Eaton NRX Series is a reliable and versatile secondary terminal block alignment bracket designed for use with NRX Drawout Circuit Breakers. Its primary function is to provide proper alignment and separation of individual terminal blocks during the levering (racking) process, ensuring secure and efficient connections. This bracket is crucial for maintaining accurate terminal block placement and preventing misalignment, which can compromise the integrity of electrical circuits.

Eaton NRX Series is a reliable and versatile secondary terminal block alignment bracket designed for use with NRX Drawout Circuit Breakers. Its primary function is to provide proper alignment and separation of individual terminal blocks during the levering (racking) process, ensuring secure and efficient connections. This bracket is crucial for maintaining accurate terminal block placement and preventing misalignment, which can compromise the integrity of electrical circuits.

Effective June 2014
IL0131065ENH01
Instructional Leaet IL0131065EN
Installation/Removal Instructions
for Series NRX Drawout Secondary
Terminal Block Alignment Bracket
WARNING
(1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO
WORK ON THE EQUIPMENT.
(2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A
CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION.
(3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO
THE DISCONNECT POSITION.
(4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION
AND MECHANISM SPRINGS DISCHARGED. FAILURE
TO FOLLOW THESE
STEPS FOR ALL PROCEDURES
DESCRIBED IN THIS INSTRUCTION LEAFLET
COULD RESULT IN DEATH, BODILY INJURY, OR PROPERTY DAMAGE.
WARNING
THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS
HAVE TO BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES:
– DISCONNECTING
ENSURE THAT DEVICES CANNOT BE
ACCIDENTALLY RESTARTED
VERIFY ISOLATION FROM THE SUPPLY
EARTHING AND SHORT-CIRCUITING
COVERING OR PROVIDING BARRIERS TO
ADJACENT LIVE PARTS
DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY
AUTHORIZED SPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE
SPECIFIED MAINTENANCE INTERVALS AS WELL AS THE INSTRUCTIONS
FOR REPAIR
AND EXCHANGE MUST BE STRICTLY ADHERED TO PREVENT
INJURY TO PERSONNEL AND DAMAGE TO THE SWITCHBOARD.
Section 1: Removal and Installation
And Removal of Drawout Terminal Block
Alignment Bracket
IMPORTANT
KEEP IN MIND THAT SECONDARY TERMINAL BLOCKS ASSOCIATED
WITH DRAWOUT CIRCUIT BREAKERS ARE DIN RAIL MOUNTED ON
THE BREAKER’S DRAWOUT CASSETTE (FIGURE 11). ACCESSORY
SECONDARY PLUGS PLUG INTO A SECONDARY PLUG HOUSING
MOUNTED ON THE TOP FRONT OF THE CIRCUIT BREAKER (FIGURE 12).
AS SUCH, SECONDARY CONNECTIONS ARE AUTOMATICALLY MADE
OR DISCONNECTED DURING THE LEVERING (RACKING) PROCESS AS
THE SECONDARY PLUG HOUSING ON THE BREAKER ENGAGES OR
DISENGAGES THE SECONDARY TERMINAL BLOCKS MOUNTED ON THE
DRAWOUT CASSETTE. FOR THIS REASON, ACCESSORY SECONDARY
PLUGS DO NOT HAVE TO BE UNPLUGGED TO ADD OR REMOVE
TERMINAL BLOCKS. REFER TO FIGURES 3 AND 4 OF SECTION 1 AND
THE ASSOCIATED COPY FOR ASSISTANCE WITH CONNECTING OR
DISCONNECTING ACCESSORY SECONDARY PLUGS.
ote:N Many illustrations use the NF Frame cassette for
illustrative purposes only. The RF Frame cassette is handled in
a similar fashion.
Figure 1. Cassette-Mounted Terminal Blocks NF Frame
Instructions apply to:
1600 NRX SUB-TITLE IMAGE (12/15/2010)
Series NRX, Type NF Frame
ANSI, UL1066, UL489/IEC, IZMX16, IZM91
Series NRX, Type RF Frame
IEC, IZMX40
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010)
2
EATON www.eaton.com
Instructional Leaet IL0131065EN
Effective June 2014
Figure 1a. Cassette-Mounted Terminal Blocks RF Frame
Proceed with the following 6 steps:
Step 1: Become familiar with the drawout terminal block
(Figure 1) and the cassette’s DIN rail mounting location.
In addition, a terminal block alignment bracket is bolted in
place to provide for proper alignment and separation of each
individual terminal block during the levering (racking) process.
Two alignment brackets are used with the RF Frame cassette
since two cradles are required to accommodate the additional
terminal blocks. The bracket’s separation teeth ensure this
alignment and separation (Figure 2). Terminal block alignment
brackets must be removed to add or remove terminal blocks.
Brackets are supplied as part of the cassette and also have
etched numerical identifications.
All of these identifications match the identifications on the
breaker’s secondary plug housing to ensure accurate terminal
block placement.
Figure 2. Step 1
Figure 3. Step 1 (NF Frame)
Figure 3a. Step 1 (RF Frame)
Numerical/Descriptive Identifications
Terminal Block Alignment Bracket
with Numerical Identification
Terminal Block Alignment Bracket
with Numerical Identification
Numerical/Descriptive Identifications
3
EATON www.eaton.com
Effective June 2014
Instructional Leaet IL0131065EN
Step 2: Remove the four mounting screws holding the termi-
nal block alignment bracket in place.
Figure 4. Step 2
Step 3: Carefully slide the alignment bracket out from
between any mounted terminal blocks, and discard with its
mounting hardware.
Figure 5. Step 3
Step 4: Carefully put the new terminal block alignment brack-
et into position by sliding it back into the DIN rail mounted
terminal blocks.
Figure 6. Step 4
Step 5: Once the terminal block alignment bracket is in place,
inspect it from the bottom to ensure that the teeth on the
bracket separate each individual terminal block. One installed
terminal block only should be visible between two teeth
when the alignment bracket is properly positioned.
Figure 7. Step 5
Step 6: Secure the terminal block alignment bracket using the
four preassembled screws. Hand tighten the four mounting
screws to complete the installation process.
Figure 8. Step 6
Disclaimer of warranties and limitation of liability
The information, recommendations, descriptions, and safety
notations in this document are based on Eaton Corporations
(“Eaton”) experience and judgment, and may not cover all contin-
gencies. If further information is required, an Eaton sales office
should be consulted.
Sale of the product shown in this literature is subject to the
terms and conditions outlined in appropriate Eaton selling poli-
cies or other contractual agreement between Eaton and the pur-
chaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS,
WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET
OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES.
ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF
EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT
BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN
THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in
contract, in tort (including negligence), strict liability, or otherwise
for any special, indirect, incidental, or consequential damage or
loss whatsoever, including but not limited to damage or loss of
use of equipment, plant or power system, cost of capital, loss of
power, additional expenses in the use of existing power facilities,
or claims against the purchaser or user by its customers resulting
from the use of the information, recommendations, and descrip-
tions contained herein.
The information contained in this manual is subject to change
without notice.
Eaton
Electrical Group
1000 Eaton Boulevard
Cleveland, OH 45122
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. IL0131065EN
June 2014
Eaton is a registered trademark.
All other trademarks are property of their
respective owners.
Instructional Leaet IL0131065EN
Effective June 2014
Juni 2014
IL0131065ENH01
Montageanweisung IL0131065EN
Arbeits- und Montageanweisung für
den Austausch der Reihenklemmen-
Halteklammer auf der NRX Kassette
WARNUNG
(1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND
ELEKTRONTECHNISCH QUALIFIZIERTES PERSONAL ERFOLGEN.
(2) VOR BEGINN DER ARBEITEN MUSS DER SPANNUNGSFREIE
ZUSTAND DER SCHALTANLAGE HERGESTELLT UND WÄHREND DER
ARBEITEN SICHERGESTELLT SEIN.
(3) SCHALTER IN AUSFAHRTECHNIK MÜSSEN IN TRENNSTELLUNG
GEFAHREN WERDEN.
(4) DIE SCHALTER SIND AUF AUS ZU STELLEN UND DER FEDERSPEICHER
IST ZU ENTSPANNEN.
BEIM BETRIEB ELEKTRISCHER GERÄTE STEHEN ZWANGSLÄUFIG
BESTIMMTE TEILE DIESER GERÄTE UNTER GEFÄHRLICHER SPANNUNG.
UNSACHGEMÄSSER UMGANG MIT DIESEN GERÄTEN KANN
DESHALB ZU TOD ODER SCHWEREN KÖRPERVERLETZUNGEN SOWIE
ERHEBLICHEN SACHSCHÄDEN FÜHREN.
WARNUNG
BEACHTEN SIE BEI INSTANDHALTUNGSMASSNAHMEN AN DIESEM
GERÄT ALLE IN DIESER AWA UND AUF DEM PRODUKT SELBST
AUFGEFÜHRTEN HINWEISE. DIE FÜNF SICHERHEITSREGELN SIND
EINZUHALTEN:
– FREISCHALTEN
– GEGEN WIEDEREINSCHALTEN SICHERN
– SPANNUNGSFREIHEIT FESTSTELLEN
– ERDEN UND KURZSCHLIESSEN
– BENACHBARTE, UNTER SPANNUNG STEHENDE TEILE ABDECKEN
ODER ABSCHRANKEN
DAS GERÄT IST VOM NETZ ZU TRENNEN. ES DÜRFEN NUR VOM
HERSTELLER ZUGELASSENE ERSATZTEILE VERWENDET WERDEN.
DIE VORGESCHRIEBENEN WARTUNGSINTERVALLE SOWIE DIE
ANWEISUNGEN FÜR REPARATUR UND AUSTAUSCH SIND UNBEDINGT
EINZUHALTEN, UM SCHÄDEN AN PERSONEN UND ANLAGEN ZU
VERMEIDEN.
Abschnitt 1: Aus-und Einbau der Reihenklem-
men-Halteklammer der Steuerleitungsan-
schlussblöcke (Kassette)
WICHTIG
BEACHTEN SIE, DASS STEUERLEITUNGSANSCHLÜSSE AN DEN
HALTELEISTEN DER KASSETTE BEFESTIGT WERDEN (ABBILDUNG
11). ANSCHLUSSSTECKER VON ZUBEHÖRLEITUNGEN WERDEN AN
STECKVERBINDUNGEN AM LEISTUNGSSCHALTER ANGESCHLOSSEN
(ABBILDUNG 12). BEIM AUSFAHREN DES SCHALTERS AUS DER
KASSETTE WERDEN STEUERLEITUNGSANSCHLÜSSE AUTOMATISCH
GETRENNT.ANSCHLUSSSTECKER MÜSSEN DAHER NICHT ENTFERNT
WERDEN BEVOR STEUERLEITUNGSANSCHLUSSBLÖCKE EIN- ODER
AUSGEBAUT WERDEN.
Abbildung 1. Steuerleitungsanschlussblock, Ausfahrtechnik
1600A
Die Montageanweisung ist für folgende Baugrößen gültig:
1600 NRX SUB-TITLE IMAGE (12/15/2010)
Series NRX, Type NF Frame
ANSI, UL1066, UL489/IEC, IZMX16, IZM91
Series NRX, Type RF Frame
IEC, IZMX40
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010)
Abbildung 3.
Abbildung 3a.
2
EATON www.eaton.com
Montageanweisung IL0131065EN
Gültig ab Juni 2014
Abbildung 1. Steuerleitungsanschlussblock, Ausfahrtechnik
4000A
Führen Sie die folgenden Schritte aus:
Schritt 1: Machen Sie sich mit den Verbindungssteckern des
Schalters und der Steuerleitungsanschlussleiste der Kassette
vertraut (siehe Abbildung (1, 2, 3).
Abbildung 2.
nmerkung:A Die Steuerleitungsanschlussblöcke werden von
einer Halteklammer in Position gehalten. Diese muss vor dem
Ein- oder Ausbau von Steuerleitungsnaschlussblöcken entfernt
werden (siehe Abbildung (2).
Halteklammer der Anschlusspositionen
Markierung der Anschlusspositionen
3
EATON www.eaton.com
Gültig ab Juni 2014
Montageanweisung IL0131065EN
Schritt 2: Entfernen Sie die vier Befestigungsschrauben der
Halteklammer.
Abbildung 4. Schritt 2
Schritt 3: Entfernen Sie vorsichtig die Halteklammer.
Abbildung 5. Schritt 3
Schritt 4: Schieben Sie neue die Halteklammer wieder vor-
sichtig in ihre ursprüngliche Position ein.
Abbildung 6. Schritt 4
Schritt 5: Überprüfen Sie, ob die Trennstifte der Haltklammer
korrekt zwischen den Steuerleitungsanschlussblöcken sitzen.
Abbildung 7. Schritt 5
Schritt 6: Setzen sie die Befestigungsschrauben der Halte-
klammer wieder ein und ziehen Sie sie fest.
Abbildung 8. Schritt 6
Montageanweisung IL0131065EN
Gültig ab Juni 2014
Eaton
Electrical Group
1000 Eaton Boulevard
Cleveland, OH 45122
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. IL0131065EN TBG01162
Juni 2014
Eaton is a registered trademark.
All other trademarks are property of their
respective owners.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Eaton NRX Series Instruction Leaflet

Type
Instruction Leaflet

Eaton NRX Series is a reliable and versatile secondary terminal block alignment bracket designed for use with NRX Drawout Circuit Breakers. Its primary function is to provide proper alignment and separation of individual terminal blocks during the levering (racking) process, ensuring secure and efficient connections. This bracket is crucial for maintaining accurate terminal block placement and preventing misalignment, which can compromise the integrity of electrical circuits.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages