Emerson WEB/485 User manual

  • Hello! I am an AI chatbot trained to assist you with the Emerson WEB/485 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
1
LIEBERT INTELLISLOT
®
WEB/485 CARD WITH ADAPTER
Product Specification/Installation Sheet
Description
The IntelliSlot Web/485 Card with Adapter
provides 10/100baseT Ethernet Network and
Modbus connectivity for your Emerson Network
Power equipment.
Operating status is monitored and alarms are
communicated via the network, using SNMP
and/or HTTP protocols and over RS-485 using
the Modbus protocol.
Additional Features
Compatibility With Other Emerson Network Power Products
Overall and Mounting Dimensions
SNMP v1, v2c with MIB-II support
HTTP/HTTPS 1.1
Telnet
BootP, DHCP per RFC2131
Secure Sockets (SSL)
Remote firmware updates via HTTP
Precision Cooling Unit (Controller*) *Controller Codes Large UPS
Liebert Challenger™ 3000 (L00, L15,
LSM, LAM)
Liebert DataMate™ (L0B)
Liebert Deluxe System/3™ (L10, L15,
LSM, LAM)
Liebert Himod™ (LAM)
Liebert Industrial Cooling Series™
(L10, LSM, LAM)
Liebert Mini-Mate™ (L0B)
Liebert Mini-Mate2™ (MM2)
Liebert Mini-Mate2 8 Ton (L8T)
Hiross™ Microface IGMnet
PEC/Atlas™ (CEMS100/LECS15)
L00:
L0B:
L10:
L15:
LSM:
LAM:
Level 00
Level 0B
Level 10
Level 15
Standard
Microprocessor
Advanced
Microprocessor
Liebert Npower™
Liebert Series 300™
Liebert Series 600™/610™ (Single Module)
Liebert Series 610 System Control Cabinet
(Multi-Module)
Hiross 7200 (EMEA)
Hiross HiPulse™ (EMEA)
Power Management
Liebert Datawave
®
Liebert FPC™
Liebert Precision Power Center™
Liebert Static Transfer Switches:
STS™, STS2-3 pole, STS2/PDU
Six holes, each
0.156" diameter
3.2"
(81.3mm)
2.8"
(71.1mm)
7" (177.8mm)
4"
(101.6mm)
2.4"
(61mm)
3.4"
(86.4mm)
0.4" (10.2mm)
0.2" (5mm)
0.6" (15.3mm)
0.8" (20.3mm)
2
© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject
to change without notice.
® Liebert and the Liebert logo are registered trademarks of
Liebert Corporation. All names referred to are trademarks or
registered trademarks of their respective owners.
SL-29105_REV02_10-07
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
Customer Wiring
Specifications
Wiring Specifications
Power
Requirements
AC Inputs 18 - 24 VAC; 50/60 Hz
DC Inputs 12 - 36VDC
Power Consumption 6VA maximum
Dimensions - W x D x H: in. (mm) 7 x 4 x 1.5 (178 x 102 x 38)
Weight
Net - oz. (kg) 7 (0.2)
Shipping - lb. (kg) 1.3 (0.6)
Ambient Operating Environment, °F (°C) 32 to 104 (0 to 40); 10% to 90% RH (non-condensing)
Ambient Storage Temperature, °F (°C) -4 to 140 (-20 to 60)
Protection SELV Isolated User Connections, Watchdog Timer Circuitry
Communication
Ports
Service Terminal (RS-232) DB9F, DTE
Unit Input
Communications
TB1, 2-Position Terminal Block
P1, 20-PIN Vertical Header with Ejection Latches (for some UPS models)
Modbus (RS-485) TB2, 2-Position Terminal Block
Ethernet Communications RJ45
Connection Supported Wire Types Maximum Wire Length
TB1 (RS-422)
18-22 AWG Stranded & Shielded; 18 AWG* recommended
Non Plenum - Belden 9461; Plenum - Belden 88761
1000 ft. (300m)
TB2 (RS-485)
18-22 AWG Stranded & Shielded; 18 AWG* recommended
Non Plenum - Belden 9461; Plenum - Belden 88761
3000 ft. (915m)
TB3 (Power Input)
18-22 AWG Stranded & Shielded; 18 AWG* recommended
Non Plenum - Belden 8770; Plenum - Belden 88770
20 ft. (6m)
DB9F Connector DTE Null Modem Cable 50 ft. (15m)
RJ45 Connector Standard Category 5 Cable 328 ft. (100m)
Input power
(input to TB3)
Pin 1(+)
Pin 2(-)
Pin 3 (NC)
Network port
for NMS and
Web access
DTE serial port
for configuration
(requires null-modem
connection)
IGMnet or Liebert SiteScan
®
Comms
from unit (input to TB1 or P1)
Refer to user manual for details
Modbus output
for BMS
(output from TB2)
TB1: Pin 1 (+), Pin 2 (-)
TB2: Pin 1 (+), Pin 2 (-)
/