STN 59 59 - PREMTA200 updates for improved temperature control ©2023 LG Electronics U.S.A., Inc. All rights reserved.
Page 1 of 6
Information:
During the operation of the LG PREMTA200 product manufactured before March 2023 with firmware versions
prior to 1.006, external influences can affect the temperature displayed on the installed remote controller.
Discrepancies between actual room temperature and displayed room temperature can occur if there is ingress
of air from an unconditioned space via the openings of the mounting plate of the PREMTA200 Controller. It is
important to seal the unused openings of the PREMTA200 backplate using the foam donut supplied with the
PREMTA200 or using field supplied insulating material. It is also recommended to upgrade the current
firmware version to 1.006 or above, as shown below.
If an electrical junction box is utilized for the controller mounting, be sure to use an alternate backplate adaptor,
not provided by LG, or other means to block off the junction box opening. Recommended IDU to Remote
Controller cable should be properly routed on the backplate of the PREMTA200 using the pathway and cable
guides in the backplate.
The procedure for updating firmware and functions:
1. Block the cable entry hole with LG-provided foam donut or field supplied insulating material as shown below
to avoid temperature variations by air movement inside the wall.
STN Number:
59
Date Issued:
August 17, 2023
Action:
Service
Distribution:
LG Applied Representatives
LG Distributors Contractor/Installers
Subject:
PREMTA200 updates for improved temperature control
LG PREMTA200 deluxe thermostat
Firmware versions prior to 1.006
Manufactured before March 2023
Description:
When the LG PREMTA200 Controller is installed, there may be temporary or persistent discrepancies between the actual
room temperature and the temperature displayed.
1.1 Installed remote control.
1.2 Pull the lower part of the remote
control. Detach the remote control.
1.3 Block the cable entry hole with LG-supplied
foam donut or field supplied insulator or tape.
STN 59 59 - PREMTA200 updates for improved temperature control ©2023 LG Electronics U.S.A., Inc. All rights reserved.
Page 2 of 6
Once the PREMTA200 backplane is secured to the wall and associated cable terminated, the PREMTA200 controller can
be mounted on and clipped into the backplate as shown. A securing screw may be used to effectively ‘lock’ the PREMTA200
controller into the backplate, thereby avoiding accidental dislocation of the controller.
2. Update firmware to version 1.006 or higher
1.4 Reinstall remote controller
2.1. Preparation
-
OTG Cable (USB to micro 5pin)
- USB Memory
- Update Files (Target version )
2.2. Copy Update Filesinto the USB Memory
- Update Filesto be added under the
rrcUpdatefolder of the USB Memory
1.5 Remote controller can be locked to
backplate with a screw as shown
Controller shown with a sealed back plate
and mounted flush to the wall.
STN 59 59 - PREMTA200 updates for improved temperature control ©2023 LG Electronics U.S.A., Inc. All rights reserved.
Page 3 of 6
To obtain the most current version of firmware, contact the LG Field Support Specialist for your region.
2.3 Check SW version of RRC (Deluxe Wired Remote Controller)
2.4 Open the RRC bottom cover and connect the OTG cable to the Micro USB port
STN 59 59 - PREMTA200 updates for improved temperature control ©2023 LG Electronics U.S.A., Inc. All rights reserved.
Page 4 of 6
3. Choose update procedure depending on existing base version
STN 59 59 - PREMTA200 updates for improved temperature control ©2023 LG Electronics U.S.A., Inc. All rights reserved.
Page 5 of 6
Optional Temperature Offset Setting
For the temperature deviation according to the installation environment, use the temperature
compensation in the installer setting.
On initial power up, please allow 10 minutes prior to applying any temperature compensation available in the advanced
installer settings.
- How to enter setting : Menu -> Installer setting -> Air conditioner -> Temperature Offset
4. Remote Controller will automatically restart
after update completion
The password for installer settings is the version of the remote control.
Example) If the remote-control version is 1.006, the password is 1006.
Disconnect OTG cable from RRC when LG logo appears, check the updated version at the bottom right.
LG logo disconnect (Alternate) Disconnect OTG
OTG cable and reset power
STN 59 59 - PREMTA200 updates for improved temperature control ©2023 LG Electronics U.S.A., Inc. All rights reserved.
Page 6 of 6
After selecting an air conditioner, use the temperature compensation function.
Temperature calibration works only when the temperature sensor reference is selected with the remote control.
Temperature compensation can be set to -10F to 10F (-5 to 5) to match the space temperature."
If temperature fluctuation continues, despite verifying and applying all of the above methods, it is recommended that the
PREMTA200 Controller be replaced with a current production model with firmware version 1.006 produced after March
2023.
To obtain the most current version of firmware, contact the LG Field Support Specialist for your region.
Note: Always refer to the LG Installa�on and Opera�ons Manual (IOM) for addi�onal instruc�ons prior to PREMTA200
Controller. Good installa�on prac�ces are essen�al when installing wall mounted controllers/thermostats/sensors to properly
sense and control temperature as well as for reliable communica�on. Loca�on, installa�on, and set-up of room controllers is
extremely important to occupant comfort and system performance. Room Controllers should be located in a central loca�on
away from doorways, windows, diffusers, or other sources of thermodynamic heat or cold.
/