Catalog No. 04-53480067-01 Printed in U.S.A. Form 48A-7SI Pg 1 8-09 Replaces: 48A-5SI
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-36
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
ROOF CURB
ALTERNATE UNIT SUPPORT
Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2
POSITIONING
ROOF MOUNT
Step 3 — Field Fabricate Ductwork. . . . . . . . . . . . . . . 2
Step 4 — Make Unit Duct Connections . . . . . . . . . . . 2
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . 19
Step 6 — Trap Condensate Drain . . . . . . . . . . . . . . . . 19
Step 7 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . 19
Step 8 — Make Electrical Connections . . . . . . . . . . 20
•POWER WIRING
FIELD POWER SUPPLY
FIELD CONTROL WIRING
Step 9 — Make Outdoor-Air Inlet
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
ECONOMIZER AND FIXED OUTDOOR
AIR DAMPER
Step 10 — Position Power Exhaust/Barometric
Relief Damper Hood. . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Step 11 — Route VAV Static Pressure Sensor . . . 34
Step 12 — Install All Accessories . . . . . . . . . . . . . . . 35
Step 13 — Field Modifications. . . . . . . . . . . . . . . . . . . 35
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should in-
stall, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
INSTALLATION
Step 1 — Provide Unit Support
WARNING
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
WARNING
1. Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, personal
injury, or loss of life. Refer to the Users Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable va-
pors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
3. IMMEDIATELY call your gas supplier from a neigh-
bors phone. Follow the gas suppliers instructions.
4. If you cannot reach your gas supplier, call the fire
department.
WARNING
Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure
testing field-supplied gas piping at pressures of 0.5 psig or
less, a unit connected to such piping must be isolated by
closing the manual gas valve(s).
CAUTION
1. All panels must be in place when rigging or damage
to unit may occur.
2. Unit is not designed for handling by fork truck.
WEATHERMAKER
®
48AJ,AK,AW,AY020-060
Single Package Rooftop Units
Electric Cooling/Gas Heating
with Scroll Compressor and
COMFORTLINK™ Controls
2
ROOF CURB — For vertical discharge units, assemble or in-
stall accessory roof curb in accordance with instructions
shipped with this accessory. See Fig. 1-3. Install insulation,
cant strips, roofing, and counter flashing as shown. Ductwork
can be installed to roof curb before unit is set in place. Curb
should be level. This is necessary to permit unit drain to func-
tion properly. Unit leveling tolerance is shown in Fig. 1-3.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required. When accessory roof curb
is used, unit may be installed on class A, B, or C roof covering
material.
ALTERNATE UNIT SUPPORT — When the preferred curb
or slab mount cannot be used, support unit with sleepers on pe-
rimeter, using unit curb support area. If sleepers cannot be
used, support long sides of unit (refer to Fig. 4-10) with a mini-
mum number of 4-in. x 4-in. pads spaced as follows:
48AJ,AK,AW,AY020-035 units require 3 pads on each side;
48AJ,AK,AW,AY036-050 units require 4 pads on each side;
48AJ,AK,AW,AY051 and 060 units require 6 pads on each
side. Unit may sag if supported by corners only.
Step 2 — Rig and Place Unit — Inspect unit for
transportation damage. See Tables 1-6 for physical data and
specifications. File any claim with transportation agency.
Do not drop unit; keep upright. Use spreader bars over unit
to prevent sling or cable damage. This unit must be handled
with a crane and can not be handled by a fork truck. Level by
using unit frame as a reference; leveling tolerance is shown in
Fig. 1-3. See Fig. 10 for additional information. Unit operating
weight is shown in Table 2.
NOTE: On retrofit jobs, ductwork may be attached to the old
unit instead of a roof curb. Be careful not to damage ductwork
when removing old unit. Attach existing ductwork to roof curb
instead of unit.
Four lifting lugs are provided on the unit base rails as shown
in Fig. 4-10. Refer to rigging instructions on unit.
POSITIONING Maintain clearance, per Fig. 4-10, around
and above unit to provide minimum distance from combustible
materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contaminated
air. For proper unit operation, adequate combustion and venti-
lation air must be provided in accordance with Section 5.3 (Air
for Combustion and Ventilation) of the National Fuel Gas
Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft
from any opening through which combustion products could
enter the building, and at least 4 ft from any adjacent building.
When unit is located adjacent to public walkways, flue assem-
bly must be at least 7 ft above grade.
ROOF MOUNT Check building codes for weight distribu-
tion requirements. See Fig. 11. Unit operating weight is shown
in Table 2.
Step 3 — Field Fabricate Ductwork — Secure all
ducts to building structure. Use flexible duct connectors be-
tween unit and ducts as required. Insulate and weatherproof all
external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.
NOTE: Due to width of the horizontal supply and return duct-
work, provisions should be made for servicing of the outdoor
air filters (i.e., catwalk over ductwork).
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier. Outlet grilles must not
lie directly below unit discharge. The return duct must have a
90-degree elbow before opening into the building space if the
unit is equipped with power exhaust.
To attach ductwork to roof curb, insert duct approximately
10 to 11 in. up into roof curb. Connect ductwork to 14-gage
roof curb material with sheet metal screws driven from inside
the duct.
Follow AMCA (Air Movement and Control Association)
guidelines relating to ductwork connections to the unit. These
guidelines recommend a minimum 2
1
/
2
equivalent duct diame-
ters of straight duct connected to supply air inlet and outlet
openings before any transitions, fittings, dampers, etc. Failure
to adhere to these guidelines may result in system effects which
can impact the unit’s ability to achieve published performance.
Step 4 — Make Unit Duct Connections
48AJ AND AK UNITS — Unit is shipped for thru-the-
bottom duct connections. Field-fabricated ductwork should be
attached to the roof curb. Supply and return duct dimensions
are shown in Fig. 4-6. Air distribution is shown in Fig. 12.
Refer to installation instructions shipped with roof curb for
more information.
48AW AND AY UNITS — Remove shipping covers from
supply and return air openings. Attach field-supplied ductwork
to unit. Connect to the unit with a single duct for all supply
openings and with a single duct for all return openings.
Splitting of the airflow into branch ducts should not be done at
the unit. Sufficient duct length should be used prior to branch-
ing to ensure the air temperatures are well mixed within the
ductwork. See Fig. 7-9 for duct opening dimensions. Secure all
ducts to building structure. Air distribution is shown in Fig. 7-9
and Fig. 13.
Install accessory barometric relief or power exhaust in the
field-fabricated return ductwork. Refer to Step 10 — Position
Power Exhaust/Barometric Relief Damper Hood section on
page 33 for more information.
Instructions continued on page 19.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket with the roof
curb as shown in Fig. 1-3. Improperly applied gasket can
also result in air leaks and poor unit performance.
WARNING
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90-degree
elbow turn in the supply and return ductwork between the
unit and the conditioned space. If a 90-degree elbow cannot
be installed, then a grille of sufficient strength and density
should be installed to prevent objects from falling into the
conditioned space.
3
Fig. 1 — Roof Curb — 48AJ,AK020-035 Units
a48-6715
NOTES:
1. UNLESS OTHERWISE SPECIFIED, ALL DIMENSIONS ARE TO OUTSIDE OF PART.
2. ROOF CURB ACCESSORY CRRFCURB005A00 IS SHIPPED DISASSEMBLED.
3. ALL ROOF CURB PARTS ARE TO BE 14 GA. GALVANIZED STEEL.
4. UNITS WITH ELECTRIC HEAT MUST BE INSTALLED WITH A 90° ELBOW ON THE SUPPLY
DUCT PRIOR TO ANY SUPPLY TAKE OFFS OR BRANCHES.
5. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMENSIONS ARE IN INCHES.
4
Fig. 2 — Roof Curb — 48AJ,AK036-050 Units
a48-6716
NOTES:
1. UNLESS OTHERWISE SPECIFIED, ALL DIMENSIONS ARE TO OUTSIDE OF PART.
2. ROOF CURB ACCESSORY CRRFCURB005A00 IS SHIPPED DISASSEMBLED.
3. ALL ROOF CURB PARTS ARE TO BE 14 GA. GALVANIZED STEEL.
4. UNITS WITH ELECTRIC HEAT MUST BE INSTALLED WITH A 90° ELBOW ON THE SUPPLY
DUCT PRIOR TO ANY SUPPLY TAKE OFFS OR BRANCHES.
5. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMENSIONS ARE IN INCHES.
5
Fig. 3 — Roof Curb — 48AJ,AK051 and 060 Units
a48-6717
NOTES:
1. UNLESS OTHERWISE SPECIFIED, ALL DIMENSIONS ARE TO
OUTSIDE OF PART.
2. ROOF CURB ACCESSORY CRRFCURB005A00 IS SHIPPED DIS-
ASSEMBLED.
3. ALL ROOFCURB PARTS ARE TO BE 14 GA. GALVANIZED STEEL.
4. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMEN-
SIONS ARE IN INCHES.
6
* OPERATING WEIGHT INCLUDES LARGEST INDOOR FAN MOTOR, CU/AL COILS,
MODULATING POWER EXHAUST (VARIABLE AIR VOLUME), AND VARIABLE
FREQUENCY DRIVE (VARIABLE AIR VOLUME).
Fig. 4 — Base Unit Dimensions — 48AJ,AK020-035
a48-8235
NOTES:
1. WEIGHTS INCLUDE ECONOMIZER (STD).
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
TOP OF UNITS: NO OVERHANG
CONDENSER COIL: 4’ - 0“ [1219]
ECONOMIZER SIDE: 6’ - 0” [1829]
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 10’ - 0” [3048] (FOR
REMOVAL OF EVAPORATOR COIL)
4. FOR SMALLER SERVICE AND OPERATIONAL
CLEARANCES, CONTACT CARRIER APPLICA-
TION ENGINEERING DEPARTMENT.
5. BOTTOM DUCTS ARE DESIGNED TO BE AT-
TACHED TO ACCESSORY ROOF CURB. IF UNIT
IS MOUNTED ON DUNNAGE, IT IS RECOM-
MENDED THAT THE DUCTS BE SUPPORTED
BY CROSS BRACES AS DONE ON ACCESSO-
RY ROOF CURB.
6. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL
OTHER DIMENSIONS ARE IN INCHES.
7
* OPERATING WEIGHT INCLUDES LARGEST INDOOR FAN MOTOR, CU/AL COILS,
MODULATING POWER EXHAUST (VARIABLE AIR VOLUME), AND VARIABLE
FREQUENCY DRIVE (VARIABLE AIR VOLUME).
Fig. 5 — Base Unit Dimensions — 48AJ,AK036-050
a48-8236
N
OTES:
1. WEIGHTS INCLUDE ECONOMIZER (STD).
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
TOP OF UNITS: NO OVERHANG
CONDENSER COIL: 4’ - 0“ [1219]
ECONOMIZER SIDE: 6’ - 0” [1829]
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 10’ - 0” [3048] (FOR
REMOVAL OF EVAPORATOR COIL)
4. FOR SMALLER SERVICE AND OPERATIONAL
CLEARANCES, CONTACT CARRIER APPLICA-
TION ENGINEERING DEPARTMENT.
5. BOTTOM DUCTS ARE DESIGNED TO BE AT-
TACHED TO ACCESSORY ROOF CURB. IF UNIT
IS MOUNTED ON DUNNAGE, IT IS RECOM-
MENDED THAT THE DUCTS BE SUPPORTED BY
CROSS BRACES AS DONE ON ACCESSORY
ROOF CURB.
6. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL
OTHER DIMENSIONS ARE IN INCHES.
8
Fig. 6 — Base Unit Dimensions — 48AJ,AK051 and 060
9
Fig. 7 — Base Unit Dimensions — 48AW,AY020-035
A48-8380
NOTES:
1. WEIGHTS INCLUDE ECONOMIZER (STD).
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
TOP OF UNITS: NO OVERHANG
CONDENSER COIL: 4’ - 0“ [1219]
ECONOMIZER SIDE: 6’ - 0” [1829]
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 10’ - 0” [3048] (FOR REMOVAL OF
EVAPORATOR COIL)
4. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES,
CONTACT CARRIER APPLICATION ENGINEERING
DEPARTMENT.
5. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMEN-
SIONS ARE IN INCHES.
10
* OPERATING WEIGHT INCLUDES LARGEST INDOOR FAN MOTOR, CU/AL COILS,
MODULATING POWER EXHAUST (VARIABLE AIR VOLUME), AND VARIABLE
FREQUENCY DRIVE (VARIABLE AIR VOLUME).
Fig. 8 — Base Unit Dimensions — 48AW,AY036-050
a48-8239
NOTES:
1. WEIGHTS INCLUDE ECONOMIZER (STD).
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
TOP OF UNITS: NO OVERHANG
CONDENSER COIL: 4’ - 0“ [1219]
ECONOMIZER SIDE: 6’ - 0” [1829]
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 10’ - 0” [3048] (FOR REMOVAL
OF EVAPORATOR COIL)
4. FOR SMALLER SERVICE AND OPERATIONAL CLEAR-
ANCES, CONTACT CARRIER APPLICATION ENGINEER-
ING DEPARTMENT.
5. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DI-
MENSIONS ARE IN INCHES.
11
Fig. 9 — Base Unit Dimensions — 48AW,AY051 and 060
a48-8240
FOR CENTERS OF
GRAVITY, OPERATING
AND CORNER WEIGHTS,
SEE FIGURE 10
12
48AJ/AK LOW HEAT
48AJ/AK HIGH HEAT
48AJ/AK LOW HEAT
48AJ/AK HIGH HEAT
48AW/AY HIGH HEAT
48AW/AY LOW HEAT
48AW/AY LOW HEAT
48AW/AY HIGH HEAT
48AJ/AK051 LOW HEAT
48AJ/AK051 HIGH HEAT
48AW/AY051 LOW HEAT
48AW/AY051 HIGH HEAT
48AJ/AK060 LOW HEAT
48AW/AY060 LOW HEAT
48AJ/AK060 HIGH HEAT
48AW/AY060 HIGH HEAT
Fig. 10 — Center of Gravity and Weights — 48AJ,AK,AW,AY051,060
a50-8102
NOTES:
1. WEIGHTS INCLUDE ECONOMIZER OR OUTDOOR AIR
DAMPER.
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
TOP OF UNITS: NO OVERHANG
CONDENSER COIL: 4’ - 0“ [1219]
ECONOMIZER SIDE: 6’ - 0” [1829]
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 15’ - 0” [4572] (FOR REMOVAL
OF EVAPORATOR COIL)
4. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES,
CONTACT CARRIER APPLICATION ENGINEERING DEPART-
MENT.
5. BOTTOM DUCTS ARE DESIGNED TO BE ATTACHED TO AC-
CESSORY ROOF CURB. IF UNIT IS MOUNTED ON DUNNAGE,
IT IS RECOMMENDED THAT THE DUCTS BE SUPPORTED BY
CROSS BRACES AS DONE ON ACCESSORY ROOF CURB.
6. BASE UNIT WEIGHTS INCLUDE OUTDOOR AIR HOODS AND
FILTERS (INDOOR FAN MOTOR IS NOT INCLUDED). ADD IN-
DOOR FAN MOTOR, FIOPS, AND ACCESSORIES FOR TOTAL
OPERATING WEIGHT.
7. VAV MOTOR WEIGHTS INCLUDE INDOOR MOTOR, VFD, VFD
TRANSDUCER, AND ASSOCIATED WIRING.
8. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMEN-
SIONS ARE IN INCHES.
9. FOR SIDE-SUPPLY/RETURN APPLICATIONS, A SINGLE RE-
TURN AND SUPPLY DUCTWORK CONNECTION IS RECOM-
MENDED FOR COVERING ALL THREE RETURN AND ALL
THREE SUPPLY OPENINGS. THE ENTIRE AREA AROUND
THE DUCT OPENINGS IS AVAILABLE FOR A 1.5” DUCT
FLANGE ATTACHMENT.
LEGEND
CV Constant Volume
FIOP Factory-Installed Option
IFM Indoor Fan Motor
VAV Volume Air volume
VFD Variable Frequency Drive
13
Table 1 — Physical Data — 48AJ,AK,AW,AY Units
LEGEND *Sizes 020-040: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper
portion.
Sizes 041-060: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have
intertwined evaporator coils.
†Rollout switch is manual reset.
UNIT 48AJ,AK,AW,AY 020 025 027 030
NOMINAL CAPACITY (tons) 20 25 27 30
BASE UNIT See Operating Weights Table
OPERATING WEIGHT (lb)
COMPRESSOR
Quantity ... Type (Ckt 1/Ckt 2) 2…SR*782AT/1…SR*782AE
1…SR*812AT, 1…SR*942AT/
1…SR*942AE
2 ... SR*942AT/1…SR*942AE 2…SR*782AT/2…SR*812AT
Number of Refrigerant Circuits 22 22
Oil (oz) (Ckt 1, Ckt 2) Precharged Precharged Precharged Precharged
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1 26-8 33-8 35-8 29-0
Circuit 2 14-0 17-8 20-0 30-8
CONDENSER COIL* Internally Enhanced,
3
/
8
Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
Quantity 11 11
Rows ... Fins/in. 2 ... 15 3 ... 15 3 ... 15 4 ... 15
Total Face Area (sq ft) 33.3 33.3 33.3 33.3
CONDENSER FAN Propeller Type
Nominal Cfm 17,200 15,850 15,850 14,500
Quantity... Diameter (in.) 2 ... 30 2 ... 30 2 ... 30 2 ... 30
Motor Hp 11 11
EVAPORATOR COIL Internally Enhanced Copper Tubes, Aluminum Plate Fins with Intertwined Circuits
Tube Size (in.)
3
/
8
3
/
8
3
/
8
3
/
8
Rows ... Fins/in. 3 ... 15 3 ... 15 4 ... 15 4 ... 15
Total Face Area (sq ft) 31.7 31.7 31.7 31.7
EVAPORATOR FAN Centrifugal Type
Quantity ... Size (in.) 2 ... 20 X 15 2 ... 20 X 15 2 ... 20 X 15 2 ... 20 X 15
Type Drive Belt Belt Belt Belt
Nominal Cfm 8,000 10,000 11,000 12,000
Motor Hp 5 10 15 5 10 15 10 15 20 10 15 20
Motor Frame Size 184T 215T 254T 184T 215T 254T 215T 254T 256T 215T 254T 256T
Motor Bearing Type Ball Ball Ball Ball
Maximum Allowable Rpm 1200 1200 1200 1200
Motor Pulley Pitch Diameter (in.) 4.8 4.4 5.7 4.8 6.1 5.5 4.4 4.9 5.9 4.4 5.7 5.9
Nominal Motor Shaft Diameter (in.) 1
1
/
8
1
3
/
8
1
5
/
8
1
1
/
8
1
3
/
8
1
5
/
8
1
3
/
8
1
5
/
8
1
5
/
8
1
3
/
8
1
5
/
8
1
5
/
8
Fan Pulley Pitch Diameter (in.) 12.4 8.6 9.1 12.4 11.1 8.7 9.4 8.1 8.7 9.5 9.1 8.7
Nominal Fan Shaft Diameter (in.) 1
15
/
16
1
15
/
16
1
15
/
16
1
15
/
16
Belt Quantity 112 1 1 2 2 22222
Belt Type BX56 BX50 5VX530 BX56 5VX570 5VX530 BX50 5VX530 5VX530 BX50 5VX530 5VX530
Belt Length (in.) 56 63 53 56 57 53 50 50 53 50 53 53
Pulley Center Line Distance (in.) 16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.0-17.9 15.6-18.4 15.0-17.9 15.0-17.9
Factory Speed Setting (rpm) 677 895 1096 677 962 1106 819 1096 1187 884 1096 1187
FURNACE SECTION
Supply Line Pressure Range 5.0-in. wg min/13.5-in. wg max.
Rollout Switch Cutout
Temp (F)† 225 225 225 225
Burner Orifice Diameter (in. ...drill size)
Natural Gas Std .111 ... 34 .111 ... 34 .111 ... 34 .111 ... 34
Liquid Propane Alt .089 ... 43 .089 ... 43 .089 ... 43 .089 ... 43
Thermostat Heat Anticipator Setting
Stage 1 (amps) 0.24 0.24 0.24 0.24
Stage 2 (amps) 0.13 0.13 0.13 0.13
Gas Input (Btuh) Stage 1
(Low Heat/High Heat)
262,500/394,000 262,500/394,000 262,500/394,000 262,500/394,000
Stage 2
(Low Heat/High Heat)
350,000/525,000 350,000/525,000 350,000/525,000 350,000/525,000
Efficiency (Steady State) (%) 82 82 82 82
Temperature Rise Range 15-45/35-65 15-45/35-65 15-45/35-65 15-45/35-65
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5
Gas Valve Quantity 22 22
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 426
Reset (Auto.) 320 320 320 320
MIXED-AIR FILTERS
Quantity ... Size (in.) Standard 10 ... 20 x 24 x 2 10 ... 20 x 24 x 2 10 ... 20 x 24 x 2 10 ... 20 x 24 x 2
Pleated 5 ... 20 x 20 x 4
5 ... 20 x 24 x 4
5 ... 20 x 20 x 4
5 ... 20 x 24 x 4
5 ... 20 x 20 x 4
5 ... 20 x 24 x 4
5 ... 20 x 20 x 4
5 ... 20 x 24 x 4
OUTDOOR-AIR FILTERS
Quantity...Size (in.)
8...16 x 25 x 2
4...20 x 25 x 2
POWER EXHAUST
Direct Drive, Single-Phase Motors (Factory-Wired for High Speed Operation), Forward-Curved Fan Wheels with Backdraft Dampers on Each Fan
Housing
Motor, Quantity...Hp 4...1
Fan, Diameter...Width (in.) 11 x 10
Al Aluminum
Cu Copper
14
Table 1 — Physical Data — 48AJ,AK,AW,AY Units (cont)
LEGEND *Sizes 020-040: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper
portion.
Sizes 041-060: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have
intertwined evaporator coils.
†Rollout switch is manual reset.
UNIT 48AJ,AK,AW,AY 035 036 040 041
NOMINAL CAPACITY (tons) 35 35 40
40
BASE UNIT See Operating Weights Table
OPERATING WEIGHT (lb)
COMPRESSOR
Quantity ... Type (Ckt 1/Ckt 2)
1…SR*812AT,
1…SR*942AT/2…SR*942AT
1…SR*812AT,
1…SR*942AT/2…SR*942AT
2…SR*942AT/2…SM125 2…SR*942AT/2…SM125
Number of Refrigerant Circuits 2222
Oil (oz) (Ckt 1, Ckt 2) Precharged Precharged Precharged Precharged
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1 33-0 36-0 36-0 47-0
Circuit 2 38-0 58-0 47-0 47-0
CONDENSER COIL* Internally Enhanced,
3
/
8
Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
Quantity 1222
Rows ... Fins/in. 4 ... 15 2...15/4…15 2 ... 15 / 4 … 15 4...15/4…15
Total Face Area (sq ft) 33.3 66.7 66.7 66.7
CONDENSER FAN Propeller Type
Nominal Cfm 14,500 30,000 30,000 30,000
Quantity... Diameter (in.) 2 ... 30 4...30 4 ... 30 4...30
Motor Hp 1111
EVAPORATOR COIL Internally Enhanced Copper Tubes, Aluminum Plate Fins with Intertwined Circuits
Tube Size (in.)
1
/
2
1
/
2
1
/
2
1
/
2
Rows ... Fins/in. 6 ... 16 4...17 4 ... 16 4...17
Total Face Area (sq ft) 31.3 31.3 31.3 31.3
EVAPORATOR FAN Centrifugal Type
Quantity ... Size (in.) 2 ... 20 X 15 2...20 X 15 2 ... 20 X 15 2...20 X 15
Type Drive Belt Belt Belt Belt
Nominal Cfm 14,000 14,000 16,000 16,000
Motor Hp 15 20 25 15 20 25 15 20 25 15 20 25
Motor Frame Size 254T 256T 284T 254T 256T 284T 254T 256T 284T 254T 256T 284T
Motor Bearing Type Ball Ball Ball Ball
Maximum Allowable Rpm 1300 1300 1300 1300
Motor Pulley Pitch Diameter (in.) 5.15.76.25.35.77.55.35.77.55.35.77.5
Nominal Motor Shaft Diameter (in.) 1
5
/
8
1
5
/
8
1
7
/
8
1
5
/
8
1
5
/
8
1
7
/
8
1
5
/
8
1
5
/
8
1
7
/
8
1
5
/
8
1
5
/
8
1
7
/
8
Fan Pulley Pitch Diameter (in.) 8.7 8.7 8.7 9.5 9.5 11.1 9.5 9.5 11.1 9.5 9.5 11.1
Nominal Fan Shaft Diameter (in.) 1
15
/
16
1
15
/
16
1
15
/
16
1
15
/
16
Belt Quantity 222222222222
Belt Type 5VX500 5VX530 5VX550 5VX530 5VX550 5VX590 5VX530 5VX550 5VX590 5VX530 5VX550 5VX590
Belt Length (in.) 50 53 55 53 55 59 53 55 59 53 55 59
Pulley Center Line Distance (in.) 15.0-17.9 15.0-17.9 15.0-17.9 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 15.0-17.9 14.6-17.6
Factory Speed Setting (rpm) 1005 1147 1247 976 1050 1182 976 1050 1182 976 1050 1182
FURNACE SECTION
Supply Line Pressure Range 5.0-in. wg min/13.5-in. wg max.
Rollout Switch Cutout
Temp (F)† 225 225 225 225
Burner Orifice Diameter (in ...drill size)
Natural Gas Std .111 ... 34 .120...31 .120 ... 31 .120...31
Liquid Propane Alt .089 ... 43 .096...41 .096 ... 41 .096...41
Thermostat Heat Anticipator Setting
Stage 1 (amps) 0.24 0.1 0.24 0.1
Stage 2 (amps) 0.13 0.1 0.13 0.1
Gas Input (Btuh) Stage 1
(Low Heat/High Heat)
262,500/394,000 300,000/600,000 300,000/600,000 300,000/600,000
Stage 2
(Low Heat/High Heat)
350,000/525,000 400,000/800,000 400,000/800,000 400,000/800,000
Efficiency (Steady State) (%) 82 82 82 82
Temperature Rise Range 15-45/35-65 10-40/30-60 10-40/3 -60 10-40/30-60
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5
Gas Valve Quantity 2222
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 426
Reset (Auto.) 320 320 320 320
MIXED-AIR FILTERS
Quantity ... Size (in.) Standard 10 ... 20 x 24 x 2 10...20 x 24 x 2
5...20 x 20 x 4
5...20 x 20 x 4
10 ... 20 x 24 x 2 10...20 x 24 x 2
5...20 x 20 x 4
5...20 x 20 x 4
Pleated 5 ... 20 x 20 x 4
5 ... 20 x 24 x 4
5 ... 20 x 20 x 4
5 ... 20 x 24 x 4
OUTDOOR-AIR FILTERS
Quantity...Size (in.)
8...16 x 25 x 2
4...20 x 25 x 2
POWER EXHAUST Direct Drive, Single-Phase Motors (Factory-Wired for High Speed Operation), Forward-Curved Fan Wheels with Backdraft Dampers on Each Fan Housing
Motor, Quantity...Hp 4...1
Fan, Diameter...Width (in.) 11 x 10
Al Aluminum
Cu Copper
15
Table 1 — Physical Data — 48AJ,AK,AW,AY Units (cont)
LEGEND *Sizes 020-040: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper
portion.
Sizes 041-060: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have
intertwined evaporator coils.
†Rollout switch is manual reset.
UNIT 48AJ,AK,AW,AY 050 051 060
NOMINAL CAPACITY (tons) 50 50 60
BASE UNIT See Operating Weights Table
OPERATING WEIGHT (lb)
COMPRESSOR
Quantity ... Type (Ckt 1/Ckt 2)
2…SM125/1…SM125,
1…SM175
2…SM125/2…SM125
1..SM160,1..SM175/
1..SM160,1..SM175
Number of Refrigerant Circuits 22 2
Oil (oz) (Ckt 1, Ckt 2) Precharged Precharged Precharged
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1 64-4 98-0 81-0
Circuit 2 58-8 98-0 81-0
CONDENSER COIL* Internally Enhanced,
3
/
8
Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
Quantity 22 2
Rows ... Fins/in. 4 ... 15 4…15 4…15
Total Face Area (sq ft) 66.7 100 100
CONDENSER FAN Propeller Type
Nominal Cfm 25,600 38,400 38,400
Quantity... Diameter (in.) 4 ... 30 6...30 6 ... 30
Motor Hp 11 1
EVAPORATOR COIL Internally Enhanced Copper Tubes, Aluminum Plate Fins with Intertwined Circuits
Tube Size (in.)
1
/
2
1
/
2
1
/
2
Rows ... Fins/in. 6 ... 16 4...17 4 ... 17
Total Face Area (sq ft) 31.3 48.1 48.1
EVAPORATOR FAN Centrifugal Type
Quantity ... Size (in.) 2 ... 20 X 15 3...20 X 15 3 ... 20 X 15
Type Drive Belt Belt Belt
Nominal Cfm 20,000 20,000 24,000
Motor Hp 20 25 30 20 25 30
40
(High Eff.)
40
(Prem. Eff.)
25 30
40
(High Eff.)
40
(Prem. Eff.)
Motor Frame Size 256T 284T 286T 256T 284T 286T 324T 324T 284T 286T 324T 324T
Motor Bearing Type Ball Ball Ball
Maximum Allowable Rpm 1300 1200 1200
Motor Pulley Pitch Diameter (in.) 5.7 6.2 6.7 5.9 5.3 5.9 6.5 9.5 5.3 5.9 6.5 9.5
Nominal Motor Shaft Diameter (in.) 1
5
/
8
1
7
/
8
1
7
/
8
1
5
/
8
1
7
/
8
1
7
/
8
2
1
/
8
2
1
/
8
1
7
/
8
1
7
/
8
2
1
/
8
2
1
/
8
Fan Pulley Pitch Diameter (in.) 9.5 9.5 9.5 11.1 9.1 9.5 9.5 13.7 9.1 9.5 9.5 13.7
Nominal Fan Shaft Diameter (in.) 1
15
/
16
1
15
/
16
1
15
/
16
Belt Quantity 2222333 2 333 2
Belt Type 5VX550 5VX570 5VX570 5VX560 5VX530 5VX550 5VX570 5VX650 5VX530 5VX550 5VX570 5VX650
Belt Length (in.) 55 57 57 56 53 55 57 65 53 55 57 65
Pulley Center Line Distance (in.) 15.0-17.9 14.6-17.6 14.6-17.6 15.0-17.9 15.2-17.5 14.7-17.2 14.2-17.0 14.2-17.0 15.2-17.5 14.7-17.2 14.2-17.0 14.2-17.0
Factory Speed Setting (rpm) 1061 1154 1249 930 1019 1086 1197 1214 1019 1086 1197 1214
FURNACE SECTION
Supply Line Pressure Range 5.0-in. wg min/13.5-in. wg max.
Rollout Switch Cutout
Temp (F)† 225 225 225
Burner Orifice Diameter (in ...drill size)
Natural Gas Std .120 ... 31 .120...31 .120 ... 31
Liquid Propane Alt .096 ... 41 .096...41 .096 ... 41
Thermostat Heat Anticipator Setting
Stage 1 (amps) 0.24 0.1 0.36
Stage 2 (amps) 0.13 0.1 0.13
Gas Input (Btuh) Stage 1
(Low Heat/High Heat)
300,000/600,000 582,000/873,000 582,000/873,000
Stage 2
(Low Heat/High Heat)
400,000/800,000 776,000/1,164,000 776,000/1,164,000
Efficiency (Steady State) (%) 82 82 82
Temperature Rise Range 10-40/30-60 10-40/30-60 10-40/30-60
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.3 3.3
Liquid Propane Alt 3.5 3.3 3.3
Gas Valve Quantity 23 3
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426
Reset (Auto.) 320 320 320
MIXED-AIR FILTERS
Quantity ... Size (in.) Standard 10 ... 20 x 24 x 2 16...20 x 24 x 2
8...20 x 20 x 4
8...20 x 24 x 4
16 ... 20 x 24 x 2
Pleated 5 ... 20 x 20 x 4
5 ... 20 x 24 x 4
8 ... 20 x 20 x 4
8 ... 20 x 24 x 4
OUTDOOR-AIR FILTERS
Quantity...Size (in.)
8...16 x 25 x 2
4...20 x 25 x 2
12...16 x 25 x 2
6...20 x 25 x 2
POWER EXHAUST Direct Drive, Single-Phase Motors (Factory-Wired for High Speed Operation), Forward-Curved Fan Wheels with Backdraft Dampers on Each Fan Housing
Motor, Quantity...Hp 4...1
11 x 10
6...1
11 x 10 Fan, Diameter...Width (in.)
Al Aluminum
Cu Copper
16
50AJ/AK020 4607 2090 87.7 2227 70.9 1801 42.0 1067
48AJ/AKD020 4697 2131 87.7 2227 71.9 1826 42.5 1080
48AJ/AKE020 4777 2167 87.7 2227 72.8 1849 41.0 1041
50AW/AY020 4685 2125 87.7 2227 70.9 1801 42.0 1067
48AW/AYD020 4737 2149 87.7 2227 71.9 1826 42.5 1080
48AW/AYE020 4817 2185 87.7 2227 72.8 1849 41.0 1041
50AJ/AK025 4680 212387.7 2227 68.0 1727 43.9 1115
48AJ/AKD025 4770 2164 87.7 2227 69.1 1755 44.3 1125
48AJ/AKE025 4850 2200 87.7 2227
69.6
1768 44.6 1133
50AW/AY025 4758 215887.7 2227 68.0 1727 43.9 1115
48AW/AYD025 4810 2182
87.7 2227 69.1 1755 44.3 1125
48AW/AYE025 4890 221887.7 2227 69.6 1768 44.6 1133
50AJ/AK027 4873 2210 87.7 2227 68.0 1727 43.9 1115
48AJ/AKD027 4963 2251 87.7 2227
69.1
1755 44.3 1125
48AJ/AKE027 5043 2287 87.7 2227 69.6 1768 44.6 1133
50AW/AY027 4951 2246 87.7 2227 68.0 1727 43.9 1115
48AW/AYD027 5003 2269 87.7 2227 69.1 1755 44.3 1125
48AW/AYE027 5083 2306 87.7 2227 69.6 1768 44.6 1133
50AJ/AK030 5023 227887.7 2227 68.0 1727 43.6 1107
48AJ/AKD030 5113 2319 87.7 2227 69.1 1755 44.0 111
8
48AJ/AKE030 5193 2356 87.7 2227 69.6 1768 44.3 1125
50AW/AY030 5101 2314 87.7 2227 68.0 1727 43.6 1107
48AW/AYD030 5153 2337 87.7 2227 69.1 1755 44.0 1118
48AW/AYE030 5233 2374 87.7 2227 69.6 1768 44.3 1125
50AJ/AK035 5229 2372 87.7 2227 68.3 173546.5 1181
48AJ/AKD035 5434 2465 87.7 2227 69.4 1763 46.9 1191
48AJ/AKE035 5594 2537 87.7 2227 70.0 1778 47.2 1199
50AW/AY035 5422 2459 87.7 2227 68.3
173546.5 1181
48AW/AYD035 5474 2483 87.7 2227 69.4 1763 46.9 1191
48AW/AYE0355634 2556 87.7 2227 70.0 1778 47.2 1199
50AJ/AK036 5609 2544 87.7 2227 93.4 2372 45.3 1152
48AJ/AKD036 5814 2637 87.7 2227 94.8 2409 45.8 1163
48AJ/AKE036 5974 2710 87.7 2227 96.3 2446 46.1 1172
50AW/AY0365802 2632 87.7 2227 93.3 2370 45.4 1153
48AW/AYD036 5854 2655 87.7 2227 94.8 2408 45.8 1163
48AW/AYE0
36 6014 272887.7 2227 96.3 2446 46.1 1172
50AJ/AK040 5769 2617 87.7 2227 90.8 2306 46.5 1181
48AJ/AKD040 5974 2710 87.7 2227 92.3 2344 46.9 1191
48AJ/AKE040
6134
2782 87.7 2227 93.8 2383 47.2 1199
50AW/AY040 5962 2704 87.7 2227 90.8 2306 46.5 1181
48AW/AYD040 6014 2728 87.7 2227 92.3 2344 46.9 1191
48AW/AYE040 6174 2801 87.7 2227 93.8 2383 47.2 1199
50AJ/AK041 5885 2669 87.7 2227 89.0 2261 45.6 1158
48AJ/AKD041 6090 2762 87.7 2227 90.5 2300 46.0 1169
48AJ/AKE041 6250 2835 87.7 2227 92.1 2338 46.3 1177
50AW/AY041 6078 2757 87.7 2227 89.1 2262 45.6 1159
48AW/AYD041 61302781 87.7 2227 90.6 2300 46.0 1169
48AW/AYE041 6290 285387.7 2227 92.1 233946.3 11 77
50AJ/AK050 6338 2875 87.7 2227 89.2 2266 46.1 1171
48AJ/AKD050 6543 296887.7 2227 90.7 2304 46.5 1181
48AJ/AKE050 6703 3040 87.7 2227 92.2 2342 46.8 11 89
50AW/AY050 6531 2962 87.7 2227 89.2 2266 46.1 1171
48AW/AYD050 6583 2986 87.7 2227 90.7 2304 46.5 1181
48AW/AYE050 67433059 87.7 2227 92.2 2342 46.8 1189
50AJ/AK051 8544 38
76 161.7 4106 126.0 3200 44.6 1133
48AJ/AKD051 8674 3935 161.7 4106 133.2 3383 46.6 1185
48AJ/AKE051 8914 4043 161.7 4106 140.2 3562 48.7 1237
50AW/AY051 8759 3973 161.7 4106 125.9 3198 44.6 1133
48AW/AYD051 8714 3953 161.7 4106 133.2 3382 46.6 1185
48AW/AYE051 8964 4066 161.7 4106 140.2 3562 48.7 1237
50AJ/AK060 8708 3950 161.7 4106 123.6 3139 44.6 1133
48AJ/AKD060 8838 4009 161.7 4106 130.7 3320 46.6 1184
48AJ/AKE060 9078
4118 161.7 4106 137.7 3498 48.6 1234
50AW/AY060 8923 4047 161.7 4106 123.6 3139 44.6 1133
48AW/AYD060 8878 4027 161.7 4106 130.7 3320 46.6 1184
48AW/AYE060 9128 4140 161.7 4106 137.7 3498 48.6 1234
NOTE: Rig with four cables and spread with two 92 inch (2337 MM) spreader bars.
Maintain a distance of 74 inches (1880 MM) from top of unit to eyehook.
CAUTION - NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE WHEN RIGGING.
CENTER
OF
GRAVITY
WEIGHT BAC
LB
KG
INCHES
MM INCHES
MM
INCHES
MM
B
A
C
NOTE:
Add 312 lb (142 kg) for export crating. (020-035 units)
Add 346 lb (157 kg) for export crating. (036-050 units)
Add 588 lb (266 kg) for export crating. (051 and 060 units)
Add 220 lb (100 kg) for copper condenser coil. (020-035 units)
Add 380 lb (172 kg) for copper condenser coil. (036-050 units)
Add 651 lb (295 kg) for copper condenser coil. (051 and 060 units)
UNIT
Fig. 11 — Rigging Information
a48-8246
17
Table 2 — Unit Operating Weights
Table 3 — Option and Accessory Weights
Table 4 — Constant Volume Fan Motor Weights
LEGEND
Table 5 — Variable Volume Fan Motor Weights
NOTES:
1. Base unit weight includes outdoor-air hoods. Base unit weight
does NOT include indoor-fan motor. ADD indoor-fan motor,
FIOPs, and accessories for TOTAL operating weight.
2. The VAV motor weights include indoor fan motor and the VFD
(variable frequency drive), VFD transducers, and associated
wiring.
UNIT
BASE UNIT WEIGHTS — lb
020 025 027 030 035 036 040 041 050 051 060
48AJ/AK Low Heat 3842 3915 4032 4182 4435 4815 4975 5091 5446 7224 7388
48AJ/AK High Heat 3922 3995 4112 4262 4595 4975 5135 5251 5606 7464 7628
48AW/AY Low Heat 3882 3955 4072 4222 4475 4855 5015 5131 5486 7264 7428
48AW/AY High Heat 3962 4035 4152 4302 4635 5015 5175 5291 5646 7514 7678
OPTION/
ACCESSORY
OPTION/ACCESSORY WEIGHTS — lb
020 025 027 030 035 036 040 041 050 051 060
Barometric Relief 300 300 300 300 300 300 300 300 300 450 450
Power Exhaust 450 450 450 450 450 450 450 450 450 675 675
Mod. Power Exhaust 500 500 500 500 500 500 500 500 500 725 725
Cu Tubing/Cu Fin Condenser Coil 220 220 220 220 285 380 285 380 380 651 651
Outdoor Air Hood Crate and Packaging
(Less Hoods' Weight)
45 45 45 45 45 45 45 45 45 45 45
(Packaging Only) (Packaging Only)
Outdoor Air Hoods/Filters 170 170 170 170 170 170 170 170 170 255 255
Hail Guard 73 73 73 73 73 146 146 146 146 219 219
Roof Curb (14-in.) 365 365 365 365 410 410 410 410 410 540 585
CV MOTOR WEIGHTS — lb
MOTOR
HP
UNIT
VOLTAGE
HIGH
EFFICIENCY
IFM
PREMIUM
EFFICIENCY
IFM
5
230/460 78 94
575 78 92
10
230/460 118 164
575 118 156
15
230/460 150 217
575 150 220
20
230/460 212 250
575 212 258
25
230/460 240 309
575 240 319
30
230/460 283 355
575 283 359
40
230/460 372 415
575 372 410
Cu Copper
CV Constant Volume
FIOP Factory-Installed Option
HP Horsepower
IFM Indoor Fan Motor
VAV Variable Air Volume
VFD Variable Frequency Drive
VAV MOTOR WEIGHTS — lb
MOTOR
HP
UNIT
VOLTAGE
HIGH
EFFICIENCY
IFM
PREMIUM
EFFICIENCY
IFM
5
230/460 125 141
575 163 177
10
230/460 204 250
575 204 242
15
230/460 238 305
575 240 310
20
230/460 348 386
575 304 350
25
230/460 377 446
575 375 454
30
230/460 480 552
575 418 494
40
230/460 637 680
575 587 625
LEGEND AND NOTES FOR TABLES 2-5
18
Table 6 — Evaporator Fan Motor Data
NOTES:
1. Motor shaft speed is 1750 rpm. The fan shaft diameter is 1
15
/
16
inches.
2. All indoor fan motors meet the minimum efficiency requirements
as established by the Energy Policy Act of 1992 (EPACT), effective
October 24, 1997.
UNIT
SIZE
48AJ,AK,
AW,AY
MOTOR
HP
MOTOR
SHAFT DIA.
(in.)
FAN
SHAFT
SPEED
(rpm)
MOTOR
SHEAVE
(P/N)
MOTOR
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
FAN
SHEAVE
(P/N)
FAN
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
BELT
(Quantity)
(P/N)
BELT
TENSION
(lb at .25 in.)
020
5 1.125 677 BK55 4.8 NONE - 1.125 1B5V124 12.4 B - 1.9375 BX56 8
10 1.375 895 2BK50 4.4 NONE - 1.375 2B5V86 8.6 B - 1.9375 BX50 8
15 1.625 1096 2B5V56 5.7 B - 1.625 2B5V90 9.1 B - 1.9375 (2) 5VX530 9
025
5 1.125 677 BK55 4.8 NONE - 1.125 1B5V124 12.4 B - 1.9375 BX56 8
10 1.375 962 1B5V60 6.1 H - 1.375 1B5V110 11.1 B - 1.9375 5VX570 11
15 1.625 1106 2B5V54 5.5 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX530 9
027
10 1.375 819 2BK50 4.4 NONE - 1.375 2B5V94 9.4 B - 1.9375 (2) BX50 8
15 1.625 1096 2B5V56 5.7 B - 1.625 2B5V90 9.1 B - 1.9375 (2) 5VX530 10
20 1.625 1187 2B5V58 5.9 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX530 11
030
10 1.375 884 2BK50 4.4 H - 1.375 2B5V94 9.5 B - 1.9375 (2) BX50 8
15 1.625 1096 2B5V56 5.7 B - 1.625 2B5V90 9.1 B - 1.9375 (2) 5VX530 9
20 1.625 1187 2B5V58 5.9 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX530 11
035
15 1.625 1005 2B5V50 5.1 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX500 9
20 1.625 1147 2B5V56 5.7 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX530 10
25 1.875 1247 2B5V62 6.2 B - 1.875 2B5V86 8.7 B - 1.9375 (2) 5VX530 11
036
15 1.625 976 2B5V52 5.3 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX530 10
20 1.625 1050 2B5V56 5.7 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX550 11
25 1.875 1182 2B5V74 7.5 B - 1.875 2B5V110 11.1 B - 1.9375 (2) 5VX590 11
040
15 1.625 976 2B5V52 5.3 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX530 10
20 1.625 1050 2B5V56 5.7 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX550 11
25 1.875 1182 2B5V74 7.5 B - 1.875 2B5V110 11.1 B - 1.9375 (2) 5VX590 11
041
15 1.625 976 2B5V52 5.3 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX530 10
20 1.625 1050 2B5V56 5.7 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX550 11
25 1.875 1182 2B5V74 7.5 B - 1.875 2B5V110 11.1 B - 1.9375 (2) 5VX590 11
050
20 1.625 1061 2B5V56 5.7 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX550 10
25 1.875 1154 2B5V62 6.2 B - 1.875 2B5V94 9.5 B - 1.9375 (2) 5VX570 11
30 1.875 1247 2B5V66 6.7 B - 1.875 2B5V94 9.5 B - 1.9375 (2) 5VX570 13
051
20 1.625 930 2B5V58 5.9 B - 1.625 2B5V110 11.1 B - 1.9375 (2) 5VX560 11
25 1.875 1019 3B5V52 5.3 B - 1.875 3B5V90 9.1 B - 1.9375 (3) 5VX530 12
30 1.875 1086 3B5V58 5.9 B - 1.875 3B5V94 9.5 B - 1.9375 (3) 5VX550 12
40 High 2.125 1197 3B5V64 6.5 B - 2.125 3B5V94 9.5 B - 1.9375 (3) 5VX570 14
40 Prem. 2.125 1214 2B5V94 9.5 B - 2.125 2B5V136 13.7 B - 1.9375 (2) 5VX650 15
060
25 1.875 1019 3B5V52 5.3 B - 1.875 3B5V90 9.1 B - 1.9375 (3) 5VX530 12
30 1.875 1086 3B5V58 5.9 B - 1.875 3B5V94 9.5 B - 1.9375 (3) 5VX550 12
40 High 2.125 1197 3B5V64 6.5 B - 2.125 3B5V94 9.5 B - 1.9375 (3) 5VX570 14
40 Prem. 2.125 1214 2B5V94 9.5 B - 2.125 2B5V136 13.7 B - 1.9375 (2) 5VX650 15
Fig. 12 — Air Distribution — Thru-the-Bottom
Fig. 13 — Air Distribution — Thru-the-Side
a48-8241
a48-8242
19
Step 5 — Install Flue Hood
48AJ,AK,AW,AY020-050 UNITS Flue hood is shipped
inside gas section of unit. To install, secure flue hood to access
panel. See Fig. 14.
48AJ,AK,AW,AY051 AND 060 UNITS — Flue hood and
wind baffle are shipped inside gas section of unit. To install, se-
cure flue hood to access panel. Install the two pieces of the
wind baffle over the flue hood. See Fig. 15.
NOTE: When properly installed, flue hood will line up with
combustion fan housing. See Fig. 16.
Step 6 — Trap Condensate Drain — See Fig. 4-9
for drain location. Condensate drain is open to atmosphere and
must be trapped. Install a trapped drain at the drain location.
One 1-in. FPT coupling is provided inside the unit evaporator
section for condensate drain connection. A trap at least 4-in.
deep must be used. See Fig. 17. Trap must be installed to pre-
vent freeze-up.
Condensate pans are sloped so that water will completely
drain from the condensate pan to comply with indoor air quali-
ty guidelines. The condensate drain pans are not insulated.
Step 7 — Install Gas Piping — Unit is equipped for
use with natural gas. Installation must conform with local
building codes or, in the absence of local codes, with the Na-
tional Fuel Gas Code, ANSI Z223.1.
Install manual gas shutoff valve with a
1
/
8
-in. NPT pressure
tap for test gage connection at unit. Field gas piping must in-
clude sediment trap and union. See Fig. 18. An
1
/
8
-in. NPT is
also located on the gas manifold adjacent to the gas valve.
WARNING
Do not pressure test gas supply while connected to unit.
Always disconnect union before servicing. Serious injury
could result.
FLUE HOOD
GAS SECTION
ACCESS PANEL
WIND
BAFFLE
TOP VIEW SIDE VIEW
Fig. 14 — Flue Hood Location
(48AJ,AK,AW,AY020-050 Units)
Fig. 15 — Flue Hood Location
(48AJ,AK,AW,AY051 and 060 Units)
a48-3712
a48-4076
Fig. 16 — Combustion Fan Housing Location
(48AJ,AK,AW,AY020-050 Shown)
a48-3823
Fig. 17 — Condensate Drain Trap Piping Details
(Typical Roof Curb or Slab Mount Shown)
a48-3714
20
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
OPTIONAL STAGED GAS UNITS See Table 7 for staged
gas information. Staging pattern is selected during controls
start-up.
For complete information and service instructions for
Staged Gas Control Units, see Control Operation and Trouble-
shooting literature.
Table 7 — 48A Series Staged Gas Control
Step 8 — Make Electrical Connections
POWER WIRING Units are factory wired for the voltage
shown on the unit nameplate.
Provide a unit safety disconnect switch in the main power
supply to each unit (see Fig. 19). Select switch size and mount-
ing location in accordance with applicable local codes or
National Electrical Code (NEC). If combining the functions of
safety disconnect with maximum overcurrent protection
(MOCP) fuses (“fused disconnect”), coordinate safety switch
size with MOCP size data as marked on unit informative plate.
Unit may be equipped with optional factory-installed non-
fused disconnect switch (see Fig. 19). Provide maximum
overcurrent protection devices (fuses or HACR breakers, per
local codes) in branch circuit wiring remote from unit. Observe
requirements of NEC Article 440. Install service switch
upstream of remote fuses if required.
The main power terminal block is suitable for use with
aluminum or copper wire. See Fig. 19. Units have circuit
breakers for compressors, fan motors, and control circuit. The
unit must be electrically grounded in accordance with local
codes, or in absence of local codes, with NEC, ANSI C1-latest
year.
FIELD POWER SUPPLY Unit is factory wired for volt-
age shown on unit nameplate. See Tables 8A and 8B for elec-
trical data.
Field wiring can be brought into the unit from bottom
(through basepan and roof curb) or through side of unit (corner
post next to control box).
A 3
1
/
2
-in. NPT coupling for field power wiring and a
3
/
4
-in.
NPT coupling for 24-v control wiring are provided in basepan.
In the side post, there are two 2
1
/
2
-in. (48A020-035) or 3-in.
(48A036-060) knockouts for the field power wiring. See
Fig. 4-9. If control wiring is to be brought in through the side of
unit, a
7
/
8
-in. diameter hole is provided in the condenser side
post next to the control box.
Do not route control wiring in the same conduit as power
wiring.
If disconnect box is mounted to corner post, be careful not
to drill or screw into the condenser coil.
IMPORTANT: Natural gas pressure at unit gas connection
must not be less than 5 in. wg or greater than 13.5 in. wg.
MODEL NUMBER POSITION
NUMBER OF
STAGES
HEAT SIZE
5 6,7,8
S
020
025
027
030
035
036
040
041
050
5 stages
Low
T
035
036
040
041
050
High
T
020
025
027
030
7 stages High
T 051,060 9 stages High
S 051,060 11 stages Low
Fig. 18 — Field Gas Piping
a48-2524
FIELD SUPPLIED
DISCONNECT PER NEC
FIELD
POWER
SUPPLY
11
21
22
23
13
12
TB1
EQUIP GND
FIELD POWER WIRING
11
21
22
23
13
12
GND
OPTIONAL
FACTORY-INSTALLED
DISCONNECT
FIELD-INSTALLED DISCONNECT
FACTORY-INSTALLED DISCONNECT
LEGEND
GND Ground
NEC National Electrical Code
TB Terminal Block
Fig. 19 — Field Power Wiring Connections
a48-6977
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36