1 Installation
Topics Covered in this Chapter
• Requiredmaterial
• Mountingtheenclosure
• Replacingthesensingelementassembly(partno.832-00045)
• Replacingthelter(Replacementplasticlterkitpartno.550-00265)
• Maintenance
• Electricalspecications
• Wiringdiagram
Required Material
• 1twoconductorcable,color-coated,22AWGwiregaugewithanoperatingtemperatureof
175°F(80°C)
• Alightchainorropetosuspendtheunittotheceiling.
NOTE: A suspension bead chain and push mount links are provided as an attachment point to
suspend the unit.
WARNING: Failure to comply with the required material and with the mounting instructions
voids warranty.
Mounting the Enclosure
WARNING: Do not make any holes on the top of the enclosure that would allow water to enter
the enclosure.
NOTE: Do not install on an outside wall, or in the path of incoming air.
1.Loosenthefourscrewsandremovethetopcover.escrewsaredesignedsothattheystayassembled
tothecoverwhenremovedfromtherestoftheenclosure.Makesuretokeepthegasketinplaceonthe
cover.
2.Passoneendofthecablethroughthecableglandgrommetintotheenclosure.Tightenthecaponthe
cableglandtosealaroundthecable.Connectconductorstotheterminalsasshowninthewiringdia-
gramontheinsideofthecoverandinFigure2attheendofthismanual.
3.Passthebeadchainthroughtheholesoftheplasticenclosureandlockitinwiththeprovidedlock
links.SeeImage1.ebeadchainloopisusedtoattachtoanotherchainorrope.
4.Installthehumidityprobenearthemiddleoftheroom.Usearopeorachaintosuspendtheprobe
fromtheceiling.ehumidityprobeshouldhangapproximatelyfourfeetaboveoorlevel.SeeFigure1.
5.Makealoopinthepowercableoutsidethehumidityprobeenclosuretopreventmoisturefromente-
ringtheenclosure.
6.Connecttheotherendofthecabletotheenvironmentcontroller.Wiringdependsonthemodelofthe
controller.