The new cluster has its own high-density zone in
the data center, with 20 racks arranged in two rows
and positioned front-to-front to create a cold aisle
between the rows. Each rack contains 50 Dell
PowerEdge Energy Smart Servers configured with
dual processors, which draw 18 kW of power per rack.
“People often underestimate the power and cooling
demands of high-density equipment,” Musgrove says.
“Those 1,000 blade servers draw 360 kW of power and
put out 104 tons of heat in 2,000 square feet.”
In the HESS data center, 10 ceiling-mounted Liebert
XDO cooling modules, rated at16 kW each,
supplement the cold air being delivered through the
raised floor by 10 Liebert Deluxe precision air
conditioning units. The Liebert Deluxe units also
provide humidity control and air filtration for the space.
A 45-t
on Liebert XDC Refrigerant Chiller connects to
the cooling modules via the pumped refrigerant circuit
and to the roof-top heat rejection units via direct
expansion refrigerant circuits.
The Liebert power system at HESS easily expanded to
handle the additional equipment. The addition of a
750 kVA Liebert UPS to an existing 500 kVA Liebert
Se
r
i
e
s 610 UPS provides at least 20 minutes of clean,
reliable backup power in the event of a power loss.
T
e
n Liebert PPC Precision Power Centers provide
power isolation, distribution, and computer-grade
grounding. The facility will soon add a 1.25 MW
ba
ck
u
p ge
ne
r
ator to ensure continual operation
in the face of increasing hurricane activity and
often unreliable utility power.
Always-On Analysis
W
ith the increase in availability demands of the new
computing cluster came a corresponding increase in
the cost of downtime. To reduce the risk, HESS
installed Liebert SiteScan Web, an enterprise-wide
monitoring solution that displays the status of all
critical support systems from any internal computer,
allowing staff to quickly ascertain the status of the
cr
iti
cal po
w
e
r and cooling systems.
Among other abilities, Liebert SiteScan Web assembles
performance data from the Liebert XD and Liebert
Deluxe precision cooling systems. It also collects data
fr
om the Liebert PPC Precision Power Centers that
allow managers to monitor the electrical load in
real time.
Data analysis and trend reporting capabilities allow
Mu
s
gr
o
v
e an
d his t
e
am to identify and correct
p
r
oblems before they affect operations. In addition,
programmable alarm and event management functions
indicate when operating conditions fall outside of set
p
ar
ame
t
e
rs, allowing time to correct issues before
they trigger cooling and power system failure.
“My Liebert equipment gives me one less thing to
worry about. You can't put a price tag on peace of
mind, especially in an operation as complex and
as critical as ours.”