2.6 Verify configuration
Emerson recommends that you verify various configuration parameters prior to
installation into the process.
The following sections detail the various parameters for each configuration tool.
Depending on what configuration tool(s) are available, follow the steps listed relevant to
each tool.
2.6.1 Verify configuration with Field Communicator
Review configuration parameters listed in Table 2-3 prior to transmitter installation. Field
Communicator menu trees and fast keys provides a full list of configuration parameters
that can be reviewed or configured using a Field Communicator.
Table 2-3 shows Fast Key sequences for the latest DD. For Fast Key sequences for legacy
DDs, contact your local Emerson representative.
From the HOME screen, enter the Fast Key sequences listed.
Table 2-3: Device Dashboard Fast Key Sequence
Function Fast Key sequence
HART
®
7 HART 5
Alarm and saturation levels 2, 2, 2, 5 2, 2, 2, 5
Damping 2, 2, 1, 1, 5 2, 2, 1, 1, 5
Primary variable 2, 1, 1, 4, 1 2, 1, 1, 4, 1
Range values 2, 1, 1, 4 2, 1, 1, 4
Tag 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Transfer function 2, 2, 1, 1, 6 2, 2, 1, 1, 6
Units 2, 2, 1, 1, 4 2, 2, 1, 1, 4
2.6.2 Verify configuration with AMS Device Manager
Complete the following steps to verify the configuration parameters with the AMS Device
Manager.
Procedure
1. Right-click the device and select Configuration Properties from the menu.
2. Navigate the tabs to review the transmitter configuration data.
2.6.3
Verify configuration with LOI
Complete the following steps to verify configuration parameters with the LOI.
Procedure
1. Press any configuration button to activate the LOI.
Reference Manual Configuration
00809-0100-4007 July 2020
Reference Manual 15