English Page 11
C. Installation
7.1.3 Setting of soft stop OPEN
• Release the stop (grub screw J) of control cam (D).
• Set control cam (D) in such way, that the limit switch is actuated approx.
0,7 - 1m before the door reaches its OPEN travel limit (position H).
• Fix control cam (D) by screwing on grub screw (J).
• Close cover of housing again.
7.2 Operator Dynamic 3 with control unit Control 75-FU
Control Cam Function Connection
A: limit switch CLOSE System socket X42
B: limit switch OPEN System socket X42
C: soft stop CLOSE Plug connection X3
D: soft stop OPEN Plug connection X3
E: CES (closing edge safety System socket X42
device) STOP
F: freely available Screw terminal X4
(change-over
contact max. 230V,
0,5 A)
The function CES STOP deactivates the reversion function of the closing
edge safety device shortly before reaching the travel limit CLOSE, in order
to avoid faulty reaction (e.g. unwilling reversion).
7.2.1 Setting CLOSE travel limit
• Move the door by hand to its mechanical travel limit CLOSE.
• Open cover of housing on door operator.
• Release the stop (grub screw J) of control cam (A).
• Set control cam (A) in such way, that the limit switch CLOSE (G) is
actuated as shown in fig. 7.2.1 (position H).
• Fix control cam (A) by screwing on grub screw (J).
• Adjust door position CLOSE, if necessary, by means of the fine
adjustment screw (K) on the control cam.