Extech Instruments MA140 is a compact and rugged True RMS AC mini clamp meter, designed for measuring AC current up to 300A. It features a non-contact voltage detector, data hold, backlight, inrush current mode, and low pass filter. The MA140 is suitable for electricians, technicians, and DIY enthusiasts for various electrical testing and troubleshooting applications, including measuring current in wires, detecting voltage presence, and capturing inrush currents of motors and appliances. Its compact size and easy-to-use interface make it ideal for field and benchtop use.

Extech Instruments MA140 is a compact and rugged True RMS AC mini clamp meter, designed for measuring AC current up to 300A. It features a non-contact voltage detector, data hold, backlight, inrush current mode, and low pass filter. The MA140 is suitable for electricians, technicians, and DIY enthusiasts for various electrical testing and troubleshooting applications, including measuring current in wires, detecting voltage presence, and capturing inrush currents of motors and appliances. Its compact size and easy-to-use interface make it ideal for field and benchtop use.

USERGUIDE
TrueRMS300AACMiniClampMeterwithNon
ContactVoltageDetector
ModelMA140
MA140enGB_V1.01/15
2
Introduction
ThankyouforselectingtheExtechMA140300AACTrueRMSMiniClampMeterwithNon Contact
VoltageDetector.TheMA140issmallinsizebutruggedinperformance.
TheMA140measuresACcurrentto300AandoffersaSmartDataHoldfeature,displayBacklight,
InrushCurrentmode,LowPass
Filtering(LPF),anda noncontactVoltDetectionfeaturethat
senseselectricalsourcessafely.
Thisdeviceisshippedfullytestedandcalibratedand,withproperuse,willprovideyearsofreliable
service.Pleasevisitourwebsite(www.extech.com)tocheckforthelatestversionofthisUser
Guide,ProductUpdates,ProductRegistration,andCustomerSupport.
SafetyInformationPleaseReadFirst
Toensurethesafeoperationandserviceofthemeter,followtheseinstructionsclosely.Failureto
observewarningscanresultinsevereinjury.
WARNINGS
WARNINGSidentifyhazardousconditionsandactionsthatcouldcauseBODILYHARMorDEATH.
IndividualprotectiveequipmentshouldbeusedifHAZARDOUSLIVEpartsintheinstallationwhere
measurementsaretobecarriedoutcouldbeaccessible.
Iftheequipmentisusedinamannernotspecifiedbythemanufacturer,theprotectionprovidedbythe
equipmentmaybeimpaired.
Toreducetheriskoffireorelectricshock,donotexposethisproducttorainormoisture.
Verifythemeteroperationbymeasuringaknownvoltage.Ifindoubt,havethemeterserviced.
Donotapplymorethantheratedvoltageasmarkedonthemeter.
Toavoidfalse
readingsthatcanleadtoelectricshockandinjury,replacebatteryassoonasthelow
batteryindicatorappears.
Donotusethemeterinoraroundexplosivegasorvapor.
Pleasekeepfingersandhandsbehindthefingerguards.
Donotexposemetertoextremesintemperature
orhighhumidity.
Deenergizetheinstallationundertestorwearsuitableprotectiveclothingwhenplacingorremoving
thecurrentclampfromatestsetup.
Donotapply/removethecurrentclampto/fromUNINSULATEDHAZARDOUSLIVEconductorswhichmay
causeelectricshock,electricburn,orarcflash.
MA140enGB_V1.01/15
3
CAUTIONS
CAUTIONSidentifyconditionsandactionsthatcouldcauseDAMAGEtothemeterorequipment
undertest.Donotexposethemetertoextremesintemperatureorhighhumidity.
SafetySymbolsthataretypicallymarkedonmetersandinstructions
Thissymbol,adjacenttoanothersymbol,indicatestheusermustrefertothe
manualforfurtherinformation.
Riskofelectricalshock
DonotapplyorremoveclampfromHAZARDOUSLIVEconductors
Equipmentprotectedbydoubleorreinforcedinsulation
Batterysymbol
ConformstoEUdirectives
Donotdiscardthisproductinhouseholdtrash.
ACmeasurement
DCmeasurement
Earthground
PERIEC1010OVERVOLTAGEINSTALLATIONCATEGORY
OVERVOLTAGECATEGORYI
EquipmentofOVERVOLTAGECATEGORYIisequipmentforconnectiontocircuitsinwhichmeasuresare
takentolimitthetransientovervoltagestoanappropriatelowlevel.
NoteExamplesincludeprotectedelectroniccircuits.
OVERVOLTAGECATEGORYII
EquipmentofOVERVOLTAGECATEGORYIIisenergyconsumingequipmenttobe
suppliedfromthefixed
installation.
NoteExamplesincludehousehold,office,andlaboratoryappliances.
OVERVOLTAGECATEGORYIII
EquipmentofOVERVOLTAGECATEGORYIIIisequipmentinfixedinstallations.
NoteExamplesincludeswitchesinthefixedinstallationandsomeequipmentforindustrialusewith
permanentconnectiontothefixedinstallation.
OVERVOLTAGE
CATEGORYIV
EquipmentofOVERVOLTAGECATEGORYIVisforuseattheoriginoftheinstallation.
NoteExamplesincludeelectricitymetersandprimaryovercurrentprotectionequipment
MA140enGB_V1.01/15
4
1
2
3
4
5
123 45
6
78
9
Description
MeterDescription
1. Transformercurrentjaw
2. FingerHandGuard
3. Jawopeningtrigger
4. LCDMultifunctiondisplay
5. Pushbuttoncontrols
Notethatthebatterycompartmentislocatedonbackofmeter
DisplayDescription
1. NonContactVoltDetecticon
2. MainDisplaydigits
3. InRushCurrentmode
4. LowPassFilter
5. DataHold
6. ACMeasurement
7. Amperes(current)
8. Batterystatusicon
9. Minus(negative)sign
ControlButtonDescription
Pressfor>2secondstoaccessInrushCurrentmode
PresstoaccessLowPassFiltermode
Presstoaccesscurrentmeasurementmode
PresstoaccessVoltagedetectmode
PresstoswitchDataHoldonoroff
PresstopowerONthemeter.Pressandhold>2secondsto
switchOFF
Presstotoggledisplaybacklightonandoff
MA140enGB_V1.01/15
5
Operation
CAUTIONS
ReadandunderstandalloftheSafetystatementslistedinthesafetysectionofthismanual
priortouse.
PoweringtheMeter
1. PressthePowerBacklightbutto ntopowerthemeter.Checkthebatteriesiftheunitfailsto
powerON.
2. PressandholdthePowerbuttonformorethan2secondstopowerOFFthemeter.
3. ThemeterhasanAutoPowerOFFfeature(APO)wherethemeterswitches
OFFafter20
minutesofinactivity.TodisableAPO,refertothenextsection.
Note:Themeterdisplaysthebatterycapacitywhenpoweringup.
DisableAutoPowerOFF
ThemeterwillautopowerOFFafter20minutesofinactivity.Todefeatthisfeature,followthe
stepsbelow.
1. WiththemeterOFF,pressandholdthe‘V’buttonand,whilecontinuingtoholdthe‘V’
button,pressthepowerbutton.
2. ThedisplaywillshowAOFF.
3. Release
allofthebuttons.
4. TheAutoPowerOFFfunctionwillnowbedisableduntilthenextcycleofpower.
DisplayBacklight
WiththemeterpoweredON,pressthebacklightbuttontoswitchthebacklightONorOFF.Note
thatexcessiveuseofthebacklightwillshortenthebatterylife.
MA140enGB_V1.01/15
6
ACCurrentMeasurements
WARNING:Donothandlethemeterabovethefinger/handguardbarrier.
CAUTION:ObserveCATIII600VwithrespecttoEarthGroundfortheJaw.
1. Pressthe‘A’buttontoaccesstheACCurrentmeasurementmode.TheAsymbolwillappear
onthedisplayinthelowerrighthandsideindicatingAmperes(Amps).
2. Pressthejawtriggertoopentheclampjaw.
3. Positiontheclamparoundonlyoneconductor.Seeaccompanyingdiagramsfor
correctand
incorrectuse.
4. Readthecurrentinthedisplay.Thedisplaywillindicatetheproperdecimalpointandvalue.
MA140enGB_V1.01/15
7
InrushCurrentMode
IntheInrushmodethemeterwaitsuntilatleast5Aisdetectedandthenstartsa100mssample
windowinwhichtocaptureaninrushcurrentRMSvalue.Refertoillustrationbelow.
1. PressandholdtheINRUSHbuttonfor>2secondstoaccesstheInrushCurrentmode.
2.
ThedisplaywillshowtheINRUSHicon.
3. Whenready,takeacurrentmeasurement.Themeterwillcapturethehighestreading
detectedduringa100mswindow.Notethatthe100mswindowdoesnotopenuntilatleast
5Aisdetected.
4. ToexittheInrushCurrentmodepresstheINRUSH
buttonagainmomentarily.TheINRUSH
iconwillswitchOFF.

100ms Sample Window
Measured Inrush
Sample time
trigger
Inrush
Button
Press
Current
Start Stop
T
hreshold
LowPassFilter
TheLowPassFiltermodeoffershighfrequencyrejectionwhenmeasuringVariableSpeedDrives.
TheLowPassFiltermodeoffersacutofffrequencyof160Hz(approx.)withanattenuation
characteristicof‐24dbperoctave(approx.).
1. MomentarilypresstheLPFbuttontoaccesstheLPFmode
2. TheLPFdisplay
iconisshownonthedisplayintheLPFmode
3. PresstheLPFbuttonagaintoexittheLPFmode,theLPFiconwillswitchOFF
MA140enGB_V1.01/15
8
VoltDetectionFeature
The meter’s audible beeper triggers and the display shows
dashes when the meter senses an electrical voltage field. The
higher the electrical field strength the greater the number of
dashesdisplayedandthefastertherateoftheaudiblebeeps.
If the meter does not emit a tone or display dashes
in this
mode,thereisstillthepossibilitythatvoltageispresent.Please
usecaution.
1. Press the ‘V’ button to access the NonContact Voltage
Detectmode.
2. Note the voltage detection display icons as shown in the
Descriptionsectionofthisguide.
3. Placethemeterneara
sourceofelectricalenergy.Thetip
oftheclampoffersthehighestsensitivity.
4. Notetheaudiblebeepingandthedashdisplays.
SmartDataHold
TofreezetheLCDmeterreading,presstheHOLDbutton.Whiledataholdisactive,the HOLD
displayiconappearsontheLCD.PresstheHOLDbuttontoreturntonormaloperation.The
HOLDiconwillswitchOFF.
Themeter’sbeeperwillsoundandthedisplaywillflashcontinuouslyifthe
detectedsignalis50
countsgreaterthantheheldreading.
MA140enGB_V1.01/15
9
Maintenance
WARNING:Toavoidelectricalshock,disconnectthemeterfromanycircuitandturnOFF
themeterbeforeopeningthecase.Donotoperatewithanopencase.
CleaningandStorage
Periodicallywipethecasewithadampclothandmilddetergent;donotuseabrasivesorsolvents.
Ifthemeterisnottobeusedfor60daysormore,removethebatteriesandstorethemseparately.
BatteryReplacement
1. RemovethePhillipsheadscrewatthelowerbackofthemeter.
2. Openthebatterycompartment.
3. ReplacethetwoLR44batteriesobservingcorrectpolarity.
4. Reassemblethemeterbeforeuse.
5. Safety:Pleasedisposeofbatteriesresponsibly;neverdisposeofbatteriesinafire,batteries
mayexplode
orleak;nevermixbatterytypes,installnewbatteriesofthesametype.
Neverdisposeofusedbatteriesorrechargeablebatteriesinhouseholdwaste.
Asconsumers,usersarelegallyrequiredtotakeusedbatteriestoappropriate
collectionsites,theretailstorewhere thebatterieswerepurchased,or
whereverbatteriesaresold.
Disposal:Donotdisposeofthisinstrumentinhouseholdwaste.Theuseris
obligatedtotakeendoflifedevicestoadesignatedcollectionpointforthe
disposalofelectricalandelectronicequipment.
MA140enGB_V1.01/15
10
Specifications
ELECTRICALSPECIFICATIONS
Function Range Resolution Accuracy(ofreading)50/60Hz
ACCurrent
60.00A 0.01
±(2.0%+5digits)
300.0A 0.1
Allspecificationsarevalidfrom10%to100%ofeachrange
TheLCDdisplays0countswhenthereading<10counts
LowPassFilter
(LPF)
60.00A 0.01
±(3.5%+5digits)
300.0A 0.1
Allspecificationsarevalidfrom10%to100%ofeachrange
TheLCDdisplays0countswhenthereading<10counts
Cutofffrequency(3dB):160Hz
Attenuationcharacteristic:‐24dbperoctave(approximately)
Function Range Resolution Accuracy(ofreading)
InrushCurrent
300.0A 0.1 ±(3.5%+5digits)
Integrationtime:100ms
Triggercurrent(threshold):5A
VoltDetection
80V~600VAC n/a n/a
Thetipoftheclampofferstheoptimumsensitivity
Notes:
Clamppositionerror:±2%ofreading.Maximum±4%nearclampjawopening.
AdjacentConductionInfluenceofJaw:<0.08A/A
Accuracyisgivenas±(%ofreading+leastsignificantdigit)at23C±3Cwithrelative
humiditylowerthan80%.Accuracyisspecifiedforaperiod
ofoneyearaftercalibration.
ACAspecificationsareforACCoupled,TrueRMS.Fornonsinusoidalwaveforms,additional
accuracyCrestFactor(C.F.)considerationsexistasdetailedbelow:
Add3.0%forC.F.1.0~2.0
Add5.0%forC.F.2.0~2.5
Add7.0%forC.F.2.5~3.0
MA140enGB_V1.01/15
11
GENERALSPECIFCATIONS
Display 6000countMultiFunctionLCD
Overrangeindication “OL”orOL”isdisplayed
Conversionrate 2updatespersecond
Maximumconductorsize 22mm(0.87”)indiameter
Lowbatteryindication isdisplayed.Meteralsodisplaysavailablebatterypowerat
startup
AutoPowerOFF After20minutes(canbedisabled)
OperatingTemperatureandHumidity
0~30C(32~86F);80%RHmaximum
30~40C(86~104F);75%RHmaximum
40~50C(104~122F);45%RHmaximum
StorageTemperatureandHumidity
20~60C(4
~140F);80%RHmaximum
TemperatureCoefficient 0.2xspecifiedaccuracy/C,<20C(68F),>26C(79F)
OperatingAltitude 2000m(6562ft.)
Batterypower (2)LR441.5Vbatteries(batterylife50hourstypical)
Weight 140g(4.9oz.)
Dimensions 60x147x31.5mm(2.4x
5.8x1.2”)
SafetyStandards Forindooruseandinaccordancewiththerequirementsfordouble
insulationtoEN610101,EN610102030,EN610102032,EN61326
1;EN610101OvervoltageCATIII600V,PollutionDegree2
ShockandVibration SinusoidalvibrationMILPRF28800FforaClassII
instrument
DropProtection 1.2m(4’)dropontohardwoodorconcreteflooring
Copyright©2015FLIRSystems,Inc.
Allrightsreservedincludingtherightofreproductioninwholeorinpartinanyform
www.extech.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11

Extech Instruments MA140 User manual

Category
Measuring, testing & control
Type
User manual

Extech Instruments MA140 is a compact and rugged True RMS AC mini clamp meter, designed for measuring AC current up to 300A. It features a non-contact voltage detector, data hold, backlight, inrush current mode, and low pass filter. The MA140 is suitable for electricians, technicians, and DIY enthusiasts for various electrical testing and troubleshooting applications, including measuring current in wires, detecting voltage presence, and capturing inrush currents of motors and appliances. Its compact size and easy-to-use interface make it ideal for field and benchtop use.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI