Novus TxRail-USB User manual

Type
User manual

Novus TxRail-USB is a configurable DIN rail mount temperature transmitter that allows for selection and configuration of input type, measurement range, output type, and calibration. It supports various sensors, including thermocouples, Pt100/Pt1000 RTDs, NTC resistors, and voltage inputs. The output can be set to either loop-powered 4-20 mA or 0-10 Vdc, making it compatible with a wide range of industrial control systems and data acquisition applications.

Novus TxRail-USB is a configurable DIN rail mount temperature transmitter that allows for selection and configuration of input type, measurement range, output type, and calibration. It supports various sensors, including thermocouples, Pt100/Pt1000 RTDs, NTC resistors, and voltage inputs. The output can be set to either loop-powered 4-20 mA or 0-10 Vdc, making it compatible with a wide range of industrial control systems and data acquisition applications.

NOVUS AUTOMATION 1/4
Tx
Rail-USB
TEMPERATURE TRANSMITTER
- OPERATING MANUAL – V2.0x B
INTRODUCTION
TxRail-USB is an USB configurable DIN rail mount temperature
transmitter. It allows selection and configuration of input type,
measurement range, output type and calibration. Its output can be
set to either loop powered 4-20 mA or 0-10 Vdc. Highly accurate and
user-friendly, the TxRail-USB performs well from simple to
sophisticated measurement applications.
The output current or voltage is linearized according to the selected
input sensor and adjusted to the configured range.
SPECIFICATIONS
Sensor input: User defined. The supported sensors are listed in
Table 1, along with their maximum ranges.
Thermocouples: Types J, K, R, S, T, N, E and B, according to
IEC 60584 (ITS-90). Impedance >> 1 M
Pt100: Excitation 0.8 mA, α= 0.00385, according IEC 60751
(ITS-90).
For 2-wire sensors, tie terminals 3 and 4 together.
Pt1000: Type 3-wire, Excitation 0.8 mA, α= 0.00385, according
IEC 60751 (ITS-90).
For 2-wire sensors, tie terminals 3 and 4 together.
NTC R25°C: 10 k ±1 %, B25/85 = 3435
Voltage: 0 to 50 mVdc. Impedance >> 1 M
0 to 100 mVdc. Impedance >> 1 M (*)
(*) Feature available for devices with firmware version
starting at V2.0x.
Sensor Type
Maximum Measurement
Range
Minimum Measurement
Range
Voltage
0 to 50 mV
5 mV
Voltage 0 to 100 mV 10mV
Thermocouple K -150 to 1370 °C 100 °C
Thermocouple J -100 to 760 °C 100 °C
Thermocouple R -50 to 1760 °C 400 °C
Thermocouple
S
-50 to 1760 °C
400 °C
Thermocouple
T
-160 to 400 °C
100 °C
Thermocouple N -270 to 1300 °C 100 °C
Thermocouple E -90 to 720 °C 100 °C
Thermocouple B 500 to 1820 °C 400 °C
Pt100 -200 to 650 °C 40 °C
Pt1000
-200 to 650 °C
40 °C
NTC
-30 to 120 °C
40 °C
Table 1Sensors accepted by the transmitter
Switch-on delay: < 2.5 s. The accuracy is only guaranteed after 15
minutes.
Terms of reference: ambient: 25 ° C; voltage: 24 Vdc, load: 250 ;
settling time: 10 minutes
Temperature Effect: < ±0.16 % / 25 °C
Response time: typical 1.6 s.
Maximum voltage allowed at input terminals no sensor: 3 V.
RTD current: 800 µA.
RTD cable resistance effect: 0.005 °C /
Maximum allowable cable resistance for RTD: 25 .
Sensor Type Typical
Accuracy
Maximum
Accuracy
Pt100 / Pt1000
(-150 to 400 °C)
0.10 % 0.12 %
Pt100 / Pt1000
(-200 to 650 °C)
0.13 % 0.19 %
K, J, T, E, N, R, S, B
0.1 % (*)
0.15 % (*)
mV 0.1 % 0.15 %
NTC 0.3 °C 0.7 °C
Table 2Calibration error, percentage of the full measurement range.
(*) Add cold junction compensation: < ± 1 °C.
Power supply influence: 0.006 % / V typical (percentage of the full
measure range).
Output (4-20 mA): 4-20 mA or 20-4 mA current, 2-wired; and
proportional to the configured range.
Output Resolution (4-20 mA): 2 µA.
Output (0-10 Vdc): 0-10 Vdc or 10-0 Vdc voltage, and proportional
to the configured range.
Output Resolution (0-10 Vdc): 0.0025 V (12 bits)
Power supply: 10 to 35 Vdc (output 4-20 mA) and
12 to 35 Vdc (output 0-10 Vdc).
Maximum load (RL): RL (máx.) = (Vdc 10) / 0.02 []
Where: Vdc= Power supply voltage (10-35 Vdc)
Operating Temperature: -40 to 85 °C
Humidity: 0 to 90 % RH
Electromagnetic Compatibility: EN 61326-1:2006
No electrical isolation between input and output.
Internal protection against polarity inversion.
Cold junction compensation for thermocouples.
Connection Wire Cross Section: 0.14 a 1.5 mm²
Screw Tightening: 0.8 Nm.
Housing: ABS UL94-HB.
Certification: CE, UKCA
CONFIGURATION
Changes to the configuration are possible through the TxConfig II
software, provided free of charge.
The transmitter configuration interface (USB cable) can be
purchased from the manufacturer or its authorized sales
representatives.
TxRail-USB
NOVUS AUTOMATION 2/4
The TxConfig II software is continuously updated and new versions
can be downloaded at no charge from the manufacturer’s website.
To install, execute the TxConfigIISetup.exe file and follow the
instructions.
Fig. 1USB cable connection
During the setup, the transmitter is powered by the USB, not
requiring an external power supply.
The transmitter setup can also be made by connecting it to the loop,
using the loop power supply. There is no electrical insulation between
the transmitter and the communication port (interface), therefore it is
not recommended to configure it with the sensor inlet connected to the
process. See Fig. 2.
Fig. 2USB cable connections Loop powered
After these connections, the user must run the TxConfig II software
and, if necessary, consult the Help topic to help using the software.
The USB communication port (interface) of the
TxBlock-USB is not electrically insulated from the
transmitter’s input.
SOFTWARE CONFIGURATION:
Fig. 3TxConfig II software main screen
The fields in the screen mean:
1. General Information: This field shows information that identifying
the transmitter. This information should be sent to the
manufacturer in an eventual request for technical assistance.
2. Sensor: Select the type of sensor to be used. See Table 1.
3. Measuring Range: Sets de measurement range of the
transmitter.
Lower Range Limit: Desired temperature for minimum
retransmission value.
Upper Range Limit: Desired temperature for maximum
retransmission value.
Sensor Range
The values chosen cannot exceed the range of sensor shown in
this field. See Table 1 of this manual.
Minimum Range
Do not set a lower band (span) that the Minimum Range
indicated below in this same field. See Table 1 of this manual.
4. Sensor Failure: It establishes the output behavior, when the
transmitter indicates a failure:
Minimum: output current goes to < 3.8 mA or output voltage is 0
V (down-scale), typically used for refrigeration.
Maximum: output current goes to > 20.5 mA or output voltage is
10 V (up-scale), typically used for heating.
5. Zero Correction: It corrects small deviations presented in the
transmitter output, for example, when the sensor is replaced.
6. Send Configuration: It applies the new setup. Once sent, the
setup will be immediately adopted by the transmitter.
7. Read Configuration: Reads the current setup in the transmitter
connected. The screen now presents the current setup that may
be changed by the user.
FACTORY SETTING:
Sensor: Pt100 3-wire, range 0 to 100 °C
Sensor failure: upscale (maximum).
0 °C zero correction.
Unit: °C;
Output: 4-20 mA.
MECHANICAL INSTALLATION
The TxRail-USB transmitter is suitable to be installed in 35 mm DIN
rail. Vibrations, moisture and extreme temperatures, electro-magnetic
interference, high voltage and other interferences can permanently
damage the unit, and could cause error in the measured value.
DIMENSIONS:
Fig. 4Transmitter dimensions
TxRail-USB
NOVUS AUTOMATION 3/4
OPENING THE TRANSMITTER:
In order to open the transmitter, you must press the orange lockers
located on both sides of the enclosure and pull the frontal cover very
carefully, just like shown in Fig. 5.
Fig. 5Opening the transmitter
ELECTRICAL INSTALLATION
The Fig. 6 shows the electrical connections required. The TxRail-
USB wiring for thermocouple, RTD, resistance and voltage are
done according figure below.
Fig. 6 TxRail-USB transmitter electrical connections
LOAD represents the 4-20 mA current or the 0-10 V voltage
measuring device (indicator, controller, register, etc.).
Polyamide enclosure.
Section of the cable used: 0.14 to 1.5 mm ²
Recommended torque in the terminal: 0.8 Nm.
RECOMMENDATIONS FOR INSTALLATION
Conductors of small electrical signals must be distant from
activation and high-tension/current conductors, preferably passing
through grounded conduits.
A specific electrical power supply network should be provided for
instruments use only.
In controlling and monitoring applications, possible consequences
of any system failure must be considered in advance.
RC filters (47R an 100nF, serial) in inductor charges (contactors,
solenoids, etc.) are recommended.
ELECTRICAL CONNECTIONS
The figures below show the electrical connections required. The
terminals 1, 2, 3 and 4 are dedicated to the sensor connection.
LOAD represents the 4-20 mA current or 0-10 V voltage measuring
device (indicator, controller, recorder, etc.).
PT100/PT1000 2-WIRE / NTC
Note: When the Pt100/Pt1000 2-wire the terminals 1 and 3 must be
interconnected, according to the figure below.
To use the Pt100/Pt1000 2-wire, you must configure the
Pt100/Pt1000 3-wire option in TxConfig II.
The Pt100/Pt1000 wire length should be less than 30 cm to
maintain the measurement error within specifications (electrical
resistance).
Fig. 7Transmitter electrical connections (Pt100/Pt1000 2-wire / NTC)
PT100/PT1000 3-WIRE
Fig. 8Transmitter electrical connections (Pt100/Pt1000 3-wire)
PT100 4-WIRE
Fig. 9Transmitter electrical connections (Pt100 4-wire)
Pt100 3 and 4-wire: For appropriate cable resistance compensation
they should be equal for all legs. Maximum wire resistance is 25 per
wire leg. Usage of a 3 or 4 wire with conductors of equal length and
gauge is recommended.
THERMOCOUPLES
Fig. 10Transmitter electrical connections (Thermocouple)
TxRail-USB
NOVUS AUTOMATION 4/4
VOLTAGE (0-50 mV / 0-100 mV)
Fig. 11Transmitter electrical connections (0-50 mV / 0-100 mV)
OUTPUTS (0-10 V and 4-20 mA)
Fig. 12Transmitter electrical connections (0-10 V and 4-20 mA)
OPERATION
The sensor offset can be changed through the TxConfig II software.
The USB cable may be connected to the transmitter without causing
any measurement errors. See item Zero Correction in the chapter
CONFIGURATION of this manual.
The user must choose the most suitable sensor and range to the
process. The chosen range must not exceed the maximum range of
measurement defined for the sensor and should not be smaller than
the minimum range for the same sensor.
It is important to note that the transmitter accuracy is based on the
maximum range of the sensor used, even when a narrower range is
programmed. Example:
The Pt100 sensor in the range 0 to 100 °C and accuracy of
0.12 %, the maximum error will be 1.02 °C (0.12 % de 850 °C);
The Pt100 sensor in the range 500 to 600 °C and accuracy of 0.19
%, the maximum error will be 1.61 °C (0.19 % of the 850 °C).
Note: When measurements are made at the transmitter, see if the
Pt100 excitation current required by the calibrator is compatible with
the Pt100 excitation current used in the transmitter: 0.8 mA.
WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Novus TxRail-USB User manual

Type
User manual

Novus TxRail-USB is a configurable DIN rail mount temperature transmitter that allows for selection and configuration of input type, measurement range, output type, and calibration. It supports various sensors, including thermocouples, Pt100/Pt1000 RTDs, NTC resistors, and voltage inputs. The output can be set to either loop-powered 4-20 mA or 0-10 Vdc, making it compatible with a wide range of industrial control systems and data acquisition applications.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI