of the
beam
Der Lichtstrahl einer Einweg-Lichtschranke trifft
auf den Empfänger einer anderen (benachbarten)
Einweg-Lichtschranke /
The beam of light of a photoelectric through-be
-
am sensor hits the receiver of another (neigh-
boring) photoelectric through-beam sensor
Bei jeder zweiten Einweg-Lichtschranke die Anordnung von Sender
und Empfänger tauschen, bzw. genügend Abstand zwischen den
Einweg-Lichtschranken einhalten. /
Swap the sender and receiver arrangement at every second pho-
toelectric through-beam sensor and ensure that there is sufficient
distance between the through-beam photoelectric sensors
WSE27-3xxxxx -3E26xx / -3F26xx R
1)
/ S
Distanza di commutazione Distancia de conmutación
开关距离 最大検出範囲
Расстояние срабатывания 0 ... 25 m 0 ... 25 m 0 ... 25 m
Distanza max. di commutazione Distancia de conmutación max.
最大开关距离 最大検出範囲
Расстояние срабатывания, макс. 0 ... 35 m 0 ... 35 m 0 ... 35 m
Diametro punto luminoso / distanza Diámetro del punto luminoso / distancia
光斑直径 / 距离 光点のスポット径 / 距離 Диаметр светового пятна / расстояние 600 mm / 25 m 600 mm / 25 m 600 mm / 25 m
Tensione di alimentazione U
B
Tensión de alimentación U
B
供电电压 U
B
供給電圧 U
B
Напряжение питания U
B
DC 10 ... 30 V
2)
DC 10 ... 30 V
2)
20 ... 250 V AC / DC
3)
Corrente di uscita I
max
Intensidad de salida I
max
输出电流 I
max
出力電流 I
max
Выходной ток I
max
100 mA 100 mA 4 A @ 250 V AC, 4 A @24 V DC,
0.125 A @ 250 V DC
4)
10)
Frequenza di commutazione Frecuencia de conmutación
开关频率 スイッチング周波数
Частота переключения 1,000 Hz
5)
1,000 Hz
5)
10 Hz
5)
Tempo di reazione Tiempo de respuesta
响应时间 応答時間
Время отклика ≤ 0.5 ms
6)
≤ 0.5 ms
6)
≤ 10 ms
6)
Tipo di protezione Tipo de protección
防护类型 保護等級
Класс защиты IP 67 IP 65 IP 65
Classe di protezione Clase de protección
防护等级 保護クラス
Класс защиты
7)
7)
8)
Commutazioni di protezione Circuitos de protección 保护电路 回路保護 Схемы защиты A, B, C
9)
A, B, C
9)
A, C
9)
Temperatura ambientale di funzionamento Temperatura ambiente de servicio
工作环境温度
周辺温度
(作動中) Диапазон рабочих температур -40°C ... +60 °C -40°C ... +60 °C -40°C ... +60 °C
10)
1)
I contatti di uscita relè sono separati dalla tensione di alimentazione da un isolamento
base di 3 mm.
2)
Valori limite; ondulazione residua max. 5 V
SS
,
corrente nominale connettore maschio: I
N
= 4A
3)
Valori limite; corrente nominale connettore maschio: I
N
= 4A
4)
Categoria d‘uso: AC-15. DC-13 (EN 60947-1)
5)
Con rapporto chiaro / scuro 1:1
6)
Durata segnale con carico ohmico
7)
Tensione nominale di isolamento U
i
= CC 50 V, categoria di sovratensione II
8)
Tensione nominale di isolamento U
i
= CA 250 V, categoria di sovratensione II
9)
A = U
B
-Allacciamenti protetti dall‘inversione di polarità
B = entrate e uscite protette da polarità inversa
C = Soppressione impulsi di disturbo
1)
Los contactos de salida de relé se encuentran aislados de la tensión de alimentación por
medio de un aislamiento básico de 3 mm.
2)
Valores límite;
ondulación residual max. 5 V
SS
,
corriente nominal del conector macho: I
N
= 4A
3)
Valores límite; corriente nominal del conector macho: I
N
= 4A
4)
Categoría de uso AC-15. DC-13 (EN 60947-1)
5)
Con una relación claro / oscuro de 1:1
6)
Duración de la señal con carga óhmica
7)
Tensión nominal de aislamiento U
i
= CC 50 V, categoría de sobretensión II
8)
Tensión nominal de aislamiento U
i
= CA 250 V, categoría de sobretensión II
9)
A = U
B
protegidas contra polarización inversa
B = Entradas y salidas protegidas contra polarización incorrecta
C = Supresión de impulsos parásitos
1)
利用 3 mm 的基本绝缘装置隔离继电 器输出触点和供电电压。
2)
极限值;最大余波 5 V
SS
,
额定电流插头:I
N
=4A
3)
极限值; 额定电流插头:I
N
=4A
4)
工作等级: AC-15. DC-13 (EN 60947-1)
5)
明暗比为 1:1
6)
信号传输时间(电阻负载时)
7)
額定絕緣電壓 U
i
= DC 50 V, 过电压类别 II
8)
額定絕緣電壓 U
i
= AC 250 V, 过电压类别 II
9)
A = U
B
接口(已采取反极性保护措施)
B = 具有反极性保护的输入端和输出端
C = 抑制干扰脉冲
1)
リレー出力接点は供給電圧から 3 mm の基本絶縁材で分離されていま
す。
2)
限界値;残留リップルは最大 5 V
SS
、 
オスコネクタ定格電流: I
N
= 4A
3)
限界値; オスコネクタ定格電流: I
N
= 4A
4)
使用カテゴリ: AC-15. DC-13 (EN 60947-1)
5)
ライト / ダークの比率 1:1
6)
負荷のある信号経過時間
7)
定格絶縁電圧 U
i
= DC 50 V, 過電圧カテゴリー II
8)
定格絶縁電圧 U
i
= AC 250 V, 過電圧カテゴリー II
9)
A = U
B
接続は逆接保護
B = 入力および出力は逆接保護
C = 干渉抑制
1)
Выходные релейные контакты отделены от напряжения питания базисной изоляцией
толщиной 3 мм.
2)
Предельные значения; остаточная волнистость макс. 5 B
SS
,
номинальный ток штекер: вход = 4A
3)
Предельные показатели; номинальный ток штекер: вход = 4A
4)
категория применения: AC-15. DC-13 (EN 60947-1)
5)
Соотношение светлых и темных участков изображения 1:1
6)
Продолжительность сигнала при омической нагрузке
7)
Номинальное напряжение изоляции U
i
= DC 50 V, категория перенапряжения II
8)
Номинальное напряжение изоляции U
i
= AC 250 V,
категория перенапряжения II
9)
A = U
B
-подключения с защитой от перепутывания полюсов
B = входы и выходы с защитой от перепутывания полюсов
C = подавление импульсных помех
WSE27-3xxxxx -3E26xx / -3F26xx R
1)
/ S
Sensing range Schaltabstand Portée Distância de comutação 0 ... 25 m 0 ... 25 m 0 ... 25 m
Sensing range max. Schaltabstand max. Portée max. Distância de comutação max. 0 ... 35 m 0 ... 35 m 0 ... 35 m
Light spot diameter / distance Lichtfleckdurchmesser / Entfernung Diamètre spot / distance Diâmetro do ponto de luz / distância 600 mm / 25 m 600 mm / 25 m 600 mm / 25 m
Supply voltage U
B
Versorgungsspannung U
B
Tension d'alimentation U
B
Tensão de alimentação U
B
DC 10 ... 30 V
2)
DC 10 ... 30 V
2)
20 ... 250 V AC / DC
3)
Output current I
max
Ausgangsstrom I
max
Courant de sortie I
max
Corrente de saída I
max
100 mA 100 mA 4 A @ 250 V AC, 4 A @24 V DC,
0.125 A @ 250 V DC
4)
10)
Switching frequency Schaltfrequenz Fréquence de commutation Frequência de comutação 1,000 Hz
5)
1,000 Hz
5)
10 Hz
5)
Max. response time Ansprechzeit max. Temps de réponse max. Tempo de resposta ≤ 0.5 ms
6)
≤ 0.5 ms
6)
≤ 10 ms
6)
Enclosure rating Schutzart Indice de protection Tipo de proteção IP 67 IP 65 IP 65
Protection class Schutzklasse Classe de protection Classe de proteção
7)
7)
8)
Circuit protection Schutzschaltungen Protections électriques Circuitos de proteção A, B, C
9)
A, B, C
9)
A, C
9)
Ambient operating temperature Betriebsumgebungstemperatur Température de service Temperatura ambiente de funcionamento -40°C ... +60 °C -40°C ... +60 °C -40°C ... +60 °C
10)
1)
Relay contacts are separated from the supply voltage by a basic isolation
of 3 mm.
2)
Limit value; residual ripple max. 5 V
SS
,
male connector rated current: I
N
= 4A
3)
Limit values; male connector rated current: I
N
=4A
4)
Utilization category: AC-15. DC-13 (EN 60947-1)
5)
With light / dark ratio 1:1
6)
Signal transit time with resistive load
7)
Rated insulation voltage U
i
= DC 50 V, overvoltage category II
8)
Rated insulation voltage U
i
= AC 250 V, overvoltage category II
9)
A = U
B
-connections reverse polarity protected
B = inputs and output reverse-polarity protected
C = Interference suppression
1)
Relaisausgangskontakte sind von der Versorgungsspannung durch eine
Basisisolation von 3 mm getrennt.
2)
Grenzwerte; Restwelligkeit max. 5 V
SS
,
Nennstrom Stecker: I
N
=4 A.
3)
Grenzwerte; Nennstrom Stecker: I
N
=4 A
4)
Gebrauchskategorie: AC-15. DC-13 (EN 60947-1)
5)
Mit Hell- / Dunkelverhältnis 1:1
6)
Signallaufzeit bei ohmscher Last
7)
Bemessungsisolationsspannung U
i
= DC 50 V, Überspannungsschutz II
8)
Bemessungsisolationsspannung U
i
= AC 250 V, Überspannungsschutz II
9)
A = U
B
-Anschlüsse verpolsicher
B = Ein- und Ausgänge verpolsicher
C = Störimpulsunterdrückung
1)
Les contacts de sortie de relais sont isolés de la tension d‘alimentation par
une isolation de base de 3 mm.
2)
Valeurs limites;
ondulation résiduelle max. 5 V
CC
,
courant nominal du connecteur : I
N
= 4 A
3)
Valeurs limites; courant nominal du connecteur : I
N
= 4 A
4)
Catégorie d’utilisation : AC-15. DC-13 (EN 60947-1)
5)
Pour un rapport clair / sombre de 1:1
6)
Temps de propagation du signal sur charge ohmique
7)
Tension d‘isolation U
i
= 50 V CC, catégorie de surtension II
8)
Tension d‘isolation U
i
= 250 V CA, catégorie de surtension II
9)
A = raccordements U
B
protégés contre les inversions de polarité
B = entrées et sorties protégées contre les inversions de polarité
C = Suppression des impulsions parasites
1)
Os contatos de saída de relé estão separados da tensão de alimentação
por uma isolação de base de 3 mm.
2)
Valores limite; ondulação residual max. 5 V
SS
,
corrente nominal conector macho: I
N
=4A
3)
Valores-limite; corrente nominal conector macho: I
N
=4A
4)
Categoria de uso: AC-15. DC-13 (EN 60947-1)
5)
Com proporção sombra / luz 1:1
6)
Tempo de funcionamento do sinal com carga ôhmica
7)
Tensão nominal de isolamento U
i
= CC 50 V, categoria de sobretensão II
8)
Tensão nominal de isolamento U
i
= CA 250 V, categoria de sobretensão II
9)
A = conexões protegidas contra inversão de pólos U
B
B = Entradas e saídas protegidas contra polaridade inversa
C = Supressão de impulsos parasitas
10)
UL:
4A @ 250V AC, general use
4A @ 250V AC, resistive (NO)
3A @ 250V AC, resistive (NC)
4A @ 24V DC, NO, general use
3A @ 24V DC, NC, general use
R300
B300 (NO contacts only)
0 °C ... +60 °C
L+
M
Test
brn
blu
blk
not connected
wht
L+
Q
Q
brn
blk
wht
M
blu
-3x11xx
-3x12xx
-3x17xx
1 Optical axis sender /
Optikachse Sender
2 Optical axis receiver /
Optikachse Empfänger
3 Mounting hole Ø 5.2 mm (0.20) /
Befestigungsbohrung Ø 5.2 mm (0.20)
4 Status indicator LED green: power on /
Anzeige-LED grün: Spannungsversorgung an
5 Status indicator LED, yellow: Status of received light beam /
Anzeige-LED gelb: Status Lichtempfang
6 Time control /
Zeitsteuerung
7 Time delay selector switch /
Schalter zur Wahl der Zeitverzögerung
8 Sensitivity control /
Empndlichkeitssteuerung
WS
WS
WE
WE
WE
WS
A B
C
E F G H I
2006/42/EC
NO
SAFETY
SICK AG, Erwin-Sick-Strasse 1, D-79183 Waldkirch
1 Sender
2 Receiver
-------------------------------------------------------- 8010965.11NX 0519 COMAT ------------------------------------------------------
  • Page 1 1
  • Page 2 2

SICK SENSICK WSE27-3 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI