  • Hello! I am an AI chatbot trained to assist you with the Danfoss Termix HD MIX Compact 28 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
TermixHDMIXCompact28
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.2Start-up..............................................................6
4.3Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
6.0Controls..........................................................10
6.1Heatingcircuit......................................................10
6.2Other.................................................................14
6.3Maintenance........................................................15
7.0Troubleshooting..............................................16
7.1Troubleshootingingeneral......................................16
7.2TroubleshootingHE...............................................16
7.3Disposal.............................................................17
8.0Declaration......................................................19
8.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
1
OperatingGuideTermixHDMIXCompact28
2.0Functionaldescription
Districtheatingsubstationfordirectheatingwithmixingloop.
Application
TheTermixHDMIXCompact28isacompletesolutionfor
spaceheatingwithoptimalsafety,efcientenergytransfer,
service-friendlyconstructionandacompactdesign.
Districtheating(DH)
Thedistrictheatingcircuitisprefabricatedwithaowcontroller
withintegratedcontrolvalve,thermometersandballvalves.
Heating(HE)
Theheatingcircuitconsistsofthermometers,ballvalves,drain
valve,airvalveandcirculationpump.Theheatingtemperaturecan
becontrolledthermostaticallyorbyanelectroniccontrollerwith
anoutdoortemperaturesensor.
2
DEN-GT
VI.GP .E2.02/LUK42860
DanfossDistrictEnergy
OperatingGuideTermixHDMIXCompact28
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
3
OperatingGuideTermixHDMIXCompact28
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
Connectionsizes:
DH+HE:
G1”(int.thread)
Dimensions(mm):
Withoutcover:
H970xW620xD420
Withcover:
H970xW640xD522
Weight(approx.):50kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4
DEN-GT
VI.GP .E2.02/LUK42860
DanfossDistrictEnergy
OperatingGuideTermixHDMIXCompact28
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
5
OperatingGuideTermixHDMIXCompact28
4.2Start-up
Start-up,Heatingwithmixingloop
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Ifthesystemoperatesinaccordancewithdesign,itcanbeput
toregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderoorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderoorheatingcontroller.Thepumpmustbestoppedif
allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
6
DEN-GT
VI.GP .E2.02/LUK42860
DanfossDistrictEnergy
OperatingGuideTermixHDMIXCompact28
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
7
OperatingGuideTermixHDMIXCompact28
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
F
Electroniccontroller
14
Sensorpocket,energymeter
29
2-waymotorizedvalve
2
Singlecheckvalve
20
Filling/drainvalve
31
Differentialpressurecontroller
9
Strainer
25
Pressuregaugewithballvalve
41
Fittingpiece,energymeter
10
Circulatorpump
27
Actuator,HE
48
Airvent,manual
8
DEN-GT
VI.GP .E2.02/LUK42860
DanfossDistrictEnergy
OperatingGuideTermixHDMIXCompact28
5.2Schematicdiagram
DH
Supply
HE
Supply
DH
Return
HE
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
F
Electroniccontroller
16
Outdoorsensor
27
Actuator
1
Ballvalve
18
Thermometer
29
2-waymotorizedvalve
2
Singlecheckvalve
19
Surfacesensor
31
Differentialpressurecontroller
9
Strainer
20
Filling/drainvalve
41
Fittingpiece,energymeter
10
Circulationpump
24
Deliveredloosewithunit
48
Airvent,manual
14
Sensorpocket,energymeter
25
Pressuregaugewithballvalve
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
120°C
Soundlevel:55dB
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
9
OperatingGuideTermixHDMIXCompact28
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsouttheuctuationsin
pressurearrivingfromthedistrictheatingnetwork.Theoperating
pressureinthesubstationisthusheldsteady.
6.1.2HEtemperaturecontrol
TheHEowtemperatureintheheatingcircuitiscontrolledbythe
HEtemperaturecontroller.
6.1.3AVTBcontroller(30–100°)
Thetemperaturesettingisasfollows:
1=35°C
2=55°C
3=75°C
4=95°C
5=100°C
Thevaluesareintendedasaguide.
Thermostaticcontrol
ThetemperatureoftheHEowlineisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
10
DEN-GT
VI.GP .E2.02/LUK42860
DanfossDistrictEnergy
OperatingGuideTermixHDMIXCompact28
6.1.4Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingowcontrollerwithintegratedcontrol
valve.Thecontrollercloseswhensetmax.owisexceededand
canbeusedincombinationwithDanfosselectricalactuatorswith
orwithoutsafetyfunction.Springreturnmotorcanbeusedas
safetyfunctionbypowerfailure.
6.1.5Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point
controls.Spring-returnactuatorscanbeusedtoprovidesafety
shut-offintheeventofpowerfailure.
6.1.6Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith
manufacturer´sinstructions.
Wheretheroomtemperatureiscontrolledbyradiatorthermostats,
itisrecommendedthatthermostatsbesetforminimum
temperatureineachroom.
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
11
OperatingGuideTermixHDMIXCompact28
6.1.7Outdoortemperaturesensor(ESMT)
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
6.1.8CirculatorpumpUPM3
UPM3Pumpscanbecontrolledinconstantpressure,proportional
pressureorconstantspeedmodedenedbythemeansofasmart
userinterface.
Thevariablespeedmodulatingmodesallowthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
12
DEN-GT
VI.GP .E2.02/LUK42860
DanfossDistrictEnergy
OperatingGuideTermixHDMIXCompact28
6.1.9GrundfosUPM3AUTOLinstructions
Controlmode
Youcanswitchfromtheperformanceviewtothesettingsviewbypressingthepushbutton.Thesettingsviewshowswhichmode
controlsthecirculator.After2seconds,thedisplayswitchesbacktoperformanceview.
Ifyoupressthebuttonfor2to10seconds,theuserinterfaceswitchesto"settingselection"iftheuserinterfaceisunlocked.Youcan
changethesettingsastheyappear.Theselectionofthecontrolmodedependsonthesystemtypeandtheallocationofpressurelosses.
Ifyoupressthekeylockformorethan10seconds,youcantogglebetweenenabling/disablingthekeylockfunction.
Function
Recommendedfor
Green
YellowYellowYellowYellow
Proportionalpressure1
1-pipesystems
µµ
Proportionalpressure2
µµµ
Proportionalpressure3
2-pipesystems
µµµµ
Constantpressure1
Underoorheating
µµ
Constantpressure2
µµµ
Constantpressure3
µµµµ
ConstantCurve1
µµµ
ConstantCurve2
µµµµ
ConstantCurve3
µµµµµ
ConstantCurveMax.
µµµµ
Operationstatus
Function
Recommendedfor
Green
YellowYellowYellowYellow
Standby**OnlyPWMcontrolled
µ
0%P125%
µµ
25%P150%
µµµ
50%P175%
µµµµ
75%P1100%
µµµµµ
Alarmstatus
Function
Recommendedfor
RedYellowYellowYellowYellow
Blocked
µµ
Supplyvoltagelow
µµ
Electricalerror
µµ
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
13
OperatingGuideTermixHDMIXCompact28
6.2Other
6.2.1Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturer’sinstructions.
6.2.2Fittingpiece
Thesubstationisequippedwithattingpieceforenergymeter.
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater
onthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththeenergymeter.Do
notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand
tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
14
DEN-GT
VI.GP .E2.02/LUK42860
DanfossDistrictEnergy
OperatingGuideTermixHDMIXCompact28
6.3Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
15
OperatingGuideTermixHDMIXCompact28
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingHE
ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
(radiatorcircuit).
Cleangate/strainer(s).
ThelterintheenergymeteronDHcircuit
clogged.
Cleanthelter(afterconsultingtheDH
plantoperator).
Defectiveorwronglyadjusteddifferential
pressurecontroller.
Checktheoperationofthedifferential
pressurecontrollercleanthevalveseatif
required.
Sensordefectiveorpossiblydirtinthe
valvehousing.
Checktheoperationofthethermostat
cleanthevalveseatifrequired.
Automaticcontrols,ifany,wronglysetor
defective-possiblypowerfailure.
Checkifthesettingofthecontroller
iscorrectseeseparateinstructions.
Checkthepowersupply.Temporary
settingofmotortomanual”controlsee
instructionsonautomaticcontrols.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
thatitturns.Checkifthereisairtrappedin
thepumphousingseepumpmanual.
Thepumpissetattoolowspeedof
rotation.
Setthepumpathigherspeedofrotation.
Pressuredropthepressuredropon
theradiatorcircuitshowslowerthan
recommendedoperatingpressure.
Fillwateronthesystemandcheckthe
functioningofthepressureexpansion
vesselifrequired.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperature
adjustedtoolow.
Adjustaccordingtoinstructions.
Defectiveradiatorvalves.
Checkreplace.
Unevenheatdistributioninbuilding
becauseofincorrectlysetbalancingvalves,
orbecausetherearenobalancingvalves.
Adjust/installbalancingvalves.
Diameterofpipetosubstationtoosmallor
branchpipetoolong.
Checkpipedimensions.
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
16
DEN-GT
VI.GP .E2.02/LUK42860
DanfossDistrictEnergy
OperatingGuideTermixHDMIXCompact28
DHsupplytemperaturetoohigh.
Wrongsettingofthermostatorof
automaticcontrols,ifany.
Adjustautomaticcontrols,see
instructionsforautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callautomaticcontrolsmanufactureror
replacetheregulator.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
DHsupplytemperaturetoolow.
Wrongsettingofautomaticcontrols,ifany.
Adjustautomaticcontrolsseeinstructions
forautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callinautomaticcontrolsmanufactureror
replacecontroller.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
Wrongplacement/ttingofoutdoor
temperaturesensor.
Adjustlocationofoutdoortemperature
sensor.
Strainerclogged.Cleangate/strainer.
ToohighDHreturntemperature.
Toosmallheatingsurface/toosmall
radiatorscomparedtothetotalheating
requirementofthebuilding.
Increasetotalheatingsurface.
Poorutilizationofexistingheatingsurface.
Defectivesensoronself-actingthermostat.
Makesuretheheatisdistributedevenly
acrossthefullheatingsurfaceopenall
radiatorsandkeeptheradiatorsinthe
systemfromheatingupatthebottom.It
isextremelyimportanttokeepthesupply
temperaturetotheradiatorsaslowas
possible,whilemaintainingareasonable
levelofcomfort.
Thesystemissinglepipeloop.
Thesystemshouldfeatureelectronic
controlsaswellasreturnsensors.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Ventthesystem.
Defectiveorincorrectlysetradiator
valve(s).Singlepipeloopsystemsrequire
specialone-piperadiatorvalves.
Checkset/replace.
Dirtinthemotorizedvalveorinthe
differentialpressurecontroller.
Checkcleanout.
Defectivemotorizedvalve,sensoror
automaticcontroller.
Checkreplace.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Noiseinsystem.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Heatloadtoohigh.
Defectivemotorizedvalve,sensoror
electroniccontroller.
Checkreplace.
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
17
OperatingGuideTermixHDMIXCompact28
18
DEN-GT
VI.GP .E2.02/LUK42860
DanfossDistrictEnergy
OperatingGuideTermixHDMIXCompact28
8.0Declaration
8.1Declarationofconformity
Catégorie0avecéquipementélectrique
DanfossDistrictEnergy
VI.GP .E2.02/LUK42860
DEN-GT
19
OperatingGuideTermixHDMIXCompact28
ProducedbyDanfossA/S©03/2017
/