EMS Zone Interface Module Installation guide

Category
Fire protection
Type
Installation guide

EMS Zone Interface Module

The EMS Zone Interface Module (ZIM) is a wireless device that can be used to connect wired input and output devices to a wireless fire alarm system. The ZIM can be used to monitor a variety of input devices, such as smoke detectors, heat detectors, and water flow switches. It can also be used to control output devices, such as sirens, strobes, and relays.

The ZIM is a self-contained device that includes a built-in antenna and power supply. It is easy to install and can be configured using a simple programming interface. The ZIM is also compatible with a variety of wireless fire alarm systems, making it a versatile solution for a variety of applications.

EMS Zone Interface Module

The EMS Zone Interface Module (ZIM) is a wireless device that can be used to connect wired input and output devices to a wireless fire alarm system. The ZIM can be used to monitor a variety of input devices, such as smoke detectors, heat detectors, and water flow switches. It can also be used to control output devices, such as sirens, strobes, and relays.

The ZIM is a self-contained device that includes a built-in antenna and power supply. It is easy to install and can be configured using a simple programming interface. The ZIM is also compatible with a variety of wireless fire alarm systems, making it a versatile solution for a variety of applications.

1 Pre Installation
2 Components
3
Part No Product Description
EC-41-0200 EMS Wireless Zone Interface Module
Zone Interface Module
Installation Guide
IDENT REV
DATE
FC-610-001
EN300 200-2
0359
!
20K
4K7
C
N/O
20K = Red/Bl
4k7 = Yellow
EOL Resistor
Conguration
ANTENNA
2
1
4 Remove Cable Entry Points
5 Fix to the Wall
Drill the cable entry
points as necessary.
Cable glands should
be used.
DO NOT leave excess
cable in the device.
ON
INPUT 1
INPUT 2
EXPAN1
EXPAN2
OUTPUT 2
OUTPUT 1
IP- IP+
IP- IP+
3VDC
SET
RST
N/O
COM
N/C
3VDC
SET
RST
N/O
COM
N/C
Do Not Use
=
Available
Cable Entry
Points
=
3 Mounting Location Guidelines
Ensure the ZIM is not installed
within 2m of the Control Panel
or any other wireless or
electrical equipment.
Ensure the ZIM is not installed
within 0.6m of any metal work.
Ensure the ZIM is not installed
within 0.6m of the WZM.
WIRELESS ZONE INTERFACE MODULE
WZM
ZIM
0.6m
Existing
Control Panel
WZM
ZIM
0.6m
POWER
FAU LT
WIRELESS ZONE MONITOR
2m
WIRELESS ZONE INTERFACE MODULE
WIRELESS ZONE INTERFACE MODULE
POWER
FAU LT
WIRELESS ZONE MONITOR
Existing
Control Panel
FIRE
Fire Alarm Control
FIRE
Fire Alarm Control
!
Installation must conform to applicable local installation
codes and
should only be installed by a fully trained
competent person.
Ensure that the device is installed as per the site survey.
The use of a non-metallic spacer should be considered if
mounting the device on to a metal surface.
Do NOT Press the Log On button on a pre-programmed
device, as this will cause communication with the Control
Panel to be lost. Should this happen, delete the device from
the system and add it back on.
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
4x Lid Fixing Screws Front Lid Back Box
1
2
3
For optimum wireless
performance, the
following must be
observed:
Use all four circled
fixing positions to
ensure a firm fixing.
Use suitable fasteners
and fixings.
ANTENNA
KEEP CABLES AWAY FROM THIS AREA
LOGON
OUTPUT 2OUTPUT 1
3VDC
SET RST
INPUT 1 INPUT 2
LED
ENABLE
POWER
INPUT
INPUT
FAULT
CLOSED
0 1
1
64
F-SAFE
N/O COM
N/C
IP- IP+ IP- IP+
3VDC
SET RST
N/O COM
N/C
EXPAN1
EXPAN2
RELAY ON
RELAY ON
2
4
8
16
32
ON
1 2 3 4 5 6 7 8
012ABC
Fixing position
location within
cavity
©2018 EMS Ltd. All rights reserved. Page 1 of 2 TSD142 Iss 4 05/09/2018 AJM
7 Power Device
When fitting / replacing batteries; observe correct polarity,
using only specified batteries.
Connect the power jumper across the PIN header.
6 Connection Wiring
Once powered, reassemble the device.
OUTPUT 2OUTPUT 1
3VDC
SET RST
INPUT 1 INPUT 2
LED
ENABLE
PO WER
INPUT 1
INPUT 2
FAULT
CLOSED
0 1
1
64
F-SAFE
N/O COM N/C
IP- IP+ IP- IP+
3VDC SET RST N/O COM N/C
EXPAN1
EXPAN2
RELAY ON
RELAY ON
2
4
8
16
32
device
unpowered
(pins unlinked)
device
powered
(both pins linked)
Refer to the Wireless Zone
Monitor Engineers Guide
(Doc Ref: TSD143) for full
wiring details.
Free to download from
www.emsgroup.co.uk
8 Configuration
The ZIM must be added to the WZM, before adding other wireless
devices to the system.
Refer to the Wireless Zone Monitor Engineers Guide (Doc Ref:
TSD143) for full programming details.
Free to download from
www.emsgroup.co.uk
9 LED Operation
The device has six indication LEDs. Pressing the LED enable button
enables their illumination for 10 minutes before automatically
timing out.
2x Input Fault: YELLOW LED ON = FAULT
2x Input Closed: RED LED ON = ACTIVE
2x Output: RED LED ON = ACTIVE
CLOSED
FAULT
INPUT 1
INPUT 2
Input 2
LEDs
Input 1
LEDs
Output 1 LED
Output 2 LED
Operating
Temperature -10°C to 55°C
Storage
Temperature 5°C to 30°C
Humidity Up to 95% non-condensing
Supply 6x AA Alkaline (Panasonic LR6AD Powerline / Varta
4006 Industrial)
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
Output rating 2A @ 24Vdc
IP Rating IP65
Operating Frequency 868MHz
Output Transmitter
Power Auto adjusting 0 - 14 dBm (0 - 25 mW)
Dimensions 270mm (W) 205mm (H) 75mm (D)
Weight 0.95kg
Location Type A: For indoor use
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For recycling, return this product to
your local supplier upon purchase of equivalent new
equipment, or dispose of it at designated collection
points. For more information see
www.recyclethis.info
Dispose of your batteries in an environmentally
friendly manner according to your local regulations.
European Union
directives
EMS declares that the radio equipment type Zone
Interface Module is in compliance with Directive
2014/53/EU. The full text of the EU declaration of
conformity is available at the following internet
address:
www.emsgroup.co.uk
Approved to
EN54-18:2005. Fire detection and fire alarm
systems. Part 18: Input/output devices.
EN54-25:2008. Incorporating corrigenda
September 2010 and March 2012. Fire detection
and fire alarm systems. Part 25: Components using
radio links.
Certification
Certification body
CPR Certificate DOP 0359-CPR-00436
EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
Manufacturer
Year of
manufacture See devices serial number label
0359
14
Specification Regulatory Information
©2018 EMS Ltd. All rights reserved. Page 2 of 2 TSD142 Iss 4 05/09/2018 AJM
  • Page 1 1
  • Page 2 2

EMS Zone Interface Module Installation guide

Category
Fire protection
Type
Installation guide

EMS Zone Interface Module

The EMS Zone Interface Module (ZIM) is a wireless device that can be used to connect wired input and output devices to a wireless fire alarm system. The ZIM can be used to monitor a variety of input devices, such as smoke detectors, heat detectors, and water flow switches. It can also be used to control output devices, such as sirens, strobes, and relays.

The ZIM is a self-contained device that includes a built-in antenna and power supply. It is easy to install and can be configured using a simple programming interface. The ZIM is also compatible with a variety of wireless fire alarm systems, making it a versatile solution for a variety of applications.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI