  • Hello! I am an AI chatbot trained to assist you with the Von Duprin JB7 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
*941084-00*
941084-00
Products covered by these instructions:
JB7Junction Box (only)
JB7-R1Junction Box with SPDT Relay
JB7-R2Junction Box with DPDT Relay
JB7-R3Junction Box with DPDT Delay on Make Relay
JB7-R4Junction Box with DPDT Delay on Break Relay
R5 SPDT Relay (only)
R6 DPDT Relay (only)
R7 DPDT Delay on Make Relay (only)
R8 DPDT Delay on Break Relay (only)
Index:
JB7 Junction Box ...................... 2
SPDT Relay .............................. 2
DPDT Relay .............................. 3
DPDT Delay on Make Relay ......3
DPDT Delay on Break Relay ......4
Junction Box and Relays
JB7
Installation Instructions
2
Jb7 Junction Box
12-1/2
10
5
24-position
terminal block
Relay mounting
holes
Back panel
(remove to
install relays)
SPDT 24 VDC RELAY (JB7-R1 AND R5)
Relay Base Wiring
(*1N4001 or 1N4002 can be
substituted; diode not included)
1
9
5
C
NC
NO 13 (—)
1N4004
diode*
14 (+24 VDC)
5-pin relay base
6-32 x 1”
machine screws
6-32
hex nuts
SPDT
relay
5
1
9
14 13
Relay
spring
5
1
9
14 13
3
DPDT 24 VDC RELAY (JB7-R2 AND R6)
Relay Base Wiring
(*1N4001 or 1N4002 can be
substituted; diode not included)
13 (—)
1
9
5
12
8
4
C
NC
C
NO
NC
NO 1N4004
diode*
14 (+24 VDC)
Relay
spring
8-pin relay base
DPDT
relay
6-32 x 1” machine screws
6-32
hex nuts
5
1
13
9
8
4
14
12
5
1
13
9
8
4
14
12
DPDT 24 VDC DELAY ON MAKE RELAY (JB7-R3 AND R7)
Delay on Make Operation: When
power is applied to the input
terminals (2 and 7), the time delay
starts. At the end of the preset time
delay, the output contacts
transfer. Removing input power
resets the relay.
Input
Voltage
On
Off
{
Time Delay
0.05 to 5 seconds
Closed
Open
Closed
Open
Normally Open
Contacts{
Normally Closed
Contacts{
Relay Base Wiring
4
1
3
5
8
6
C
NC
C
NO
NC
NO
2 (+24 VDC)
7 (—)
Time delay
control
(0.05 to 5
seconds)
8-pin relay base
6-32 x 1” machine screws
6-32
hex nuts
DPDT delay on
make relay 6543
7812
© Allegion 2014
Printed in U.S.A.
941084-00 Rev. 04/14-b
DPDT 24 VDC DELAY ON BREAK RELAY (JB7-R4 AND R8)
Delay on Break Operation: Power is applied to the input terminals (2 and 10) at all times. When
the normally open start switch is closed, the output contacts transfer and remain in this position as
long as the start switch is kept closed. When the start switch is opened, the time delay starts. At the
end of the preset time delay, the output contacts transfer back to their original position and the relay
resets.
Input
Voltage
On
Off
{
Closed
Open
Closed
Open
Normally Open
Contacts{
Normally Closed
Contacts{
Time Delay
0.01 to 10 seconds
Closed
Open
Normally Open
Start Switch{
Relay Base Wiring
4
1
3
8
11
9
5
C
NC
C
NO
NC
NO
6
Normally
open start
switch
10 (—)
2 (+24 VDC)
DPDT delay on
make relay
Time delay
control
(0.10 to 10
seconds)
11-pin relay base
6-32 x 1” machine screw 6-32 hex nuts
8754
6
910 23
11 1