Montigo L Series ST Indoor Operating instructions

Category
Fireplaces
Type
Operating instructions

This manual is also suitable for

XG0223
Installation & Maintenance Manual
• Theinstallationofthisreplacemustbedonebya
qualiedandcertiedgasapplianceinstaller.
• Checklocalcodesandreadallinstructionspriorto
installation.
®
C
US
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury,
death, or property damage.
—Donotstoreorusegasolineorotherammablevaporsand
liquidsinthevicinityofthisoranyotherappliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phoneinyourbuilding.
• Leavethebuildingimmediately.
• Immediatelycallyourgassupplierfromaneighbour's
phone. Follow the gas supplier’s instructions.
• Ifyoucannotreachyourgassupplier,callthere
department.
—Installationandservicemustbeperformedbyaqualied
installer,serviceagencyorthegastter.
L Series See-Through
INDOOR GAS FIREPLACE
L38ST 25,000 BTU/hr Natural Gas or Propane Gas
L42ST 32,000 BTU/hr Natural Gas or Propane Gas
L52ST 40,000 BTU/hr Natural Gas or Propane Gas
Read and understand this manual. Improper installation, adjustment,
alteration, service or maintenance can cause serious injury, property
damage or even death. For assistance or additional information
consult a qualied installer, service agency or the gas supplier.
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and
shall be installed for the protection of children and other
at-risk individuals.
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
Installation and service must be performed by a qualied installer,
service agency or the gas tter.
Installer: Leave this manual with the appliance.
Consumer: Retain this manual for suture reference.
NOTICE
CAUTION
DANGER
DANGER
Some materials used in the manufacturing process of this product can
expose you to Benzene which is known in the State of California to
cause cancer and birth defects or other reproductive harm. For more
information go to www.P65warnings.ca.gov
WARNING
XG02232
General
Congratulations on your purchase of a Montigo Fireplace.
With over 30 years of experience, Montigo is committed to providing
you with a gas fireplace that is not only a beautiful addition to your
space, but that is also designed and manufactured to the highest
safety, reliability and engineering standards.
We strongly encourage you to read and carefully follow the
instructions laid out in this Installation, Operation and Maintenance
Manual and retain it for your future reference. Pay special attention
to all cautions, warnings, and notices throughout this manual
intended to ensure your safety.
This manual covers installation, operation and maintenance. Lighting,
operation and care of this replace can be easily performed by the
homeowner. All installation and service work should be performed
by a qualied or licensed installer, plumber or gas tter as certied
by the state, province, region or governing body where the replace
is being installed.
This installation, operation and maintenance manual is applicable
to the models described in Table 1. Refer to your rating plate to
verify included options.
Warranty and Installation Information: (See Appendix B)
The Montigo warranty will be voided by, and Montigo disclaims any
responsibility for, the following actions:
Modication of the replace and/or components including Direct-
Vent assembly or glass doors.
Use of any component part not manufactured or approved by
Montigo in combination with this Montigo replace system.
Installation other than as instructed in this manual.
Consult your local Gas Inspection Branch on installation
requirements for factory-built gas replaces. Installation & repairs
should be done by a qualied contractor.
MODEL
Natural gas
Propane
Gas Rating
(BTU /HR)
Linear Burner
Standing Pilot IGN.
SIT Electronic IGN.
L38FSDN X 27,000 X X
L38FSDL X 27,000 X X
L38FSDNI X 27,000 X X
L38FSDLI X 27,000 X X
L42FSDN X 34,000 X X
L42FSDL X 34,000 X X
L42FSDNI X 34,000 X X
L42FSDLI X 34,000 X X
L52FSDN X 40,000 X X
L52FSDL X 40,000 X X
L52FSDNI X 40,000 X X
L52FSDLI X 40,000 X X
Introduction
Safety Alert Key
Indicates a hazardous situation which, if
not avoided, WILL result in death or serious
injury or property damage.
Indicates a hazardous situation which, if not
avoided, WILL result in minor or moderate
injury.
Indicates a hazardous situation which, if not
avoided, COULD result in death or serious
injury or property damage.
Indicates practices that are important, but
not related to personal injury.
DANGER
CAUTION
WARNING
NOTICE
Figure 1 L**ST Specications
XG0223 3
General
Contents
Safety Alert Key .................................................................................. 2
Introduction ....................................................................................................................... 2
Contents ............................................................................................................................. 3
Section A: Before You Begin ......................................................................................... 4
Installation Checklist ........................................................................................................ 4
Standard Installation Checklist ...................................................................................... 5
Rating Plate Sample ......................................................................................................... 6
Section 1: Product Dimensions ......................................................... 7
L38-ST, L42-ST Dimensions............................................................................................ 7
L52-ST Dimensions .......................................................................................................... 7
Section 2: Framing ............................................................................ 8
Back Framing the unit ..................................................................................................... 8
Top vent - Shelf over fireplace framing ....................................................................... 8
Top vent - Shelf over fireplace framing ....................................................................... 8
Side vent - Shelf over fireplace framing ...................................................................... 9
Top vent - Alcove over fireplace framing .................................................................... 9
Clearances .......................................................................................................................... 9
Installing The Heat Guard - L38ST .............................................................................. 10
Installing the Nailing Flange Extension ...................................................................... 10
Installing The Heat Guard - L42ST .............................................................................. 10
Section 3: Venting ............................................................................ 11
Section 3-1: Converting to Side Vent ........................................................................ 11
Section 3-2: Installing a Roof Mounted Direct Vent Termination
for5''/8''(PVTK1SS) .......................................................................... 12
Section 3-2-1: Venting Layout .....................................................................................12
Section3-3:InstallingaWallMountedTermination5''/8'' ......... 14
Section 3-3-1: Venting Layout: Wall Mounted Termination ........ 15
Top Venting Layout: Wall mounted termination. L38ST: ......................................15
Side Venting Layout: Wall mounted termination. L38ST: .....................................16
Top Venting Layout: Wall mounted termination. L42ST: ......................................17
Side Venting Layout: Wall mounted termination. L42ST: .....................................18
Top Venting Layout: Wall mounted termination. L52ST: ......................................19
Section 3-3-2: Venting Components .......................................................................... 20
Section 3-3-2.2: Simpson Duravent Venting Components ..................................21
Section 3-3-2.3: ICC Venting Components* .............................................................22
Section 3-3-2.4: Metalfab Venting Components* ..................................................22
Section3-3-3:HeatShields5''/8'' .................................................... 23
Section 4: Wiring .............................................................................. 24
Installing the On/Off Wall Switch ................................................................................24
CPI [Continuous Pilot Ignition] / IPI [Intermittent Pilot Ignition]
JumperCableInstallation ............................................................... 25
“Why use CPI mode”? ..................................................................................................... 25
The difference between IPI and CPI: .......................................................................... 25
Installing the CPI Jumper Cable ................................................................................... 25
Section 5: Installing the gas line.....................................................26
Fuel Type ...........................................................................................................................26
Gas Pressure ...................................................................................................................26
Section 5-3: GAS CONNECTION ..................................................................................26
Section 6: Finishing .......................................................................... 27
Mantel Clearances .......................................................................................................... 27
Fireplace Facing .............................................................................................................. 27
Finishing the Fireplace................................................................................................... 28
Flush Finishing the Fireplace ....................................................................................... 28
Section7:ScreenInstallationandRemoval ................................. 29
Removing the Screen..................................................................................................... 29
To Install Screens: ........................................................................................................... 29
Replacement Screens: ................................................................................................... 29
Section8:Installing&RemovingtheDoor ................................... 30
Removing the door: ....................................................................................................... 30
Reinstalling the door ...................................................................................................... 30
Section 9: Installing the Accessories .............................................. 31
Installing the Firestones or optional Fireglass ........................................................ 31
Installing Cultured Rocks .............................................................................................. 31
Section 10: Start up Sequence ........................................................ 32
SIT Proflame 2 Electronic Ignition ............................................................................... 33
Remote Operation (Optional) ......................................................... 34
Initializing the System for the first time .................................................................... 35
Operating the System for the first time .................................................................... 35
Temperature Indication Display.................................................................................. 35
Turn On the Fireplace ................................................................................................... 35
Turn Off the Fireplace ................................................................................................... 35
Remote-Flame Control .................................................................................................. 36
Room Thermostat (Remote Control Operation) ..................................................... 36
Smart Thermostat (Remote Control Operation) ..................................................... 36
Disabling Thermostat .................................................................................................... 37
Fan Speed Control.......................................................................................................... 37
Section 10: Cleaning and Maintenance ........................................ 38
General ............................................................................................................................. 38
Cleaning ............................................................................................................................ 38
Pilot Burner Adjustment. (SIT Nova 820). ................................................................. 38
Burner Adjustment: (SIT Proflame 2). ........................................................................ 38
Pilot Burner Adjustment. .............................................................................................. 38
Troubleshooting ............................................................................... 39
Replacement Parts .......................................................................... 39
Appendix A: Venting Terminations ................................................ 40
Appendix B: Warranty ..................................................................... 41
Appendix B: Warranty Continued .................................................. 42
Appendix C: Amendment ................................................................ 43
(Gas Fireplace / Equipment sold in the State of Massachusetts) 43
XG02234
General
IMPORTANT MESSAGE: SAVE THESE INSTRUCTIONS
The L Series replaces must be installed in accordance with these
instructions. Carefully read all the instructions in this manual rst.
Consult the Local Gas Branch to determine the need for a permit prior
to starting the installation. It is the responsibility of the installer to
ensure this replace is installed in compliance with the manufacturers
instructions and all applicable codes.
Installation Checklist
Determine the desired install location of your replace.
See Section 1, Dimensions on Page 7, and refer to the Framing
Section 2 for details.
Select the location of your termination and resulting vent run.
Your selected termination location must be the highest point in the
Direct Vent installation.
Should it be impossible to meet the venting requirements laid out
in Section 3: Venting, please contact your Montigo dealer regarding
the use of a Montigo Power Vent.
Lay out the Vent run; calculating the required elbows and straight
runs of 5"/8" ex and/or rigid pipe
Layout Electrical Requirements refer to Section 4: Wiring, for Details.
Refer to Section 5: Installing the Gas Line, for details on the gas
connection and access.
Refer to local codes and guidelines for installation requirements.
Installation and repairs should be done by a qualied contractor
and must conform to:
Installations in Canada must conform to the local codes or in the
absence of local codes to the current version of Natural Gas and
Propane Installation Code, CSA B149. Electrical installations must
conform to the local codes or, in the absence of local codes, to the
current version of Canadian Electrical Code, CSA C22.1.1
Installations in the USA must conform to the local codes or in the
absence of local codes to the current version of National Fuel Gas
Code, ANSI Z223.1/NFPA 54. Electrical installations must conform
to the local codes or, in the absence of local codes, to the current
version of the National Electrical Code, ANSI/NFPA 70. See Appendix
C for installation within the State of Massachusetts
Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect the appliance
and to replace any part of the control system and any gas control that
has been under water
Due to high temperatures, the appliance should be located out of
trac and away from furniture and draperies
Children and adults should be alerted to the hazards of high surface
temperature and should stay away to avoid burns or clothing ignition
A barrier designed to reduce the risk of burns from the hot viewing
glass is provided with this appliance and shall be installed for the
protection of children and other at-risk individuals
Clothing or other ammable material should not be placed on or near
the appliance
Installation and repair should be done by a qualied service person.
The appliance should be inspected before use and at least annually
by a professional service person. More frequent cleaning might be
required due to excessive lint from carpeting, bedding material, etc. It
is imperative that control compartments, burners, and circulating air
passageways of the appliance be kept clean
NOTICE
NOTICE
NOTICE
NOTICE
NOTICE
NOTICE
Section A: Before You Begin
XG0223 5
General
Standard Installation Checklist
This standard installation checklist is to be used by the installer in conjunction with, not instead of, the instructions contained within this
installation manual.
Customer Date Installed:
Install Address: Location of Fireplace:
Installer:
Model (circle one): L38FSDN, L38FSDL, L38FSDNI, L38FSDLI, L42FSDN,
L42FSDL, L42FSDNI, L42FSDLI L52FSDN, L52FSDL, L52FSDNI, L52FSDLI
Dealer Phone:
Serial #:
YES NO IF NO, WHY NOT?
Appliance Install: Section 2
Framing complies with install manual.
Standos have been installed.
Proper clearances have been maintained.
Venting: Section 3
Venting conguration complies with vent diagrams.
Venting installed, fastened, and secured in place maintaining proper clearance.
Firestops installed.
Exterior wall/roof ashing installed and sealed in compliance with local building code.
Terminations installed and sealed in compliance with local building code.
Direct vent termination is highest point in vent assembly.
Wiring/Electrical: Section 4
Unswitched power provided to the appliance PPO box.
Low voltage wire connected to dry contact wall switch (non-powered)
Gas: Section 5
Proper appliance for fuel type.
Was a conversion performed?
Leak check performed & inlet pressure veried.
Finishing: Section 6
Only non-combustible materials installed in non-combustible areas.
Clearances meet installation manual requirements
Mantels and/or projections comply with install manual
Appliance Setup: Section 7 through 9
Media, door, and screen installed according to install manual
Manual given to home owner.
Started appliance and veried no gas leaks exist.
Comments:
XG02236
General
Rating Plate Sample
Figure 1.1 Rating Plate for L38ST



 













LBL1205-V6.1 Stand. Pilot- Screen DEC06.2014


















































 










Teklynx LabelView Demo
XG0223 7
General
998
39
5
16
"
492
19
3
8
"
134
5
1
4
"
124
4
7
8
"
853
33
9
16
"
895
35
1
4
"
32
1
1
4
"
32
1
1
4
"
676
26
5
8
"
173
6
13
16
"
606
23
13
16
"
639
25
1
8
"
959
37
3
4
"
127
5"
203
8"
472
18
5
8
"
77
3"
185
7
5
16
"
POWER
SUPPLY
GAS
SUPPLY
637
25
1
16
"
L38-ST
DIMENSIONS TOLERANCES ARE IN:
METRIC - MM
1.6 MM
IMPERIAL - FRACTIONAL
1/16"
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
December-06-17 11:38:00 AM
DATE:
1480
58
1
4
"
554
21
13
16
"
138
5
7
16
"
192
7
9
16
"
64
2
1
2
"
64
2
1
2
"
1194
47"
152
5
15
16
"
127
5"
203
8"
606
23
7
8
"
640
25
3
16
"
1321
52"
1362
53
5
8
"
320
12
9
16
"
740
29
1
8
"
843
33
3
16
"
884
34
13
16
"
968
38
1
8
"
277
10
15
16
"
165
6
1
2
"
166
6
1
2
"
L52-ST
DIMENSIONS TOLERANCES ARE IN:
METRIC - MM
1.6 MM
IMPERIAL - FRACTIONAL
1/16"
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
November-28-17 1:15:42 PM
DATE:
Figure 2.0 Dimentional Drawing for L38ST, L42ST
Figure 2.1 Dimentional Drawing for L52ST
Section 1: Product Dimensions
B
C
D
A
E
F
G
H
I
J K
L
L
M
N
O
P
Q
R
UNIT DIMENSIONS
L38-ST L42-ST
A
5" 5"
B
8" 8"
C
6
13/16
" 6¼"
D
37¾" 42"
E
23
13/16
" 23
15/16
"
F
25⅛" 25¼"
G
39
5/16
" 45
11/16
"
H
4⅞" N/A
I
19" 20
5/16
"
J
25
1/16
" 25
3/16
"
K
5¼" 5
7/16
"
L
1¼" 1¼"
M
35¼" 39½"
N
26⅝" 27
7/16
"
O
33
9/16
" 33⅞"
P
18⅝" 16
11/16
"
Q
7
5/16
" 7⅜"
R
3" 3"
L52-ST
Dimensions
L38-ST, L42-ST
Dimensions
XG02238
Installation
4
5
40”
45”
23 3/4”
4
0”
NOTE: When constructing the
framed opening, please ensure
there is access to install the gas
line when the unit is installed.
1). Slide the replace into the cavity.
2). Tack four studs in place, shown in Figure 2 and 3 as dashed lines.
3). Secure the replace in position by nailing into these cleats.
Section 2: Framing
Figure 3.b Framing dimensions (Straight wall & Corner Installation).
Figure 3.b.b Securing the replace to the framing cleats, both walls typical.
B
Combustible
shelf
NG or
Propane
REAR VENT
NG AND
PROPANE OK
C*
A
A
Back Framing the unit
Topvent-Shelfoverfireplaceframing
Topvent-Shelfoverfireplaceframing
10"
L38ST Only
Figure 3.b Combustible Framing for shelves over the replace, Top vent.
SUPPLIED SHIELD
COMBUSTIBLE SHELF
A
B
C
PEL
SHORT 90°
ELBOW
Figure 3.c Combustible Framing for shelves over the replace, Side vent.
NON-COMBUSTIBLE HEADER
COMBUSTIBLE HEADER
L38ST
A 41''
B 40''
C 23 ¾''
L52ST
A 59''
B 39''
C 23 ¾''
L42ST
A 45''
B 40''
C 23 ¾''
L38ST
A
41” Min N.G.
54” Min Propane
B
2'' Min.
C
17½” Min N.G.
17½” Min Propane
L42ST
A
41” Min N.G.
54” Min Propane
B
2'' Min.
C
17½” Min N.G.
17½” Min Propane
L52ST
A
84” Min.
B
2'' Min.
C
30” Min.
XG0223 9
Installation
Figure 3.c Combustible Framing for shelves over the replace, Side vent.
Sidevent-straight
outthewallventing
not permitted for
L42 and L52 units
A
A
B
NG AND
PROPANE OK
Topvent-Alcoveoverfireplace
framing
Sidevent-Shelfoverfireplaceframing
C
SUPPLIED SHEILD
COMBUSTIBLE SHELF
Figure 3.b Non Combustible Framing with alcove above replace, Right side. Combustible
Framing above replace, Left side, see gure 2. (Top Vent).
1" Min.
Non-
combustible
nailingange
(supplied)
Both sides
typical
Non-combustible
materials.Alcove
overreplace
CeilingLevel
Door
Opening
Floor
Non-Combustible
header
Combustible
header
7"
10"
B C
A
Clearances
MODEL
Top - Top
vent†
Top - Side
vent†
Sides
Floor
Mantel
L38DF-ST 17 ½" 10" 1" 0"
See Section 6 Finishing
around the replace
L42DF-ST
12" NG
17" Propane
12" 2" 0"
See Section 6 Finishing
around the replace
L52DF-ST 30" 24" 1" 0"
See Section 6 Finishing
around the replace
L38-ST NOTES:
Clearance from top of replace to a ceiling within the replace enclosure.
When installing a shelf over the top of the replace, the following guidelines
must be adhered to: For Side Vent applications, the minimum clearance is
10" from the top of the replace to the underside of any combustible shelf.
For Top Vent applications, the minimum clearance is 17½" from the top of
the replace to the underside of any combustible shelf.
L42-ST NOTES:
Clearance from top of replace to a ceiling within the replace enclosure.
When installing a shelf over the top of the replace, the following guidelines
must be adhered to: For Side Vent applications, the minimum clearance is
12" from the top of the replace to the underside of any combustible shelf.
For Top Vent applications, the minimum clearance is 17" for LP and 12" for
NG from the top of the replace to the underside of any combustible shelf.
L52-ST NOTES:
Clearance from top of replace to a ceiling within the replace enclosure.
When installing a shelf over the top of the replaces, the minimum clearance
is 30" to the underside of any combustible shelf materials.
Figure 4. Combustible Wall Clearances
L38ST, L42ST, L52ST:
1” clearance is maintained on sides and bottom of vent runs and 2”
above horizontal vent runs to any combustible material.
L38ST
A 84'' Min.
B 39''
C 33 ¼''
L52ST
A 84'' Min.
B 39''
C 33 ¼''
L42ST
A 95''
B 40''
C 30 ½''
L38ST
A 1'' Min.
B 12'' Max
C 12'' Min.
L42ST
A 1'' Min.
B 12'' Max
C 12'' Min.
L52ST
Side vent not
available on
L52ST units
XG022310
Installation
40”
Installing The Heat Guard - L42STInstalling The Heat Guard - L38ST
Figure 4. Combustible Framing Side Heat Shield L42FS01 x 4 pcs.
Figure 4. Installing the supplied metal headers, both sides typical.
Figure 4. Non combustible header H42ST060 x 2 pcs.
Included with the L42DF-ST Gas replace, is a framing heat shield Kit.
This kit is fabricated from galvanized steel and arrives with six (6) pieces,
as shown below. The shields protect all adjacent combustible materials,
mantels and mouldings from excessive heat radiated by the replace.
STEP 1. Fasten 4 side shields in place with nails or screws, ush with
the framing as shown. These are installed with the Wide anges facing
the center of the replace opening, and the shallow ange toward
inside of room.
Included with the L38DF-ST* gas replace are two metal headers
made of galvanized steel. The metal headers must be installed after
the replace has been back framed in place. Install metal headers at
34 1/2" from the base of the unit, as shown in gure 6.
STEP 2. Nail or screw the top shield in place ush with framing
NOTE: The nailing ange extension can be substituted with a piece of
NON-Combustible material of the same size and thermal characteristics,
ie: cement board or equivalent. This is recommended in applications
where the facing materials will not adhere to the metal nailing ange.
Installing the Nailing Flange Extension
Figure 4.c Securing the Nailing Flange Extension.
Before installing the supplied nailing ange extension, fold tabs at
bottom of nailing ange to a 90° angle. NOTE: Do not install nailing
ange when installing a Montigo Surround.
NOT NEEDED FOR L52ST
Framing
Flush with
framing
Fasteners
Fireplace
INSET
SECTION
Both sides
shields typical
Bothwallsmaynotbe
exactly as shown
Bothwallsmaynotbe
exactly as shown
40”
40"
40"
35"
45"
35½"
45"
23¾"
23¾"
40”
34½"
SuppliedNon-CombustibleHeader
6" Nailing Flange
XG0223 11
Installation
Figure 5. Flue cover and collar removal, Top Vented replace.
Figure 5.b Flue cover and collar installation, Side Vented replace.
Note: Images are shown without screens for clarity purposes. However,
your replace should not be operated without proper installation of
screens.
Flue Collar
8" Outer Flue Collar
8" Outer
Flue Collar
5" Inner Flue
Coverplate
5" Inner Flue
Coverplate
5" Inner
Flue Collar
Outer Flue
Coverplate
8" Outer Flue
Coverplate
Under no circumstances can Montigo ex venting be cut to
accommodate an installation. Use an alternative length to complete
your vent run.
NOTICE
Section 3: Venting
Montigo supplies a variety of direct venting and termination options.
The direct vent termination location MUST be selected such that it is the
highest point in the venting assembly. It should also be selected such
that it provides the shortest vent run possible. Should it be impossible
to ensure that the termination is the highest point or to meet the
venting guidelines laid out below please contact your Montigo dealer
to discuss power venting options.
Notes For Planning Venting:
Venting can originate from the unit through the top or through the side.
Venting can terminate through the roof or through an exterior wall.
Refer to Appendix A - Termination Locations to ensure the planned
termination location is acceptable.
Once the termination location has been established, refer to the
appropriate section below for installation details
All replaces shipped from the factory are Top vent.
Silicone application is NOT required when joining Montigo vent pipes
and components.
Section3-1:ConvertingtoSideVent
Use the following instructions to convert a unit for Side Vent use:
1. Remove the Side ue cover and gasket (5" and 8") on the ue
outlet, as shown in Figure 9.
2. Next, Remove the Top ue collar's (5" and 8") on the ue outlet,
as shown in Figure 9.
3. Install the (removed) Side ue cover and gasket material, to the
Top vent outlet. Fasten the cover with included hardware, as
illustrated Figure 9a.
4. Install the (5" and 8") collars to the Side vent outlet using the
included hardware, as illustrated Figure 9a.
XG022312
Installation
Roof mounted Terminations
The following details are some possible congurations for Roof mounted
terminations. See below.
This section applies to installations where the direct vent termination
will be roof mounted.
Section 3-2-1: Venting Layout
Selection of components and details of venting lay out should adhere
to the following guidelines:
The maximum termination point is 32’ above the replace (NOTE:
if the maximum termination height is used, the ame pattern may
be aected).
The Vertical termination must be a minimum 2’ higher than where
the termination exits the roong materials, (asphalt shingles, cedar
shakes, etc). This distance should be measured from the high side of
the roof slope where the ue ashing intersects the roong materials.
(see Figures 6 to 6c).
Termination location must be a minimum 6’ from a mechanical air inlet.
1” clearance is maintained on sides and bottom of vent runs and 2”
above horizontal vent runs to any combustible material.
For a more detailed diagram of allowed termination locations, see
Appendix A.
A maximum of two osets (each oset is made up of 2-90° bends)
may be made for vertical vent runs.
Firestops must be installed as required by National & local codes
Ensure all horizontal runs are supported with a minimum of 3
supports per 10’ of venting.
Install all roof ashing and storm collars as shown.
Figure 6. Top vent, Roof mounted termination with no oset in vent run.
Figure 6.b Top vent, Roof mounted with 1 oset (1 oset= two 90° bends).
Figure 6.c Top vent, Roof mounted with 2 osets (1 oset= two 90° bends).
Section 3-2: Installing a Roof Mounted Direct Vent
Terminationfor5''/8''(PVTK1SS)
PVTK1 Termination
PVTK1 Termination
PVTK1 Termination
Storm collar
Storm collar
Storm collar
2' min
2' min
2' min
Support ring
Support ring
Support straps OR
Support ring and plates
Support ring and plates
Support plate
Support plate
Firestop
PEXT
PEXT-10
Adaptor
Flue
collar
Firestop
2' Oset
2' Oset
2' Oset
Firestop
Firestop
Obstacle
Obstacle
Firestop
32' max
32' max
32' max
Roof ashing
Roof ashing
Roof ashing
XG0223 13
Installation
Figure 6.d Side vent, Roof mounted venting (1 = 90° bend).
Storm collar
Support plate
Roof ashing
PVTK1 Termination
Support ring
PEXT Sections
Firestop
Firestop
90° Elbow
12''
MAX
2' MIN
32' max
XG022314
Installation
Figure 7. Installing a PTO4-F termination.
Figure 7.b Installing a PTO termination with the MSR frame.
Figure 7.c Installing a PTO termination with the BSR frame.
Figure 7.d Installing a PTO termination with MOSR frame.
Figure 7.e Installing the VSS Vinyl Shield.
Figure 7.f Installing a PTO termination heat guard.
1
12”
2”
1
2”
12”
This section applies to installations where the direct vent termination
will be wall mounted. NOTE: If subject to a highly corrosive environment
i.e. Seaside, Montigo recommends using Stainless Steel Termination.
Section3-3:InstallingaWallMountedTermination5''/8''
Installationofterminationwithbuiltinframe
A Termination with a Built-In Frame is installed during framing of a
structure.
1. Frame the termination opening to 11" x 11".
2. Install exterior sheathing to the structure framing.
3. Fasten the termination to the sheathing using a minimum of 4 screws.
MSR Frame
PTO-4 (5"/8")
Termination
PTO-4F (5"/8")
Termination
Installationofaterminationshieldforvinylsiding
The VSS Termination shield is installed when the exterior of a structure
is clad with Vinyl siding. It is placed directly above, and on-center with
the termination.
Installation of termination frame at time of framing
Terminations with a MSR frame allow the installation of the frame prior
to installation of the termination.
1. Frame the termination opening to 12" x 12".
2. Secure the MSR Frame to the exterior sheathing of the structure.
3. Fasten the termination to the MSR Frame using a minimum of 4 screws.
1. Frame the MOSR opening to 12" x 12".
2. Fasten the MOSR frame to the interior side of the studs, concrete,
or nished wall construction using a minimum of 4 screws.
3. Insert the termination into the MOSR frame as shown here, (from
the inside) and attach to the MOSR by installing a min. quantity of 4
bolts into the threaded nuts on the MOSR Frame.
Installation of termination frame at time of framing in masonry
Terminations with a BSR frame allow the installation of the frame in
masonry prior to the installation of the termination
1. Frame the BSR opening to 12" x 12".
2. Secure the BSR Frame to the exterior sheathing of the structure.
3. Fasten the termination to the BSR Frame using a minimum of 4 screws.
BSR Frame
MTKOG (5"/8")
Installing heat guards
Installing heat guards over terminations is recommended in installations
where the termination is located within 7' feet above grade, or above
a pedestrian walkway, and may be required by code in public areas.
1. Ensure that the two long mounting brackets are facing the bottom
of the termination (See inset). This will provide more heat protection
at the top of the termination, where temperatures are highest.
2. Attach to the faceplate of the termination using four sheet metal
screws.
1
1”
11”
Framing
Exterior
Sheathing
Fastening Hard-
ware, minimum
4-screws
Framing
Exterior
Sheathing
Fastening Hardware,
minimum 4-screws
PTO-4 (5"/8")
Termination
Framing
Exterior
Sheathing
Fastening Hardware,
minimum 4-screws
Exterior Vinyl
siding
PTO-4 (5"/8")
Termination
VSS Vinyl shield
Installation of termination from inside structure
A Termination with a MOSR Frame is installed from the inside of the
structure. These are commonly used in high-rise construction.
MOSR Frame
PTO-4 (5"/8")
Termination
12”
12”
Fastening Hardware,
minimum 4-screws
Framing,
concrete
or other
materials
Exterior
Sheathing, concrete
or other materials
XG0223 15
Installation
Figure 8.b L38DF* Top Vent Venting Graph for wall mounted terminations.
Figure 8.c Top Vented, wall mounted Multi-elbow installation. See Venting Graph for Top vent,
wall mounted terminations, Figure 8 or 8.b
Selection of components and details of venting layout should adhere
to the following guidelines:
Vent terminations must not be recessed in walls or siding.
For Heat Shield requirements see Section 3-3 on page 14.
Once the proposed venting layout has been determined refer to
Figure 8, 8b, 8c to ensure the layout is acceptable.
Notes Wall Mounted Terminations: TOP VENT
All measurements for vertical or horizontal runs are measured from
center of the vent pipe.
Venting runs must fall within the limits set by the venting graph,
see Figure 8 or 8b.
ExampleA:(AcceptableInstallation)
If the vertical dimension from the hearth is 96" and the horizontal
run to the wall ange of the vent termination is 60", this would be an
acceptable installation.
ExampleB:(AcceptableInstallation)
If the vertical dimension from the hearth is 66" and the horizontal
run to the wall ange of the vent termination is 72", this would be an
acceptable installation.
ExampleC:(UnacceptableInstallation)
If the vertical dimension from the oor of the replace is 60" and the
horizontal run to the wall ange of the vent termination is 144", this
would not be an acceptable installation.
Top Venting Layout: Wall mounted
termination. L38ST:
Measure the vertical height from the replace hearth to the centre of
the termination and the horizontal run from the replace ue collar
to the wall ange of the termination. Plot on the Venting Graph Figure
8 or 8b with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Figure 10.d Top Vented, wall mounted Multi-elbow installation. See Venting Graph for Top vent,
wall mounted terminations
Figure 10.e Top Vented, wall mounted Retracted Multi-elbow installation. See Venting Graph for
Top vent, wall mounted terminations
Exterior
Wall
Hearth
Termination
Heat Shield
42''
Min.
36''
Max.
Exterior
Wall
96''
Min.
Rigid
Section
Flex
Section
150"
Max.
30" Min.
Termination
Heat Shield
Exterior
Wall
96''
Min.
Rigid
Section
Flex
Section
120" Max.
30" Max.
Termination
Heat Shield
0
HEARTH
12
12
0
60
36
84
120
24
72
108
48
96
132
Vertical Height (In.)
Horizontal Run (In.)
36 60 84 108 132 15624 48 72 96 120 144 168 180
Acceptableventrun
within non-shaded area.
B
C
Unacceptableventrun
within shaded area.
A
Section 3-3-1: Venting Layout: Wall Mounted Termination
42''
36''
XG022316
Installation
Figure 8.b Side Vent Venting Graph for wall mounted terminations.
ExampleA:(AcceptableInstallation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall ange of the vent termination is 138", this would be an
acceptable installation.
ExampleB:(UnacceptableInstallation)
If the vertical dimension from the hearth is 48" and the horizontal run
to the wall ange of the vent termination is 96", this would be would
not be an acceptable installation.
ExampleC:(UnacceptableInstallation)
If the vertical dimension from the oor of the replace is 72" and the
horizontal run to the wall ange of the vent termination is 120", this
would not be an acceptable installation.
Notes Wall Mounted Terminations: Side Vent
All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
Vent runs must fall within the limits set by the venting graphs, see
Figure 15.
Fireplace must be converted to Rear Vent conguration prior to
running vent, see Figure 9 and 9a.
Side Venting Layout: Wall mounted
termination. L38ST:
Measure the vertical height from the replace hearth to the centre of
the termination and the horizontal run from the replace ue collar
to the wall ange of the termination. Plot on the Venting Graph Figure
15 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Figure 9.c Side Vented, wall mounted Multi-elbow termination installation. Installation for
L38DF*-ST must have a minimum vertical rise of 42".The vent run must comply with the Venting
Graph for Rear vent, wall mounted terminations, Figure 13.
Figure 9.c Straight run, Side Vented, wall mounted termination for L38DF-ST*, Figure 13.
Hearth
Flex or Rigid
42''
Min.
15¼''
Min.
26¾''
30''
Max.
12''
Max.
Hearth
Termination
Heat Shield
PXT Extension
12''
Max.
12'' Max. horizontal
run with no vertical lift
26¾''
Max
0
HEARTH
12
12
0
60
36
84
120
24
72
108
48
96
132
Vertical Height (In.)
Horizontal Run (In.)
36 60 84 108 132 15624 48 72 96 120 144 168 180
Acceptableventrun
within non-shaded area.
A
Unacceptableventrun
within shaded area.
B
C
42''
42''
26¾''
12''
XG0223 17
Installation
Exterior
Wall
126''
Min.
Rigid
Section
Flex
Section
150"
Max.
30" Min.
Termination
Heat Shield
Exterior
Wall
96''
Min.
Rigid
Section
Flex
Section
120" Max.
30" Max.
Termination
Heat Shield
Figure 8.b L42DF* Top Vent Venting Graph for wall mounted terminations.
Figure 8.c Top Vented, wall mounted installation with 1 elbow (1 one 90° bend). The vent run
must comply with Venting Graph for Top vent, wall mounted terminations, Figure 14.
Selection of components and details of venting layout should adhere
to the following guidelines:
Vent terminations must not be recessed in walls or siding.
For Heat Shield requirements see Section 3-3 on page 14.
Once the proposed venting layout has been determined refer to
Figure 8, 8b, 8c to ensure the layout is acceptable.
Notes Wall Mounted Terminations: TOP VENT
All measurements for vertical or horizontal runs are measured from
center of the vent pipe.
Venting runs must fall within the limits set by the venting graph,
see Figure 8 or 8b.
ExampleA:(AcceptableInstallation)
If the vertical dimension from the hearth is 114" and the horizontal
run to the wall ange of the vent termination is 114", this would be an
acceptable installation.
ExampleB:(AcceptableInstallation)
If the vertical dimension from the hearth is 78" and the horizontal
run to the wall ange of the vent termination is 54", this would be an
acceptable installation.
ExampleC:(UnacceptableInstallation)
If the vertical dimension from the oor of the replace is 84" and the
horizontal run to the wall ange of the vent termination is 138", this
would not be an acceptable installation.
Top Venting Layout: Wall mounted
termination. L42ST:
Measure the vertical height from the replace hearth to the centre of
the termination and the horizontal run from the replace ue collar
to the wall ange of the termination. Plot on the Venting Graph Figure
8 or 8b with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Figure 10.d Top Vented, wall mounted Multi-elbow installation. See Venting Graph for Top vent,
wall mounted terminations, Figure 14.
Figure 10.e Top Vented, wall mounted Retracted Multi-elbow installation. See Venting Graph for
Top vent, wall mounted terminations, Figure 12.
0
HEARTH
12
12
0
60
36
84
120
24
72
108
48
96
132
Vertical Height (In.)
Horizontal Run (In.)
36 60 84 108 132 15624 48 72 96 120 144 168 180
Acceptableventrun
within non-shaded area.
Unacceptableventrun
within shaded area.
A
B
C
54''
30''
Exterior
Wall
Hearth
Termination
Heat Shield
54''
Min.
30''
Max.
XG022318
Installation
Hearth
Flex or Rigid
54''
Min.
26¼''
Min.
27¾''
30''
Max.
12''
Max.
Figure 8.b Side Vent Venting Graph for wall mounted terminations.
ExampleA:(AcceptableInstallation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall ange of the vent termination is 138", this would be an
acceptable installation.
ExampleB:(UnacceptableInstallation)
If the vertical dimension from the hearth is 48" and the horizontal run
to the wall ange of the vent termination is 72", this would be would
not be an acceptable installation.
ExampleC:(UnacceptableInstallation)
If the vertical dimension from the oor of the replace is 60" and the
horizontal run to the wall ange of the vent termination is 144", this
would not be an acceptable installation.
Notes Wall Mounted Terminations: Rear Vent
All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
Vent runs must fall within the limits set by the venting graphs, see
Figure 15.
Fireplace must be converted to Rear Vent conguration prior to
running vent, see Figure 9 and 9a.
Side Venting Layout: Wall mounted
termination. L42ST:
Measure the vertical height from the replace hearth to the centre of
the termination and the horizontal run from the replace ue collar
to the wall ange of the termination. Plot on the Venting Graph Figure
15 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Figure 9.c Side Vented, wall mounted Multi-elbow termination installation. Installation for
L42DF*-ST must have a minimum vertical rise of 54".The vent run must comply with the Venting
Graph for Side vent, wall mounted terminations, Figure 13.
0
HEARTH
12
12
0
60
36
84
120
24
72
108
48
96
132
Vertical Height (In.)
Horizontal Run (In.)
36 60 84 108 132 15624 48 72 96 120 144 168 180
Acceptableventrun
within non-shaded area.
A
Unacceptableventrun
within shaded area.
B
C
54''
42''
XG0223 19
Installation
Exterior
Wall
108''
Min.
Rigid
Section
Flex
Section
150"
Max.
30" Min.
Termination
Heat Shield
Exterior
Wall
96''
Min.
Rigid
Section
Flex
Section
120" Max.
30" Max.
Termination
Heat Shield
Figure 8.b L52DF-ST* Top Vent Venting Graph for wall mounted terminations.
Figure 8.c Top Vented, wall mounted installation with 1 elbow. The vent run must comply with
Venting Graph for Top vent, wall mounted terminations, Figure 9.
Selection of components and details of venting layout should adhere
to the following guidelines:
Vent terminations must not be recessed in walls or siding.
For Heat Shield requirements see Section 3-3 on page 14.
Once the proposed venting layout has been determined refer to
Figure 8, 8b, 8c to ensure the layout is acceptable.
Notes Wall Mounted Terminations: TOP VENT
All measurements for vertical or horizontal runs are measured from
center of the vent pipe.
Venting runs must fall within the limits set by the venting graph,
see Figure 8 or 8b.
ExampleA:(AcceptableInstallation)
If the vertical dimension from the hearth is 90" and the horizontal
run to the wall ange of the vent termination is 36", this would be an
acceptable installation.
ExampleB:(AcceptableInstallation)
If the vertical dimension from the hearth is 108" and the horizontal
run to the wall ange of the vent termination is 120", this would be an
acceptable installation.
ExampleC:(UnacceptableInstallation)
If the vertical dimension from the oor of the replace is 48" and the
horizontal run to the wall ange of the vent termination is 108", this
would not be an acceptable installation.
Top Venting Layout: Wall mounted
termination. L52ST:
Measure the vertical height from the replace hearth to the centre of
the termination and the horizontal run from the replace ue collar
to the wall ange of the termination. Plot on the Venting Graph Figure
8 or 8b with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Figure 10.d Top Vented, wall mounted Multi-elbow installation. See Venting Graph for Top vent,
wall mounted terminations, Figure 9.
Figure 10.e Top Vented, wall mounted Retracted Multi-elbow installation. See Venting Graph for
Top vent, wall mounted terminations
0
HEARTH
12
12
0
60
36
84
120
24
72
108
48
96
132
Vertical Height (In.)
Horizontal Run (In.)
36 60 84 108 132 15624 48 72 96 120 144 168 180
Acceptableventrun
within non-shaded area.
Unacceptableventrun
within shaded area.
C
84''
60''
96''
120''
A
B
Exterior
Wall
Hearth
Termination
Heat Shield
84''
Min.
60''
Max.
XG022320
Installation
Connectionandinstallationofthevent
components should adhere to the following
guidelines:
Section 3-3-2: Venting Components
The following components and associated Montigo part numbers for
installation of a roof or wall mounted termination. Use of non-Montigo
approved parts will VOID the warranty and may impede operation of
the replace.
Use any combination of rigid and ex pipe as required and in any
orientation (Male connectors can face in any direction).
Flex sections may be stretched up to 150% of their total length (e.g.
a 24” section maybe stretched to 36”).
Connect all vent sections using a minimum of three sheet metal
screws on the outer pipe ue.
Ensure the pipe ends male to female slide in a minimum of 1 ½” of
overlap.
Ensure all horizontal runs are supported with a minimum of 3
supports per 10’ of venting.
When hanging/supporting venting, ensure that 1” clearance is
maintained on sides and bottom of vent runs and 2” above horizontal
vent runs to any combustible material.
Rigid pipe may be cut less than half way from the FEMALE END ONLY.
Ensure when cutting sections of rigid pipe to maintain integrity of
internal supports.
FLEX PIPE CANNOT BE CUT
Place the springs, supplied with the pipe kit (ex only), between the
outer and inner pipes to keep the pipes separate and avoid any
possible hot spots.
Montigo recommends the use of a ex section for the rst section of
venting connected directly to the replace, oering greater exibility
of installation and absorption of movement.
Firestops must be installed as required by National & local codes.
Montigo recommends that all exterior corners and joints be sealed
with exterior caulking. However, we encourage you to consult your
Building Envelope Engineer or Waterproong Consultant for further
recommendations.
IMPORTANT:
Please Refer to your Building Envelope Engineer
or Waterproong Consultant for a review of ALL
penetrations through exterior walls or the roof.
A - Termination PTO4F (5/8 Vent)
PTO4 (5/8 Vent)
PVTK1SS (5/8 Vent)
B - Frame Kits MSR (Stucco Frame)
MOSR (Stucco Frame)
BSR-4 (4" Brick Frame)
BSR-6 (6" Brick Frame)
C - Flex Sections
(5/8 Vent)
PFL - 1 (12" f/f Section)
PFL - 18 (18" f/f Section)
PFL - 2 (24" f/f Section)
PFL - 3 (36" f/f Section)
PFL - 4 (48" f/f Section)
PFL - 6 (72" f/f Section)
D - Rigid Sections
(5/8 Vent)
PXT - 5 (5" f/f Section)
PXT - 10 (10" f/f Section)
PXT - 20 (20" f/f Section)
PEXT - 1 (12" f/m Section)
PEXT - 2 (24" f/m Section)
PEXT - 3 (36" f/m Section)
PEXT - 4 (48" f/m Section)
PEXT - 6 (72" f/m Section)
E-Elbows
(5/8 Vent)
PEL-90MM (m/m 90º Elbow)
PEL-90FF ( f/f 90º Elbow)
PEL-90FM ( f/m 90º Elbow)
PEL-45FM ( f/m 45º Elbow)
F - Wall Penetration Kit PRVK01F (5/8 venting only)
PRVK01 (5/8 venting only)
G - Support Ring & Plate PSPXT-8 (5/8 venting)
H - Firestop FS-8
I - Roof Flashing PRF-7 (1/12 - 7/12 pt.)
PRF-12 (7/12 - 12/12 pt.)
J - Heat Shield RHS101 (5"/8")
K - Heat Guard MTKOG
Under no circumstances can Montigo ex venting be cut to
accommodate an installation. Use an alternative length to complete
your vent run.
NOTICE
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44