14
11. BCR SERIES TECHNICAL FEATURES
(1) Cooling capacity under cold room temperature of 0 ºC (32 ºF) and ambient temperature of 35 ºC (95 ºF).
(2) Total absorbed power by compressor and fans under nominal conditions.
(3) As defined by RD138/2011. IF-01.
(4) Maximum absorbed current even beyond compressor operation limits (axial version)
BCR Series R404A 0008 1018 1026 1034 2034 2054 2074
Cooling capacity
Cooling capacity (1) (W) 515 502 734 876 1102 1443 1689
Absorbed power (2) (W) 630 671 928 1160 1297 1830 2147
COP performance 0,81 0,75 0,79 0,76 0,85 0,79 0,79
Installed power (3) (kW) 0,87 0,88 1,29 1,76 1,76 2,60 3,39
Condenser fan
NF version
Nominal air flow rate (m3/h) 375 575 1150
Type Axial
Power (W) - r.p.m 85 W @ 1300 rpm 120 W @ 1300 rpm
Condenser fan
CF version
Nominal air flow rate (m3/h)
-
575 1150
Available static pressure (Pa) 45
Type Centrifugal
Power (W) 45 W @ 1300 rpm 105 W @ 1300 rpm
Evaporator fan
Nominal air flow rate (m3/h) 300 600 1150
Range (m) 3 4
Type Axial
Power (W) - r.p.m 47 W @
2500rpm 62 W @ 2600 rpm 2 x 62 W @ 2600 rpm
Compressor
Type Hermetic reciprocating
Swept volume (m3/h) 3,18 3,18 4,57 6,01 6,01 9,25 12,91
Nominal discharge pressure (bar
rel.) 20
Nominal suction pressure (bar rel.) 1,30
Nominal power (CV) 5/8 5/8 3/4 1 1/4 1 1/4 1 3/4 2 1/2
High pressure
switch
Type ACB
Brand Danfoss
Model 061F8175
Cut out (bar rel.) 28
Max. absorbed
intensity (A)
230 V / I ph / 50 Hz 4,8 7,2 8,4 10,9 11,4 17,4 25,4
400 V / III ph / 50 Hz Not available 6,21 6,91
Starting-up
intensity (A)
230 V / I ph / 50 Hz 21,9 21,9 29,9 40,9 41,4 69,4 82,4
400 V / III ph /50 Hz Not available 24,4 29,4
Refrigerant
Type R-404A / Grupo L1 / PCA-100: 3260
Load (kg) 0,64 0,75 0,75 0,80 1,20 1,00 1,10
Dimensions
Length (mm) 790 850 850
Wide (mm) 600 665 835
Height (mm) 480 385+189 468+189
Weight (kg) 65 83 84 84 135 145 145
Sound pressure level db(A) 33 38 38 40 41 42 43