Danfoss VACON NXP Air cooled Installation guide

Type
Installation guide
installation quick guide
frames fr9 to fr14
ip00 modules
ac drives
vacon
®
nxp
vacon • 3
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
TABLE OF CONTENTS
Document: DPD00889B
Release date : 28.02.2019
1. Delivered modules / installing AC chokes and power module .........................4
1.1 Products included in the delivery ......................................................................................4
1.2 Lifting the power module...................................................................................................4
1.3 Installing the power module ..............................................................................................5
2. Ventilation........................................................................................................6
2.1 Steering the internal air flow.............................................................................................6
2.2 Arranging ventilation of the enclosure..............................................................................7
3. Grounding and cabling the unit ........................................................................8
3.1 Connecting the internal power cable.................................................................................8
3.2 Installing the optical fibers ................................................................................................9
3.3 Installing the motor cable..................................................................................................9
1
vacon • 4 Delivered modules / installing AC chokes and power module
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1. DELIVERED MODULES / INSTALLING AC CHOKES AND
POWER MODULE
1.1 Products included in the delivery
NOTE! FR12 = 2 x FR10; FI14 = 2 x FI13 power modules.
NOTE! In FR9, the AC choke is inside the power module.
1.2 Lifting the power module
NOTE! Place the lifting hooks symmetrically in at least two holes. The lifting devices must be able
to carry the weight of the module.
NOTE! The maximum allowed lifting angle is 45°.
Frame Weight kg
FR9 146
FR10 123
FR11 210
FI9 65
FI10 100
FI12 200
FI13 302
Power module
AC choke
Control unit
12017A_uk
Max
12018A_u
k
45
°
Delivered modules / installing AC chokes and power module vacon • 5
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1
1.3 Installing the power module
NOTE! For detailed drawing, see manual.
Frame
Device width
A/mm
Supporting bar range
B/mm
Recommended cabinet width
C/mm
FR9 480 A - 50 mm 600
FR10 500 A - 50 mm 600
FR11 709 A - 20 mm 800
FI9 239 A - 50 mm 400
FI10 239 A - 50 mm 400
FI12 478 A - 50 mm 600
FI13 708 A - 50 mm 800
B
C
AC choke
12019A_uk
A
2
vacon • 6 Ventilation
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
2. VENTILATION
2.1 Steering the internal air flow
NOTE! Outgoing air must be directed out of the cabinet so that it does not mix with incoming cooling
air.
Air barrier
Duct
or
12022A_uk
Ventilation vacon • 7
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
2
2.2 Arranging ventilation of the enclosure
CAUTION! It is of utmost importance for the operation and lifetime of the frequency converter that
the closure is well ventilated to keep the temperature below the maximum operating temperature.
Repeated overheating will shorten the lifetime of the converter.
Table 1. Ventilation requirements table
Minimum air hole on switchgear/dm
2
Frame
Cooling air
required m
3
/h
1) Inlet 2) Outlet
FR9 1300 9.1 7
FR10 2000 9.5 5
FR11 3000 14 7.5
FI9 1150 5.5 3
FI10 1400 6.5 4
FI12 2800 13 7
FI13 4200 19.5 10.5
1
2
12023A_00
3
vacon • 8 Grounding and cabling the unit
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3. GROUNDING AND CABLING THE UNIT
3.1 Connecting the internal power cable
See IP00 Module Installation Manual for details.
NOTE! No external choke in FR9.
FI FR
DC BUS
U V W
L1
L2
L3
U V W
L1
L2
L3
CHOKE CHOKE
12024A_uk
Grounding and cabling the unit vacon • 9
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
3.2 Installing the optical fibers
3.3 Installing the motor cable
Min bending
radius
X2
X1
1
2
3
4
5
6
7
12025A_uk
Cable fixing clamps
EMC grounding
360°
12026A_uk
Document ID:
DPD00889B
Rev. B
Vacon Ltd
Member of the Danfoss Group
Runsorintie 7
65380 Vaasa
Finland
www.danfoss.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

Danfoss VACON NXP Air cooled Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI