Protection
13
and ZCA enter into the largest zone of
distance protection
Without operation of sudden-change
current startup element, all phase
currents are bigger than the power
swing current setting
In addition, according to the experimental
results of power swing, it is not possible for
impedance vector to come into protected
zones in 150 ms after triggering of the
current sudden- -change startup element.
After 150 ms, the protection program will
be switched to power swing logic process if
no tripping is issued.
Therefore, according to the above
condition, the IED program enters the
power swing logic process and the
distance protection is blocked until
removing of the mentioned conditions or
until a fault occurrence in the protected
line.
Power swing unblocking logic
The unblocking logic provides possibility
for selective tripping of faults on
transmission lines during system
oscillations, when the distance protection
function is normally blocked. In order to
unblock distance protection and therefore,
fast clearing of the faults, the following
elements are in service to discriminate
between an internal fault and power swing
conditions.
Asymmetric faults detection element
The zero and negative sequence
current are always the key features of
the asymmetric fault. By comparison
amongst the positive, negative and
zero sequence component of phase
current, the element distinguishes the
asymmetric fault from power swing.
Three phase fault detection element
Based on the experimental results and
practical proof, the change rate of
measuring resistance and the change
vector of measuring impedance are
combined to detect the three phase
fault during the power swing.
Tele-protection
scheme for distance
protection (85-21)
To achieve non-delayed and selective
tripping on 100 % of the line length for all
faults, the communication scheme logic is
provided for distance protection. The
communication schemes are as follows:
Permissive Overreach Transfer Trip
(POTT)
Permissive Underreach Transfer Trip
(PUTT)
Blocking scheme
Following protection logic are used to
ensure correct operation under some
special fault conditions:
Current reversal logic
Weak-infeed end and echo logic
Evolving fault logic
Sequence tripping logic
Direct Transfer Trip
The function is provided to cooperate with
related local protection IED, such as
busbar protection, breaker failure
protection, etc., to trip the opposite end
circuit breaker.