Greenheck 483586 Microprocessor Controller DOAS v3.001 December 2018 Reference guide

Category
Split-system air conditioners
Type
Reference guide

This manual is also suitable for

®
Document 483586
Microprocessor Controller for
Dedicated Outdoor Air System
Microprocessor Controller for DOAS 1
®
Reference Guide for Microprocessor Controller
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
DOAS Technical Support
Call 1-866-478-2574
Program Features
The microprocessor controller offers control through
easy monitoring and adjustment of unit parameters by
way of a lighted graphical display and an integral push-
button keypad.
Pre-Programmed Operating Sequences
The controller has been pre-programmed to offer
multiple control sequences to provide tempered air.
Factory default settings allow for easy setup and
commissioning. The sequence parameters are fully
adjustable. Refer to the Sequence of Operation for
details.
BMS Communication
The user can remotely adjust setpoints, view unit status
points and alarms. The microprocessor controller is
capable of communicating over several protocols:
BACnet® MSTP Modbus RTU
BACnet® IP Modbus TCP
• LonWorks®
Reference Points List for a complete list of BMS points.
Internal Time Clock (Schedule)
The controller has an internal programmable time clock,
allowing the user to set occupancy schedules for each
day of the week. The controller option also has morning
warm-up and cool down capability for improved
comfort at the time of occupancy.
Alarm Management
The microprocessor controller will monitor the unit’s
status for alarm conditions. Upon detecting an alarm,
the controller will record the alarm description, time,
Introduction
date, and input/output status points for user review. A
digital output is reserved for remote alarm indication.
Alarms are also communicated via BMS (if equipped).
Occupancy Modes
The microprocessor controller offers three modes of
determining occupancy: a digital input, the internal time
clock or the BMS. If in the unoccupied mode, the unit
will either be shut down, continue normal operation
utilizing adjustable unoccupied setpoints, recirculate
with unoccupied setpoints or will cycle on to maintain
adjustable unoccupied room temperature and humidity
setpoints (room temperature and humidity sensor is
optional).
Remote Display Panel (if equipped)
A touch pad display panel allows for remote monitoring
and adjustment of parameters, allowing ease of control
access without going outdoors.
WARNING
Electrical shock hazard. Can cause personal injury or
equipment damage. Service must be performed only
by personnel that are knowledgeable in the operation
of the equipment being controlled.
WARNING
Mechanical high static protection cutoffs must
be installed by others to protect the system and
equipment from over-pressurization when using
factory provided control sensors. The manufacturer
does not assume responsibility for this.
DOAS v3.001
Microprocessor Controller for DOAS2
®
Sequence of Operation
General Operation . . . . . . . . . . . . . . . . 3-4
Setpoint Control (Occupied) . . . . . . . . . . . . 4
Setpoint Control (Unoccupied). . . . . . . . . . . 4
Heating . . . . . . . . . . . . . . . . . . . . . . . 4
Cooling . . . . . . . . . . . . . . . . . . . . . . . 4
Economizer. . . . . . . . . . . . . . . . . . . . . 5
Dehumidification . . . . . . . . . . . . . . . . . . 5
Reheat . . . . . . . . . . . . . . . . . . . . . . . 5
Supply Fan VFD Sequence. . . . . . . . . . . . . 5
Exhaust Fan VFD Sequence . . . . . . . . . . . . 5
OA and Recirc Air Damper Control. . . . . . . . . 6
Energy Recovery Wheel . . . . . . . . . . . . . . 6
Alarms . . . . . . . . . . . . . . . . . . . . . . . 7
Controller Overviews
Large Controller . . . . . . . . . . . . . . . . . . 8
Medium Controller . . . . . . . . . . . . . . . . . 9
c.pCOe - Expansion Board Overview, Medium . . 10
pCOe - 4:1 Furnace. . . . . . . . . . . . . . . . .11
pCOe - High Turndown Furnace . . . . . . . . . . 11
Display Use . . . . . . . . . . . . . . . . . . . . . 12
Example of Parameter Adjustment . . . . . . . .12
Example of Web User Interface . . . . . . . . . .13
Main Menu . . . . . . . . . . . . . . . . . . . . . 14
Unit Status Overview. . . . . . . . . . . . . . 15-17
Unit Enable . . . . . . . . . . . . . . . . . . . . . 18
Menus
Control Variables
Temp Control . . . . . . . . . . . . . . . . 18-20
Dehumidification . . . . . . . . . . . . . . 20-21
Refrigeration. . . . . . . . . . . . . . . . . . .22
Damper Control . . . . . . . . . . . . . . . 22-23
Energy Recovery . . . . . . . . . . . . . . . . 24
Fan Control
Supply Fans Control . . . . . . . . . . . . . 25
Exhaust Fans Control. . . . . . . . . . . . .26
Occupancy . . . . . . . . . . . . . . . . . . . 27
Advanced
Manual Overrides. . . . . . . . . . . . .28-30
Network Settings . . . . . . . . . . . . . 30-31
Backup/Restore . . . . . . . . . . . . . 32-33
I/O Configuration . . . . . . . . . . . . . . .34
Unit Configuration . . . . . . . . . . . . . .34
Alarms . . . . . . . . . . . . . . . . . . . . . .35
Table of Contents
IG Furnace Alarm Descriptions . . . . . . . . . .35
Appendix
Remote Display . . . . . . . . . . . . . . . . . . 36
Carel
®
NTC Temp Sensor Chart . . . . . . . .36
I/O Expansion Board Quick Start . . . . . . . . . 37
Room Thermostat Quick Start. . . . . . . . .38-39
GreenTrol
®
Airflow Monitoring Quick Start . . . . 40
Points List . . . . . . . . . . . . . . . . . . . 41-52
Modbus Connections . . . . . . . . . . . . . . .53
Maintenance Log . . . . . . . . . . . . . . . .53-54
Our Commitment . . . . . . . . . . . . . Backcover
Microprocessor Controller for DOAS 3
®
Sequence of Operation
The microprocessor controller can be configured for
air handler, energy recovery, and dedicated outdoor air
systems. Each application utilizes similar technologies
for heating and cooling: chilled water, hot water, indirect
gas, electric heat, packaged DX cooling, and packaged
DX cooling with digital and inverter scrolls. All setpoints,
lockouts and delays are user adjustable via the integral
keypad display, remote display, or web user interface.
General Operation
UNIT START COMMAND: The microprocessor
controller requires a digital input to enable operation.
The unit can then be commanded on or off by this
digital input, keypad, the BMS or internal time clock.
When a start command becomes active the following
steps occur:
Energy recovery wheel starts, if equipped
Factory mounted and wired dampers are powered
(Outdoor air, exhaust air, and recirculation air
dampers, if equipped)
Exhaust fan, if equipped, starts after adjustable delay
Supply fan starts after adjustable delay
Tempering operation starts after adjustable delay
UNIT STOP COMMAND: A shutdown occurs when
there is not an occupied or unoccupied start command.
The following shutdown methods can occur.
Hard shutdown occurs under the following conditions:
A user or the BMS disables the system, and the
supply temperature is less than the soft shutdown
enable setpoint.
Occupancy is commanded to unoccupied while there
is no unoccupied start command, and the supply
temperature is less than the soft shutdown enable
setpoint.
When a hard shutdown occurs:
The unit shuts down immediately.
Dampers spring-return to their off position.
Soft shutdown occurs under the following conditions:
A user or the BMS disables the system, and the
supply temperature is greater than or equal to the
soft shutdown enable setpoint.
There is no unoccupied or occupied start command
and the supply temperature is greater than or equal
to the soft shutdown enable setpoint.
The following occurs during a soft shutdown:
Tempering outputs immediately revert back to their
off value; while
Dampers remain open and fans continue to run; until
The supply air temperature falls below the soft
shutdown enable setpoint minus 5.0°F; or
The soft shutdown delay timer has expired.
UNIT/SYSTEM DISABLED COMMAND:
The unit becomes disabled due to the following:
The unit was disabled from the controller’s Unit
Enable screen.
The unit was disabled from the BMS.
The shutdown input is in the shutdown position.
A shutdown alarm was activated.
When disabled the following actions occur:
The unit shuts down immediately; and
Dampers spring-return to their off position.
OCCUPIED/UNOCCUPIED MODES: The
microprocessor controller offers three modes of
determining occupancy: digital input, the internal time
clock or the BMS. When in the unoccupied mode, the
unit can be configured to shut down, or cycle on to
maintain the unoccupied room setpoints. The unit can
be temporarily overridden to the occupied mode via
a digital input, keypad display, or room thermostat, if
equipped.
The controller can be configured with morning warm-
up and cool down to bring the space to the occupied
setpoint prior to occupancy.
Occupied Mode:
- Exhaust fan on, if equipped
- Supply fan on
- Heating (refer to Heating section)
- Cooling (refer to Cooling section)
- Energy Recovery Wheel Control (refer to
Energy Recovery Wheel section), if equipped
- Damper Control (refer to Outdoor Air and
Recirculated Air section), if equipped
Unoccupied Mode (Unit Off): Unit remains off when
in unoccupied mode.
Normal Operation with Unoccupied Setpoints:
Optional unoccupied mode will operate as if in
occupied mode but will utilize adjustable unoccupied
setpoints.
- Exhaust fan on, if equipped
- Supply fan on
- Heating (refer to Heating section)
- Cooling (refer to Cooling section)
- Energy Recovery Wheel Control (refer to Energy
Recovery Wheel section), if equipped
- Damper Control (refer to Outdoor Air and
Recirculated Air section), if equipped
Recirculation with Unoccupied Setpoints: Optional
unoccupied mode when there is an unoccupied
recirculation damper. The unit will continue to run,
but in full recirculation.
- Supply fan on
- Recirculation air damper open
- OA damper closed
- Tempering operations begin
Microprocessor Controller for DOAS4
®
Sequence of Operation
Unoccupied Mode (Cycle on Room): Optional
unoccupied mode when there is an unoccupied
recirculation damper and room temperature and/
or humidity sensor(s) connected to the controller.
The unit will cycle on to maintain unoccupied room
setpoints if there is a call for unoccupied heating,
cooling or dehumidification.
- Exhaust fan off, if equipped
- Supply fan on
- Recirculation air damper open
- OA damper closed
- Tempering operations begin
Setpoint Control (Occupied)
Supply air temperature setpoint can be configured
as constant, or can be reset by either outside air
temperature, or room temperature setpoint. If equipped
with BMS communications, the user can also directly
command the supply temperature setpoint, or room
temperature setpoint, if equipped.
Outdoor Air Temperature Reset Function: The
controller will default to supply temperature reset
based on outdoor air temperature. The controller will
monitor the OA temperature and reset the supply
temperature setpoint based upon the outdoor air
reset function.
Room Temperature Reset (optional): With a
room temperature sensor, the controller will adjust
the supply air temperature setpoint between
the minimum (55°F) and maximum (90°F), to
satisfy the desired room temperature. Room
temperature setpoint can be adjusted locally at
the microprocessor by BMS or room thermostat, if
equipped.
Setpoint Control (Unoccupied)
When equipped with an unoccupied recirculation
damper and optional room temperature and/or
humidity sensors, the unit will cycle on to maintain the
unoccupied room setpoints.
Unoccupied Heating: If equipped with heating,
the unit is enabled when the room temperature is
less than the unoccupied heating setpoint minus
differential (60°F). The supply air temperature setpoint
will be set to the supply maximum reset limit (90°F).
The unit cycles off when the room temperature
reaches the unoccupied heating setpoint.
Unoccupied Cooling: If equipped with cooling, the
unit is enabled when the room temperature is greater
than the unoccupied cooling setpoint plus differential
(80°F+5°F). The supply air temperature setpoint will
be set to the supply minimum reset limit (55°F). The
unit cycles off when the room temperature reaches
the unoccupied cooling setpoint.
Unoccupied Dehumidification: If equipped with
cooling, the unit is enabled when the room relative
humidity exceeds the unoccupied room relative
humidity setpoint plus differential (50%+5%). The
supply air temperature setpoint will be set to the
equivalent occupied supply setpoint.
Morning Warm-Up/Cool Down: The unit uses
adjustable preset time to temper the space to
occupied setpoint prior to occupancy (room
temperature sensor is optional).
Heating
The heating is controlled to maintain the supply
temperature setpoint. The heating will be locked out
when the outside air temperature is above the heating
lockout (80°F adj).
Indirect Gas Furnace: Microprocessor controller
will modulate the indirect gas furnace to maintain the
supply temperature setpoint.
Hot Water Coil: Microprocessor controller will
modulate a hot water valve (provided by others) to
maintain the supply temperature setpoint. Coil freeze
protection must be provided by others in the field!
Electric Heater: Microprocessor controller will
modulate an electric heater to maintain the supply
temperature setpoint.
Cooling
The cooling is controlled to maintain the supply
temperature setpoint. The mechanical cooling will be
locked out when the outside air temperature is below
the cooling lockout (55°F).
Chilled Water: Microprocessor controller will
modulate a chilled water valve (provided by others) to
maintain supply air setpoint. Coil freeze protection
must be provided by others in the field!
Packaged/Split DX Cooling (Standard Scroll):
Microprocessor controller will enable stages of
cooling to maintain the supply air setpoint.
Packaged DX Cooling (Digital Scroll):
Microprocessor controller will modulate the digital
scroll to maintain the supply air temperature setpoint.
Packaged DX Cooling (Inverter Scroll):
Microprocessor controller will modulate the inverter
scroll to maintain the supply air temperature setpoint.
Microprocessor Controller for DOAS 5
®
Economizer
If the application requires cooling, and the outdoor
air conditions are suitable for free cooling, the
controller may enter the economizer state. If the unit is
economizing and the discharge temperature setpoint is
not being met, the controller may bring on mechanical
cooling. If equipped with a modulating outdoor air and
recirculated air damper, the dampers will modulate
between the minimum OA and maximum positions to
maintain the supply temperature setpoint. If equipped
with an energy wheel, Reference Energy Recovery
Wheel Sequence.
Temperature: The economizer will be locked out
when:
- The outside air is greater than the economizer
high lockout (65°F).
- The unit is operating in dehumidification mode.
- There is a call for heating.
Temperature/Enthalpy: The economizer will be
locked out when:
- The outside air is greater than the economizer
high lockout (65°F dry-bulb).
- The outside air is greater than the economizer
high enthalpy lockout (23 btu/lb).
- The unit is operating in dehumidification mode.
- There is a call for heating.
Dehumidification
The cooling is controlled to maintain the cold coil
setpoint. The dehumidification sequence will be locked
out when the OA is less than the dehumidification
lockout (10°F) above the cold coil setpoint. If equipped
with BMS communications, the user can also directly
set the cold coil leaving air setpoint.
Optional Room Relative Humidity Sensor or
Thermostat: The controller will adjust the cold
coil leaving air temperature setpoint between the
minimum (50°F) and maximum (55°F) setpoint to
satisfy the desired room relative humidity setpoint.
Reheat
While the unit is in dehumidification mode, the supply
air can be reheated via Primary Heating Source, On/Off
Hot Gas Reheat or Modulating Hot Gas Reheat.
Modulating Hot Gas Reheat (valve): The
microprocessor controller will modulate the hot gas
reheat valve to maintain the supply temperature
setpoint.
Reheat Plus: The primary heat source configured to
act as secondary reheat.
Supply Fan VFD Sequence
The factory installed VFD is wired to the controller.
Supply fan speed needs to be set during test
and balance of the unit. If equipped with BMS
communications, the user can also directly command
the supply fan speed.
Optional Space/Duct CO
2
Sensor: The controller
will modulate the supply fan based upon a
comparison of the CO
2
setpoint to the actual CO
2
levels reported from the sensor.
Optional Duct Static Pressure Sensor: The
controller will modulate the supply fan based upon
a comparison of the duct static pressure setpoint to
the actual duct static pressure level reported from the
sensor.
Optional Building Static Pressure Sensor: The
controller will modulate the supply fan based upon a
comparison of the building static pressure setpoint to
the actual building static pressure level reported from
the sensor.
Optional Single Zone VAV (SZ): The controller will
control the supply air temperature and supply fan
speed to maintain the room temperature setpoint.
This sequence requires a room temperature sensor.
Heating - When the room requires heating,
the controller will reset the supply air temperature
setpoint up to the maximum (90°F) while increasing
the supply fan speed up to its maximum heating
speed.
Cooling - When the room requires cooling, the
controller will first reset the supply air temperature
setpoint down to the minimum (55°F) while the
supply fan remains at the minimum cooling speed.
After a time delay, the supply fan speed will increase
up to its maximum cooling speed to maintain the
room temperature setpoint.
Exhaust Fan VFD Sequence
The factory installed VFD is wired to the controller.
Exhaust fan speed needs to be set during test
and balance of the unit. If equipped with BMS
communications, the user can also directly command
the exhaust fan speed.
Optional Building Static Pressure Sensor: The
controller will modulate the exhaust fan based upon a
comparison of the building static pressure setpoint to
the actual building static pressure level reported from
the sensor.
Optional Supply Fan Tracking: The controller will
proportionally modulate the exhaust fan based upon
the supply fan speed.
Optional Outdoor Air Damper Tracking: The
controller will proportionally modulate the exhaust fan
based upon the outdoor air damper position.
Sequence of Operation
Microprocessor Controller for DOAS6
®
Outdoor Air and Recirculated (Recirc) Air
Damper Control
If equipped with a modulating outdoor air and
recirculated air damper, the recirculated air damper will
operate inverse of the outdoor air damper. The outdoor
air damper will open to a Minimum Outdoor Air Position
(Min OA) when in occupied mode. If the controller
is configured to modulate the supply fan speed, the
minimum and maximum OA positions can be reset
based on supply fan speed. If equipped with BMS
communications, the user can also directly reset the
damper position up to the maximum OA position.
Optional Space CO
2
Sensor: The controller will
proportionally modulate the OA/RA dampers based
upon a comparison of the CO
2
setpoint to the actual
CO
2
level reported from the sensor. As the CO
2
level
rises, the controller will proportionally modulate the
outdoor air damper open, between the minimum OA
damper position and maximum CO
2
position.
Optional Building Pressure: The OA/RA dampers
will modulate based upon the signal from a building
static pressure sensor. The controller will modulate
the dampers, between the minimum and maximum
OA positions, based upon a comparison of the
building static pressure setpoint to the actual building
static pressure level reported from the sensor.
Energy Recovery Wheel Sequences
Economizer (optional): If the unit is equipped with an
energy recovery wheel, the economizer will modulate/
stop the energy wheel to achieve free cooling. Jog
wheel control is available during stop wheel economizer
operation. This sequence allows the wheel to rotate for
a short period of time exposing a new section to the air
stream.
Stop Wheel: When economizer mode is enabled
and there is a signal for cooling, the wheel will stop
rotating to allow free cooling.
Modulate Wheel: When economizer mode is
enabled and there is a signal for cooling, the
controller modulates wheel speed to maintain the
supply temperature setpoint.
Energy Wheel Bypass Dampers, if equipped:
During normal operation, the dampers shall remain
closed to allow full operation of the energy wheel.
During economizer sequences, the dampers will be
open to bypass the energy wheel.
Frost Control (optional): The microprocessor
controller will activate the frost control method when
the outdoor air temperature is less than the defrost
setpoint (5°F) and the wheel pressure switch is closed
due to a high wheel pressure drop. Once the pressure
drop decreases below the pressure switch point or the
outdoor air temperature increases, the unit will resume
normal operation.
Electric Preheater: When frosting is occurring, the
preheater is energized to defrost the wheel.
Modulate Wheel: When frosting is occurring, the
wheel slows to allow defrosting to occur.
Cycle Wheel: When frosting is occurring, the
energy wheel is cycled off for a defrost cycle time
(5 minutes). After the defrost cycle time, the wheel
is re-energized to continue normal operation. The
controller will not allow another defrost cycle for a
minimum normal operating cycle time (30 minutes).
Timed Exhaust: When frosting is occurring, the
supply fan is cycled off along with the tempering for
a defrost cycle time (5 minutes). The exhaust fan
will continue to run allowing the warm exhaust air
to defrost the wheel. After the defrost cycle time,
the supply fan and tempering are re-energized to
continue normal operation. The controller will not
allow another defrost cycle for a minimum normal
operating cycle time (30 minutes).
Sequence of Operation
Microprocessor Controller for DOAS 7
®
Alarms
The microprocessor controller includes a digital output
for remote indication of an alarm condition, which
connects via the J15 port. Possible alarms include:
Dirty Filter Alarm: If the outside air or return air
filter differential pressure rises above the differential
pressure switch setpoint, the microprocessor
controller will activate an alarm.
Supply and Exhaust Air Proving Alarm:
Microprocessor controller monitors proving switch on
each blower and displays an alarm in case of blower
failure.
Sensor Alarm: Microprocessor controller will send
an alarm if a failed sensor is detected (temperature,
pressure, relative humidity).
Supply Air Low Limit: If the supply air temperature
drops below the supply air low limit (35°F), the
microprocessor controller will de-energize the unit
and activate the alarm output after a preset time
delay (300s).
Other Alarms: Wheel Rotation, High Wheel
Pressure, High/Low Refrigerant Pressure.
Sequence of Operation
Microprocessor Controller for DOAS8
®
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
NO12
C12
NC12
NO13
C13
NC13
C9
NO9
NO10
NO11
C9
G
G0
U1
U2
U3
GND
+VDC
+V term
GND
+5 V
REF
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
U6
U7
U8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J1
J24 J2 J3
J4 J5 J7
J8
J20
J21
J14
J10
J13
J12
J22
J16
J17
J18
J15
J6
J19
NO14
C14
NC14
NO15
C15
NC15
C16
NO16
NO17
NO18
C16
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
ID17
ID18
IDC17
U9
GND
U10
GND
drac SMBdrac suBdleiF
J23 FBus2
J11 pLAN
J25
BMS2
J26
FBus2
4321
Wheel Pressure Limit
Supply Fan Proving
Unit On/Off Input
Wheel Rotation Alarm
Occupied/Unoccupied Input
Exhaust Fan Proving
Dirty Filter Input
Supply Fan VFD Output
Room Temperature Sensor
Exhaust Fan VFD Output
Outdoor Air Damper Analog Output
Cooling/VSC Cond Fan Analog Output
Heating Analog Output
Hot Gas Reheat Analog Output
24VAC for Analog Outputs
Outdoor Relative Humidity Sensor
Duct Pressure Sensor
Building Pressure Sensor
Room RH
After Cold Coil Temperature Sensor
CO2 Sensor
Sensor B1, B2, B3 Commons
Supply Discharge Temperature Sensor
Outdoor Air Temperature Sensor
24VAC to Controller
Wheel Frost Mode
24 VAC When Unit On
Exhaust Fan Enable
Supply Fan Enable
Heating Enable
24 VAC from Supply Fan Proving
Staged Compressor 2
Staged Compressor 1
Economizer Mode/Output to Dampers
24 VAC
Alarm Dry Contact
Staged Compressor 3
Compressor Limit Circuit A
Compressor Limit Circuit B
Compressor Limit Circuit C
Compressor Limit Circuit D
Discharge Pressure Circuit B (VSC)
2 Speed Fan Input
2 Position Damper Input
Staged Compressor 4
Energy Recovery Wheel Enable
Inverter Compressor E-Stop (VSC)
Compressor Fan 1 Enable (VSC)
Compressor Fan 2 Enable (VSC)
Optional BACnet IP, Modbus TCP, Web UI, Ethernet Connections
Large Controller Overview
Remote Display
• Six conductor RJ25 cable
• Connects to J10
Optional LonWorks cards are
located in BMS Card port.
Optional Modbus RTU/BACnet MSTP connections
are made to the J26 FBus2 terminal.
Microprocessor Controller for DOAS 9
®
Medium Controller Overview
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
NO12
C12
NC12
NO13
C13
NC13
C9
NO9
NO10
NO11
C9
G
G0
U1
U2
U3
GND
+VDC
+V term
GND
+5 V
REF
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
U6
U7
U8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J1
J24 J2 J3
J4 J5 J7
J8
J20
J21
J14
J10
J13
J12
J22
J16
J17
J18
J15
J6
J19
NO14
C14
NC14
NO15
C15
NC15
C16
NO16
NO17
NO18
C16
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
ID17
ID18
IDC17
U9
GND
U10
GND
drac SMBdrac suBdleiF
J23 FBus2
J11 pLAN
J25
BMS2
J26
FBus2
4321
High Pressure Switch Circuit A
Supply Fan Proving
Occupied/Unoccupied Input
Low Pressure Switch Circuit A
Unit On/Off Input
OA/RA Damper End Switch
Cooling Analog Output
Hot Gas Reheat Analog Output
Condenser Fan Circuit A or Heating Analog Output
24VAC for Analog Outputs
Outdoor Relative Humidity Sensor
Supply Fan VFD Output
Outdoor Air Damper Output
Refrigerant Pressure Circuit A
Supply Discharge Air Temperature
Sensor B1, B2, B3 Commons
After Cold Coil Temperature Sensor
Outdoor Air Temperature Sensor
24VAC to Controller
Stagged Compressor 1
24 VAC When Unit On
Stagged Compressor 3
Stagged Compressor 2
Stagged Compressor 4
24 VAC from Supply Fan Proving
Economizer Mode/Output to Dampers
24 VAC
Alarm Dry Contact
Condenser Fan VFD Start
Exhaust Fan Proving
Dirty Filter Input
Wheel Rotation Alarm
Freeze Stat Input
Condenser Fan Stage 2 Start
Condenser Fan Stage 3 Start
Inverter Compressor E-Stop (VSC)
Refrigerant Pressure Circuit B
Condenser Fan Circuit B or Heating Analog Output
High Pressure Switch Circuit B
Low Pressure Switch Circuit B
Condensate Drain Pan Switch
Remote Start Input
Optional BACnet IP, Modbus TCP, Web UI, Ethernet Connections
Remote Display
• Six conductor RJ25 cable
• Connects to J10
Optional LonWorks cards are
located in BMS Card port.
Optional Modbus RTU/BACnet MSTP connections
are made to the J26 FBus2 terminal.
Microprocessor Controller for DOAS10
®
c.pCOe - Expansion Board Overview, Medium Controller Arrangement
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
19.2 K
9.6 K
38.4 K
57.6 K
CAREL
Modbus
ON
OFF
Address Ext. ProtBaud
Address Ext Baud Prot
24 VAC Power
Heating Output
Exhaust Fan VFD Output
Energy Recovery Output
Space Temperature
Mixed Air Temperature
Exhaust Air Temperature
Space Static Pressure
Supply Air Duct Static Pressure
Space Setpoint Adjustment
Wheel Enable
Furnace Heating Stage 1
Furnace Heating Stage 2
Preheater Enable
The expansion board is an I/O module than can be used to monitor additional statuses or provide commands from
medium board controller.
Microprocessor Controller for DOAS 11
®
pCOe - 4:1 Furnace Overview
High Speed Pressure Switch
Main Gas Valve
Ignition Controller Alarm
Low Speed Pressure Switch
24 VAC for Analog Outputs
Modulating Gas Valve
Modbus Connection
24 VAC to Controller
Modbus Address Switches
24 VAC
High Speed Fan
24 VAC
Ignition Controller
pCOe - High Turndown Furnace
Low Speed Pressure Switch
Main Gas Valve - Small Manifold
Main Gas Valve - Large Manifold
Ignition Controller Alarm
24 VAC for Analog Outputs
Modulating Gas Valve
Modbus Connection
24 VAC to Controller
Modbus Address Switches
24 VAC
High Speed Fan
24 VAC
Ignition Controller - Small Manifold
24 VAC
Ignition Controller - Large Manifold
High Speed Pressure Switch
Microprocessor Controller for DOAS12
®
The microprocessor controller is located in the unit control center. The face of the controller has six buttons,
allowing the user to view unit conditions and alter parameters. The microprocessor controller is pre-programmed
with easy to use menus. A remote display is also available, which connects via the J10 port. A six wire patch cable
is needed.
Display Use
Keypad Description
Button Description Functions
Main Menu Press to go directly to the Main Menu from any screen.
From the Main Menu, navigate to the following screens:
• Unit Enable
• Unit Status
• Ctrl Variables
• Alarm Menu
Alarm The Alarm button flashes when there is an active alarm.
Press to view active alarms.
Press twice to go to the alarms reset screen.
Escape Press from the Main Menu to view the Unit Status screen.
Press to go back one menu level.
Press when editing a variable to cancel editing.
Up Press to navigate through the menus/screens.
Press after entering a variable to increase a current value.
Enter Press to enter a highlighted menu or screen item.
Press to enter a writable variable and press again to confirm the new variable value.
Down Press to navigate menus/screens.
Press after entering a variable to decrease the current value.
Virtual keypad/display on web interface only.
These two buttons on the virtual keypad/display are used to simulate two-button actions on the handheld
keypad/display.
To simulate pressing two buttons simultaneously:
1. Click on 2-Button Click.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
To simulate pressing and holding two buttons simultaneously:
1. Click on 2-Button Hold.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
Example of Parameter Adjustment
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
Once the cursor has reached the desired parameter, press the
buttons to
adjust the value.
The cursor always begins in the upper left corner of the display and will be
blinking. Press the
button to move the cursor down for parameter adjustment.
Supply air low limit
Alarm when supply is
below: 35.0º F
Alarm delay: 300s
When satisfied with the adjustment, press the button to save the parameter.
When finished, make certain the cursor is in the upper left corner. If the cursor is
not in the upper left corner, the changes will not be saved. The cursor must be in
the upper left corner to enable screen advancement.
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
Microprocessor Controller for DOAS 13
®
Web User Interface
The Web User Interface allows access to the unit controller through the building network. Reference Cntrl Variables/
Advanced/Network Settings to set the IP network protocol. Once proper communication is established, the user
can click on the follow tabs:
Overview – Includes a functioning unit graphic, monitoring points, and active setpoint adjustment.
Alarm – Shows current and cleared alarms.
Unit Display – Mimics the unit controller display. Allows the user full access to the controller without physically
being at the unit.
Trending – User can view past and present controller points.
Information – Provides manufacturer support information as well as IOM resources.
Service – User must be logged with service access criteria (9998). Once proper login is established, the user can
view configured input/output points associated with the unit controller
Microprocessor Controller for DOAS14
®
Main Menu Navigation
Unit Enable
Main Status Ctrl Variables Alarm Menu
Unit Status
Temp Control
Active Alarms
Input Output Status
Dehumidification
Reset Alarms
Note:
Additional status screens
are displayed depending
on unit configuration.
Screens may include, but
are not limited to:
Occupancy
Damper positions
Fan status
Airflow
Setpoints
Economizer
Energy recovery
Cooling
Circuit pressure
Heating
Dehumidification
Static pressure
Refrigeration Compressor Control
Alarm History
Pressure Control
Clear History
Damper Control
Export History
Energy Recovery
Fan Control Supply Fan Control
Exhaust Fan Control
Occupancy
Advanced
Note:
The Advanced
menu is read-
only. The service
password is
required to change
these settings.
Reference the
Advanced menu
section for more
information.
*Consult
factory for more
information.
Login
Manual Overrides
Adv. Setpoints*
Network Settings
Backup/Restore
IO Status/Offset*
IO Config
Unit Config
Unit Settings*
Service Info*
Alarm
Management
Shutdown
Alarms
General
Alarms
Microprocessor Controller for DOAS 15
®
The microprocessor controller will revert to a default main menu loop. This loop includes several screens to view the
operating conditions of the unit. Scroll through the menu screens by using the
buttons.
Unit Status Overview
Unit Status Screen Symbols
Symbol Indicates
Supply air fan status.
Rotation indicates airflow; static blades indicate no airflow.
Cooling
Heating
Dehumidifying
Economizing
Defrost
THE INITIAL MENU SCREEN DISPLAYS THE JOB NAME, UNIT TAG, UNIT STATUS, OUTSIDE
AIR CONDITIONS, SPACE CONDITIONS AND SETPOINTS.
Possible modes include:
• Off/Standby
• Unoccupied Start
• Dampers Open
• Fan Start Delay
• Fans Starting
• Startup Delay
• System On
• Soft Shutdown
• System Disabled
• Remote Off
• Shutdown Alarm
• Fans Only
• Economizing
• Cooling
• Dehumidifying
• Heating
• HGRH Purging
• Defrost Active
• Overrides Active
• Expansion Offline
INPUT OUTPUT STATUS
Displays real time conditions from sensors located in the unit and building space
if equipped with space mounted sensors. Controller output conditions can also
be viewed from this screen. To view the desired input/output point, the user must
select the desired channel. Reference the Controller Overview section in this IOM
for individual point locations.
OCCUPANCY STATUS
Displays current status of occupancy and the configured occupancy control
method and time zone.
DAMPER COMMANDED POS
This screen appears if equipped with modulating outdoor air and recirculated air
dampers. Displays current position of the outdoor air damper. Recirculating air
damper position is the inverse of outside damper position.
SUPPLY FAN STATUS
This screen displays the fan enable command, fan proving status, and the supply
fan ramp being sent from the controller to the VFD. The minimum and maximum
speeds are set in the VFD (Reference unit Installation and Operation Manual for
VFD programming). The controller can modulate the fan between the min and
max speeds via an analog output.
Microprocessor Controller for DOAS16
®
EXHAUST FAN STATUS
This screen displays the fan enable command, fan proving status, and the
exhaust fan ramp being sent from the controller to the VFD. The minimum and
maximum speeds are set in the VFD (Reference unit Installation and Operation
Manual for VFD programming). The controller can modulate the fan between the
min and max speeds via an analog output.
AIRFLOW STATUS
This screen displays the current status of airflow volumes if the unit is provided
with airflow monitoring.
AMBIENT LOCKOUT STATUS
Displays heating and cooling lockout status based on the outside air ambient
temperature. Ambient lockouts for heating and cooling can be altered by entering
Main Menu/Ctrl Variables/Temp Control/Cooling or Heating.
OUTSIDE RESET
This screen will be active if the controller is configured for outside air reset. The
heating and cooling devices modulate to maintain the supply air temperature
setpoint as determined by the outside reset calculation.
SUPPLY SETPOINT
Displays current supply temperature and supply temperature setpoint to be
achieved.
ECONOMIZER RAMP
The economizer ramp screen will be active if the unit is configured for an
economizer control method. This screen displays the economizer setpoint, supply
air discharge temperature, economizer ramp status, and economizer control
mode of control. Economizer control mode options include, outside dry bulb,
outside enthalpy, comparative dry bulb, and comparative enthalpy.
CO
2
RAMP OUTPUT
The CO
2
Ramp Output screen will be active if the unit is configured for CO
2
control. This screen displays the CO
2
setpoint, CO
2
level from the space, and the
status of the control ramp.
ENERGY RECOVERY WHEEL STATUS
This screen provides overall status of the energy recovery wheel.
ACTIVE RESET
This screen will be active if temperature control mode is set for space or return air
reset. The supply temperature setpoint is calculated based on the active setpoint
and the current space or return temperature. The calculated setpoint is scaled
between the supply temperature minimum and maximum setpoints determined by
the current mode of operation.
Unit Status Overview
Microprocessor Controller for DOAS 17
®
COOLING RAMP
This screen displays the active setpoint, supply discharge temperature, cooling
enable/disable, cooling ramp being sent from the controller, and the overall
capacity being demanded.
COMPRESSOR REQUEST
The compressor request screen will be active if the unit is equipped with DX
cooling. Screen displays overall status of individual compressor operation being
sent from the unit controller. Example: Circuit A compressor enable (On) with
modulating value of 26%.
HEATING RAMP
This screen displays the active setpoint, supply air temperature, heating enable/
disable, and heating ramp being sent from the controller.
DEHUMIDIFICATION
This screen will display the overall dehumidification status and selected mode of
dehumidification control.
The following dehumidification modes are available when the space is in occupied
mode:
• Cold coil setpoint plus offset (10ºF)
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point
*Available during unoccupied mode.
HGRH RAMP OUTPUT
This screen will display overall hot gas reheat status which includes active
setpoint, supply air discharge temperature, hot gas reheat enable/disable, and hot
gas reheat control loop being sent from the controller.
SUPPLY SPACE STATIC
This screen displays status points if the unit is configured for space static
pressure control. Status points include controller output ramp, static pressure
in the space, and the space static pressure setpoint. Similar status screen will
appear for the exhaust fan if the unit is configured for exhaust fan space static
control.
SUPPLY/RETURN DUCT STATIC
This screen displays status points if the unit is configured for duct static pressure
control. Status points include controller output ramp, static pressure in the duct,
and the duct static pressure setpoint. Similar status screen will appear for the
exhaust fan if the unit is configured for exhaust fan duct static control.
DEFROST RAMP OUTPUT
This screen only appears if the unit has an energy recovery wheel and a frost
control method was provided on the unit.
Upon sensing a high differential pressure across the energy wheel, the unit will
go into defrost if the outside air temperature is below the defrost temperature
setpoint.
Unit Status Overview
Microprocessor Controller for DOAS18
®
Unit Enable
The controller is equipped with several menus to help guide users with altering program parameters. The following
menus can be accessed by pressing the
button. To enter the desired menu, press the button.
The Unit Enable menu allows the user to enable and disable the unit through the
controller. Reference sequence of operation for additional unit starts/stop details.
The unit ships from the factory in a disabled state. To allow the unit to operate,
the controller must receive a run command from digital input ID4. Jumper unit
terminals R - G to allow the unit to operate.
Change to (Enabled/Disabled): Enables user to manually turn unit on/off via
display. Unit terminal G must have 24 VAC power to enable the unit.
Outdoor Air Reset Function
45°
50°
55°
60°
65°
50° 55° 60° 65° 70°
Outside Air Temperature (°F)
Supply Air Set Point (°F)
70°
75°
Control Variables
The Controls Variables menu allows the user to view and adjust unit control
parameters.
METHOD FOR TEMPERATURE CONTROL
Possible Setpoint Sources:
Supply Temp Control – The supply discharge setpoint to be a constant value (e.g.
72°F). Reference Temperature Setpoint screen for setpoint adjustment.
Space ResetThe controller will reset the supply air temperature set point to
maintain the room temperature set point (requires room temp sensor). Reference
the Temperature Setpoint screen for room setpoint adjustment.
Return ResetThe controller will reset the supply air temperature set point to
maintain the return air temperature set point (requires duct mounted return air
temp sensor). Reference the Temperature Setpoint screen for return air setpoint
adjustment.
OA Reset – The controller monitors the outdoor air temperature and adjusts the
desired supply temperature set point accordingly. For example, when the outdoor
air is below 55°F, the controller will change the supply set point to 70°F. If the
outdoor air is above 65°F, the controller will change the supply set point to 55°F.
If the outdoor air temperature is between 55°F and 65°F, the supply set point
changes according to the outdoor air reset function. A visual representation of
the outdoor air reset function is shown below. Reference Outside Setpoints for
minimum and maximum outside air limits.
Control Variables
Temp Control
The Temperature Control menu allows the user to view and adjust temperature
control conditions of the unit.
Menu
Microprocessor Controller for DOAS 19
®
OUTSIDE SETPOINTS
This screen only appears if outside reset is selected as the reset control mode.
TEMPERATURE SETPOINT
This screen only appears if supply temp control, space reset, or return reset is
selected as the reset control mode.
Possible Setpoint Sources:
Local – The room set point will be constant; set from screen (e.g. 72°F).
BMS – The BMS can directly control the room temperature set point (requires
BMS communication option).
T-Stat – The room set point will be adjustable from the room thermostat.
Reference Appendix: Room Thermostat Quick Start for additional information.
HEAT COOL DEADBAND
This screen only appears if space reset or return air reset is selected as the reset
control mode. The heat cool deadband allows for separate cooling and heating
setpoints when the reset control mode is set for space reset or return air reset.
SUPPLY SETPOINTS
Cooling and heating supply setpoints screens only appear if outdoor reset,
space reset, or return air reset is selected. These screens allow the user to set
the minimum and maximum setpoint limits for cooling or heating operation.
The controller will adjust the supply temperature setpoint between the set limits
depending on mode of operation.
COOLING LOCKOUT
This screen displays the cooling lockout temperature. Cooling will be disabled
when outside air is below the cooling lockout temperature (55ºF).
MODE SWITCH DISPLAY
This screen displays the delay time required before switching between heating
and cooling mode.
STARTUP DISPLAY
This screen displays the delay time after the fans have started and tempering
begins
Menu
Microprocessor Controller for DOAS20
®
HEATING LOCKOUT
This screen displays the heating lockout temperature. Heating will be disabled
when outside air is above the cooling lockout temperature (80ºF).
SPACE SETPOINTS DURING THE UNOCCUPIED MODE
The controller will have separate screens for unoccupied cooling and heating
setpoints. Reference Occupied control variables for further detail.
Unoccupied Cooling Example: If setpoint = 80ºF, unoccupied cooling is enabled
when room equals 80ºF and above. Unoccupied cooling is disabled when room
temperature is below 75ºF.
Unoccupied Heating Example: If setpoint = 60ºF, unoccupied heating is enabled
when room temperature equals 60ºF and below. Unoccupied heating is disabled
when room temperature is above 65ºF.
THIS SCREEN DISPLAYS METHOD FOR DEHUMIDIFICATION.
Possible Methods:
• Outside Air Temp is greater than cold coil setpoint plus offset (10ºF)
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point
*Available during unoccupied mode.
There must be a constant call for dehumidification for the duration of the enable
delay for dehumidification mode to become enabled. The call remains active
until conditions are satisfied and dehumidification mode has been active for
the minimum active time. Reference Ctrl Variables/Advanced/Unit Config/Unit
Configuration Occupied Dehum Call for dehumidification method options.
THIS SCREEN DISPLAYS METHOD FOR DEHUMIDIFICATION IN UNOCCUPIED MODE.
If the unit is unoccupied while there is a dehumidification call, the unit will start
and dehumidify until the unoccupied dehumidification setpoints are satisfied.
The above dehumidification modes marked with an * indicate availability during
unoccupied mode. The unoccupied dehumidification mode can be set differently
than the occupied dehumidification mode. Reference Ctrl Variables/Advanced/
Unit Config/Unit Configuration Unoccupied Dehum Call for dehumidification
method options.
Control Variables
Dehumidification
The Dehumidification menu allows the user to view and adjust dehumidification
control parameters.
Menu
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55