MGE UPS Systems EPS 6000 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
EPS 6000 UPS
Shared Systems
User’s Guide
IMPORTANT SAFETY INSTRUCTION
SAVE THESE INSTRUCTIONS This manual contains important instructions for the EPS
6000 series UPS Systems that must be followed during installation, operation and
maintenance of the equipment.
This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and
used in accordance with instruction manual, may
cause harmful interference to radio
communications. Operation of this equipment in a
residential area is likely to cause harmful
interference in which case the user will be required
to correct the interference at his own expense.
NOTE
As standards, specifications, and designs are
subject to change, please ask for confirmation of
the information given in tihs publicaion.
This manual is a controlled document, pages
should not individually be removed from this
binder.
WARNING
OPENING ENCLOSURES EXPOSES HAZARDOUS
VOLTAGES. ALWAYS REFER SERVICE TO
QUALIFIED PERSONEL ONLY
WARNING
For service call
1-800-438-7373
86-130034-00 B00 11/96
Copyright © 1996 MGE UPS Systems, Inc..
All rights reserved. Printed in U.S.A.
MGE UPS Systems
1660 Scenic Avenue
Costa Mesa, CA 92626
(714) 557-1636
prepared for:
EPS 6000
Shared Systems
User’s Guide
Warranty
Seller warrants to the Ultimate Purchaser (the purchaser who buys for use, and not for resale) that all products
furnished under this order and which are manufactured by Seller will conform to final specifications, drawings, samples
and other written descriptions approved in writing by Seller, and will be free from defects in materials and workmanship.
These warranties shall remain in effect for period of twelve (12) months after delivery to the Ultimate Purchaser. But if the
Seller installs the equipment or supplies technical direction of installation by contract, said one year shall run from the
completion of installation, provided installation is not unreasonably delayed by Ultimate Purchaser. Parts replaced or
repaired in the warrant period shall carry the unexpired portion of the original warranty. A unit placed with the Purchaser
on consignment and then later purchased will be warranted for twelve (12) months from the time the Seller receives notifi-
cation of the Purchaser’s intent to purchase said consigned item. The foregoing in its entirety is subject to the provision
that in no case will the total warranty period extend beyond 18 months from date Seller ships equipment from point of
manufacture.
The liability of Seller hereunder is limited to replacing or repairing at Seller’s factory or on the job site at Seller’s
option, any part or parts which have been returned to the Seller and which are defective or do not conform to such speci-
fications, drawings or other written descriptions; provided that such part or parts are returned by the Ultimate Purchaser
within ninety (90) days after such defect is discovered.The Seller shall have the sole right to determine if the parts are to
be repaired at the job site or whether they are to be returned to the factory for repair or replacement. All items returned to
Seller for repair or replacement must be sent freight prepaid to its factory. Purchaser must obtain Seller’s Return Goods
Authorization prior to returning items.The above conditions must be met if warranty is to be valid. Seller will not be liable
for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of the item,
or for damage due to accident, abuse, or Act of God.
In no event shall the Seller be liable for loss, damage, or expense directly or indirectly arising from the use of the
units, or from any other cause, except as expressly stated in this warranty. Seller makes no warranties, express or
implied, including any warranty as to merchantability or fitness for a particular purpose or use. Seller is not liable for and
Purchaser waives any right of action it has or may have against Seller for any consequential or special damages arising
out of any breach of warranty, and for any damages Purchaser may claim for damage to any property or injury or death to
any person arising out of its purchase of the use, operation or maintenance of the product. Seller will not be liable for any
labor subcontracted or performed by Purchaser for preparation of warranted item for return to Seller’s factory or for
preparation work for field repair or replacement.Invoicing of Seller for labor either performed or subcontracted by
Purchaser will not be considered as a liability by the Seller.
This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a
writing signed by an officer of the Seller. This warranty shall extend to the Ultimate Purchaser but to no one else.
Accessories supplied by Seller, but manufactured by others, carry any warranty the manufacturers have made to Seller
and which can be passed on to Ultimate Purchaser.
Seller makes no warranty with respect to whether the products sold hereunder infringe any patent, U.S. or foreign,
and Buyer represents that any specially ordered products do not infringe any patent.Buyer agrees to indemnify and hold
Seller harmless from any liability by virtue of any patent claims where Buyer has ordered a product conforming to Buyer’s
specifications, or conforming to Buyer’s specific design.
Buyer has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any oral
representation shall not bind Seller and shall not be part of any warranty.
There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS
Systems, Inc. be responsible for consequential damages or for any damages except as expressly stated herein.
Service and Factory Repair - Call 1 - 800 - 438 - 7373
Direct questions about the operation, repair, or servicing of this equipment to MGE UPS Systems, Inc. Customer
Support Services. Include the part number, assembly number, and serial number of the unit in any correspondence.
Should you require factory service for your equipment, contact MGE UPS Systems, Inc. Customer Support Services and
obtain a Return Goods Authorization (RGA) prior to shipping your unit. Never ship equipment to MGE UPS Systems, Inc.
without first obtaining an RGA.
Proprietary Rights Statement
The information in this manual is the property of MGE UPS Systems, Inc., and represents a proprietary article in
which MGE UPS Systems, Inc., retains any and all patent rights, including exclusive rights of use and/or manufacture
and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture the article
or articles shown herein.Such permission may be granted only by specific written authorization, signed by an officer of
MGE UPS Systems, Inc.
IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE
UPS Systems are trademarks of MGE UPS Systems, Inc. Other trademarks that may be used herein are owned by their
respective companies and are referred to in an editorial fashion only.
Revision History
EPS 6000 Uninterruptible Power System Installation Manual
86-130034-00
Copyright © 1996 MGE UPS Systems. All rights reserved. Printed in U.S.A.
Revision: B00 11/96
EPS 6000 UPS
Shared Systems
User’s Guide
Section I Introduction
1.0 . . . . . . . . . . . . . . . Scope 1 — 1
1.1 . . . . . . . . . . . . . . . General Description 1 — 1
1.2 . . . . . . . . . . . . . . . Description of UPS Module
Major Internal Components 1 — 4
1.2.1 Rectifier/Battery Charger 1 — 4
1.2.2 Inverter 1 — 4
1.2.3 Inverter Transformer 1 — 4
1.2.4 Battery System 1 — 4
1.3 . . . . . . . . . . . . . . . Description of SSC
Major Internal Components 1 — 5
1.4 . . . . . . . . . . . . . . . Options 1 — 13
1.5 . . . . . . . . . . . . . . . Specifications, UPS Modules 1 — 13
1.5.1 Electrical 1 — 13
1.5.2 Mechanical 1 — 14
1.5.3 Environmental 1 — 15
1.6 . . . . . . . . . . . . . . . Specifications,
Static Switch Cabinet 1 — 15
1.6.1 Electrical 1 — 15
1.6.2 Mechanical 1 — 16
1.6.2 Mechanical 1 — 12
Section II Operation
2.0 . . . . . . . . . . . . . . . Scope 2 — 1
2.1 . . . . . . . . . . . . . . . System Operation Overview 2 — 1
2.1.1 Static Switch Cabinet Operation 2 — 1
2.1.2 Normal Operation 2 — 2
2.1.3 On-Battery Operation 2 — 2
2.2 . . . . . . . . . . . . . . . Indicators and Controls 2 — 3
2.2.1 Front Panel 2 — 3
2.2.2 Alphanumeric Display
and Controls 2 — 6
2.2.3 Hidden Panel 2 — 9
2.2.4 Circuit Breakers,
Contactors and Switches 2 — 13
2.3 . . . . . . . . . . . . . . . Using the Alphanumeric Display 2 — 23
2.3.1 Settings 2 — 24
2.3.2 Alarms 2 — 25
2.3.3 Measurements 2 — 26
2.3.3.1 Voltage Measurements 2 — 26
2.3.3.2 Current Measurements 2 — 27
2.3.3.3 Power and
Frequency Measurements 2 — 28
2.3.3.4 Battery Measurements 2 — 29
iii
Contents
section description page number
2.4 . . . . . . . . . . . . . . . Normal Operating Procedures 2 — 29
2.4.1 Checks Before Start-up 2 — 29
2.4.2 Start-up 2 — 30
2.4.3 Checks After Start-up 2 — 31
2.4.4 Shut-down 2 — 32
2.4.4.1 Emergency Shutdown
Using EPO 2 — 32
2.4.4.2 Normal Shutdown 2 — 33
2.4.5 Isolation for Maintenance 2 — 33
2.4.5.1 Isolation of an
Individual UPS Module 2 — 33
2.4.5.2 Isolation of
Static Switch Cabinet (SSC) 2 — 35
2.4.5.2.1 Without Maintenance Bypass 2 — 35
2.4.5.2.2 With Maintenance Bypass 2 — 35
2.4.6 Forced Transfers 2 — 36
2.4.6.1 Uninterrupted
Transfer Conditions 2 — 36
2.4.6.2 Forced Transfer From
Bypass AC Input Source
to Inverter 2 — 37
2.4.6.3 Forced UPS Module Shut Down 2 — 37
2.5 . . . . . . . . . . . . . . . LCD Messages 2 — 37
Section III Maintenance and Service
3.0 . . . . . . . . . . . . . . . Scope 3 — 1
3.1 . . . . . . . . . . . . . . . Safety Instructions 3 — 1
3.2 . . . . . . . . . . . . . . . Preventive Maintenance 3 — 1
3.3 . . . . . . . . . . . . . . . Replacement Parts 3 — 2
3.4 . . . . . . . . . . . . . . . Troubleshooting and
MGE Servicing 3 — 3
Glossary
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . g — 1
iv Contents
EPS 6000 UPS Shared Systems
Illustrations
figure description page number
1-1 . . . . . . . . . . . . . . . Pictorial, Typical EPS 6000 UPS
Shared Installation
(Shown With Two 375 kVA
UPS Modules) 1 — 3
1-2 . . . . . . . . . . . . . . . Single-Line Diagram,
Typical EPS 6000 UPS
Shared Installation 1 — 3
1-3 . . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 150 - 225 kVA
UPS Modules 1 — 5
1-4 . . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 375 kVA UPS Modules 1 — 6
1-5 . . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 500 kVA UPS
I/O Cabinet 1 — 7
1-6 . . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 500 kVA UPS Cabinet 1 — 8
1-7 . . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 750 kVA UPS Cabinet 1 1 — 9
1-8 . . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 750 kVA UPS Cabinet 2 1 — 10
1-9 . . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 750 kVA UPS
Cabinet 3 1 — 11
1-10 . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Static Switch Cabinet (SSC) 1 — 12
2-1 . . . . . . . . . . . . . . . Power Flow, Normal Operation 2 — 1
2-2 . . . . . . . . . . . . . . . Power Flow,
On-Battery Operation 2 — 2
2-3 . . . . . . . . . . . . . . . Power Flow, Bypass Operation 2 — 3
2-4 . . . . . . . . . . . . . . . EPS 6000
Controls and Indicators 2 — 4
2-5 . . . . . . . . . . . . . . . EPS 6000 Front Panel 2 — 4
2-6 . . . . . . . . . . . . . . . Alphanumeric Display
and Controls 2 — 7
2-7 . . . . . . . . . . . . . . . Hidden Panel 2 — 9
2-8 . . . . . . . . . . . . . . . Hidden Panel Pushbuttons 2 — 12
vContents
User’s guide
2-9 . . . . . . . . . . . . . . . Single-Line Diagram,
Typical EPS 6000 UPS
Shared Installation 2 — 14
2-10 . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 150 - 225 kVA
UPS Module 2 — 15
2-11 . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 300 / 375 kVA
UPS Module 2 — 16
2-12 . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 500 kVA UPS Module
I/O Cabinet 2 — 17
2-13 . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 500 kVA UPS Module
UPS Cabinet 2 — 18
2-14 . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 750 kVA UPS Module
UPS Cabinet 1 2 — 19
2-15 . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 750 kVA UPS Module
UPS Cabinet 2 2 — 20
2-16 . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Shared 750 kVA UPS Module
UPS Cabinet 3 2 — 21
2-17 . . . . . . . . . . . . . . EPS 6000
Major Internal Components,
Static Switch Cabinet (SSC) 2 — 22
2-18 . . . . . . . . . . . . . . Alphanumeric Display 2 — 23
2-19 . . . . . . . . . . . . . . General Display Configuration 2 — 24
2-20 . . . . . . . . . . . . . . Display Settings Display 2 — 24
2-21 . . . . . . . . . . . . . . Displaying Alarm Messages 2 — 25
2-22 . . . . . . . . . . . . . . Voltage Measurements 2 — 26
2-23 . . . . . . . . . . . . . . Current Measurements 2 — 27
2-24 . . . . . . . . . . . . . . Power and
Frequency Measurements 2 — 28
2-25 . . . . . . . . . . . . . . Battery Measurements 2 — 29
vi Contents
EPS 6000 UPS Shared Systems
Tables
table description page number
1-1 . . . . . . . . . . . . . . . EPS 6000 Model Numbers,
Shared System UPS Modules 1 — 2
1-2 . . . . . . . . . . . . . . . EPS 6000 Model Numbers,
Static Switch Cabinets (SSC) 1 — 2
viiContents
User’s guide
This manual is designed for ease of use and easy location
of information.
To quickly find the meaning of terms used within the text, look in the Glossary.
This manual uses Noteboxes to convey important information. Noteboxes come in four
varieties:
A WARNING notebox
indicates information
provided to protect the
user and service
personnel against safety
hazards and/or possible
equipment damage
WARNING
A CAUTION notebox
indicates information
provided to protect the
user and service
personnel against
possible equipment
damage.
CAUTION
An IMPORTANT notebox
indicates information
provided as an operating
instruction, or as an
operating tip.
IMPORTANT
A NOTE notebox
indicates information
provided as an
operating tip or an
equipment feature.
NOTE
How to use this manual
viii
EPS 6000 UPS Shared Systems
This manual provides technical information required for
operation and maintenance of the shared EPS 6000
uninterruptible power system (UPS). Please read this manual before operating the EPS 6000
equipment. Please retain this manual for future reference.
The manual is divided into three sections:
Section I — General Description
This section introduces the EPS 6000 family of uninterruptible power systems, including a
general description of the system and its internal components, a description of available
options, and system specifications.
Section II — Operation
This section describes operating information for EPS 6000 UPS shared systems, including
an overview of the system, its components, and their function; a description of the
indicators and controls and their function; and operational sequences to be followed for all
conditions of normal, emergency, and maintenance operation.
Section III — Maintenance and Service
This section describes maintenance of the EPS 6000 UPS, including safety instructions,
preventive maintenance, information about replacement parts, and customer service.
A Glossary in the rear of this manual provides definitions of terms used within the text. A
separate manual, EPS 6000 UPS Installation Manual (MGE part number 86-130035-00)
provides detailed installation instructions.
EPS 6000 is a family of compact, high-efficiency uninter-
ruptible power systems, available in power ratings up to
1,500 kVA. EPS 6000 UPS are optimized for compatibility with non-linear computer-type
loads. Computer-aided UPS diagnostics and modular construction assures that any required
service on the UPS can be identified and completed rapidly. Remote system monitoring,
remote annunciation of UPS performance signals, and telecommunication capabilities allow
total control of the UPS by the user.
The EPS 6000 UPS, SSC, battery, and all auxiliary equipment is listed for safety by
Underwriter’s Laboratories, Inc. (UL) under UL Standard 1778; and under
Canadian Standards Association (CSA) standard C22.107.
Major components of the EPS 6000 UPS family include:
EPS 6000 UPS module
EPS 6000 SSC static switch cabinet
EPS 6000 SSC maintenance bypass cabinet
EPS 6000 auxiliary cabinet
1.1 General Description
1.0 Scope
1 — 1
Introduction
EPS 6000 battery cabinet
Each of these cabinets is described below. Figure 1-1 shows a typical shared UPS
installation, consisting of one static switch cabinet (SSC), two UPS modules, and two adjacent
battery cabinets. Figure 1-2 shows a single-line diagram of the same
shared UPS installation. Table 1-1 identifies EPS 6000 UPS model numbers for modules
used in shared systems, and Table 1-2 identifies EPS 6000 SSC model numbers.
Table EPS 6000 Model Numbers, Shared System UPS Modules
1-1
Table
EPS 6000 Model Numbers, Static Switch Cabinets (SSC)
1-2
LEDOM
REBMUN
TUPNI
EGATLOV
)CAV(
TUPTUO
EGATLOV
)CAV(
TUPTUO
GNITAR
Wk/AVk
BCTUPNI
)serepmA(
LATOT
HTDIW
)ni/mm(
LATOT
THGIEW
)bl/gk(
TAEH
SSOL
)rh/utB(
0051CSS0840840021/0051000227/92810092/7131)elbigilgeN(
LEDOM
REBMUN
TUPNI
EGATLOV
)CAV(
TUPTUO
EGATLOV
)CAV(
TUPTUO
GNITAR
)Wk/AVk(
BCTUPNI
)spmA(
HTDIWLATOT
)ni/mm(
LATOT
THGIEW )bl/gk(
TAEH
SSOL
)rh/utB(
P66,44/0516-SPE084084021/0510045.18/010,2805,4/440,2818,03
P66,44/5226-SPE084084081/5220045.18/010,2805,4/440,2202,93
-SPEP66,44/0036084084042/0030065.18/010,2345,5/415,2962,25
P66,44/5736-SPE084084003/5730075.18/010,2216,5/545,2633,56
P66,44/0056-SPE084084004/0050001311/568,2112,7/442,4354,97
6-SPEP66,44/057084084006/0570061591/009,42,31/000,600,131000
:SETON
.1 .stellapgnidulcxetubstenibacyrailixuagnidulcnipu-enilmetsysroferassoltaehdna,thgiew,htdiwlatoT
.2 .tnempiuqeruoyhtiwdeilppussgniwardnoitallatsniehtotrefer;atadyrettabedulcnitonseodataD
.3 ehttlusnoC.tnempiuqelanoitpohtiwegnahcyamatad;snoitarugifnocdradnatsrofsidedivorpnoitamrofnI
.tnempiuqeruoyhtiwdedivorpsgniwardnoitallatsni
1 — 2 Introduction
EPS 6000 UPS Shared Systems
Figure Pictorial, Typical EPS 6000 UPS Shared Installation
1-1 (Shown With Two 375 kVA UPS Modules)
Figure Single-Line Diagram, Typical EPS 6000 UPS Shared Installation
1-2
TO
ATTACHED
LOAD
MAIN
AC INPUT/
MAINS 1
QF1
OUTPUT
FUSES
EPS 6000 UPS MODULE
EPS 6000
BATTERY
CABINET
K3N
Q1
INVERTER
RECTIFIER/
CHARGER
INPUT
FUSES
Q5N
STATIC SWITCH
QF1
OUTPUT
FUSES
EPS 6000
BATTERY
CABINET
INVERTER
RECTIFIER/
CHARGER
INPUT
FUSES
STATIC SWITCH
EPS 6000 UPS MODULE
MAINTENANCE
BYPASS CABINET
STATIC SWITCH
Q2S
STATIC SWITCH
CABINET
Q38P
Q5N
Q5N
K3N
Q1
MAINTENANCE
BYPASS
AC INPUT
(OPTIONAL)
Q4S
(CUSTOMER
SUPPLIED)
FROM ADDITIONAL
UPS MODULES
BYPASS
AC INPUT/
MAINS 2
STATIC SWITCH
CABINET (SSC)
MAINTENANCE
BYPASS
CABINET
(OPTIONAL)
AUXILIARY
CABINET
EPS 6000
UPS MODULE
BATTERY
CABINET
1 — 3Introduction
User’s guide
Following is a description of the EPS 6000 UPS major
internal components. Refer to the single-line diagram
provided in Figure 1-2, and the component locators
provided in Figure 1-3 through Figure 1-10
The rectifier/battery charger converts the AC input voltage
from the utility source into a DC voltage, supplying the
inverter and regulating the charge of the battery system. A
capacitor bank filters the DC voltage.
The inverter chops the DC voltage supplied from either the
rectifier/battery charger or the battery system into a three-
phase AC voltage. An AC output filter is used to achieve a computer-grade sinewave output
voltage waveform, with a total harmonic distortion of less than 2% under linear-load conditions.
During normal operation, the inverter transformer provides
complete electrical isolation between the UPS output to the
attached load and the utility power source input as well as
the UPS battery source.
The battery system stores energy for use by the inverter.
The stored energy is utilized in the event that the AC input
power from the utility source fails, or falls outside of acceptable tolerance.
The battery system may be an MGE battery cabinet designed for operation with the EPS 6000
UPS, or a customer-supplied battery installation.
MGE-supplied EPS 6000 battery cabinets may be a provided as stand-alone enclosures, or as
enclosures designed to be mounted adjacent to the EPS 6000 UPS module.
The EPS 6000 comes with a special battery ambient temperature sensor which allows the
optimization of the DC voltage level as a function of the temperature, ensuring that the battery
is properly charged and preserving its longevity.
1.2.4 Battery System
1.2.3 Inverter
Transformer
1.2.2 Inverter
1.2.1 Rectifier/Battery
Charger
1.2 Description of UPS
Module Major
Internal
Components
1 — 4 Introduction
EPS 6000 UPS Shared Systems
The static switch cabinet (SSC) provides an electrical path
between the output of the UPS modules and the load.
When the UPS modules are off, the SSC provides power to
the load from the bypass AC input source (mains 2). Up to
six (6) modules can be connected to the SSC, supporting
loads as great as 1,500 kVA. UPS modules may be turned
off individually for maintenance, provided that the remaining modules can support the load.
The SSC incorporates a static bypass switch. A wrap-around circuit breaker (Q2S) in the SSC
switches between the UPS module output and the bypass AC input source (when the UPS
modules are off). Optionally, the SSC can be provided with its own maintenance bypass
cabinet (MBC), allowing the SSC and/or any attached UPS module to be serviced while the
load is supplied via the maintenance bypass AC input source.
Figure EPS 6000 Major Internal Components,
1-3 Shared 150 - 225 kVA UPS Modules
FRONT VIEW, DOORS AND COVERS REMOVED
TOP VIEW, COVER REMOVED
INVERTERS
OUTPUT
CIRCUIT BREAKER
NEUTRAL CONNECTION
(BEHIND OUTPUT)
OUTPUT XFMR
(BEHIND BREAKERS)
RAUZ PCA
DC CAPACITORS
OUTPUT FUSES F7, F8, F9
120V AC OUTLET
(FOR MGE USE ONLY)
(BEHIND EACH INVERTER)
OBEZ PCA
IBEZ PCA
FAN
TRANSFORMER
FB9
1- GTCZ PCA
2- SRIZ PCA
3- CRIZ PCA
4- CROZ / DO6Z PCA
5- AROZ PCA
6- ALEZ PCA
CARD CAGE:
ALBZ
CHARGER, STATIC SW,
INPUT
CONNECTIONS
GROUND
CONNECTIONS
BATTERY
CONNECTIONS
OUTPUT
CONNECTIONS
K3N
1
C3B3A3
BAIZ & TREZ
(BEHIND PLATE)
EPOZ
INPUT FUSES F1, F2, F3
FUSES F16, F17
F18, F19
FB1 TO FB8
F10,F11 RATED 2A,500VDC
F12,F13
AC CAPACITOR
ASSEMBLY
FANS
(x 6)
6543
1 2
FB4
FB3
FB2FB1
FB8
FB7
FB6FB5
C4B4A4
+
2
3
4
5
6
INVERTER FUSES (BEHIND)
Q1 Q5N
ARUZ PCA (BEHIND MTG. PLATE)
ACPZ PCA
APOZ PCA
K3NZ PCA
1.3 Description of SSC
Major Internal
Components
1 — 5Introduction
User’s guide
Figure EPS 6000 Major Internal Components,
1-4 Shared 375 kVA UPS Modules
FRONT VIEW, DOORS AND COVERS REMOVED
TOP VIEW, COVER REMOVED
INVERTERS (x6)
OUTPUT
CIRCUIT BREAKER
NEUTRAL CONNECTION
(BEHIND OUTPUT)
OUTPUT XFMR
(BEHIND BREAKERS)
RAUZ PCA
DC CAPACITORS
OUTPUT FUSES F7, F8, F9
120V AC OUTLET
(FOR MGE USE ONLY)
(BEHIND EACH INVERTER)
OBEZ PCA
IBEZ PCA
FAN
TRANSFORMER
FB9
1- GTCZ PCA
2- SRIZ PCA
3- CRIZ PCA
4- CROZ / DO6Z PCA
5- AROZ PCA
6- ALEZ PCA
CARD CAGE:
ALBZ
CHARGER, STATIC SW,
INPUT
CONNECTIONS
GROUND
CONNECTIONS
BATTERY
CONNECTIONS
OUTPUT
CONNECTIONS
K3N
1
C3B3A3
BAIZ & TREZ
(BEHIND PLATE)
EPOZ
INPUT FUSES F1, F2, F3
FUSES F16, F17
F18, F19
FB1 TO FB8
F10,F11 RATED 2A,500VDC
F12,F13
AC CAPACITOR
ASSEMBLY
FANS
(x 6)
6
6
5
43
21
543
1 2
FB4
FB3
FB2FB1
FB8
FB7
FB6FB5
C4B4A4
+
2
3
4
5
6
INVERTER FUSES (BEHIND)
F23 TO F34
Q1 Q5N
ARUZ PCA (BEHIND MTG. PLATE)
ACPZ PCA
APOZ PCA
K3NZ PCA
1 — 6 Introduction
EPS 6000 UPS Shared Systems
Figure EPS 6000 Major Internal Components,
1-5 Shared 500 kVA UPS I/O Cabinet
Q1
A3 B3 C3
INPUT
CONNECTIONS
A4 B4 C4
OUTPUT
CONNECTIONS
BATTERY
CONNECTIONS
FRONT VIEW, DOORS AND COVERS REMOVED
TOP VIEW, COVERS REMOVED
A12B12 C12
C1B1A1
GROUND CONNECTION
BONDING
JUMPER
SHUNT
L2
CURRENT XFMRS
ACPZ
L4
ARUZ
AC CAPACITORS
NEUTRAL CONNECTION
GROUND
CONNECTION
NEUTRAL
CONNECTION
INPUT FUSES
F1,F2,F3
FUSES F16,F17
L3
Q5N
A2
N12
C2
B2
1 — 7Introduction
User’s guide
Figure EPS 6000 Major Internal Components,
1-6 Shared 500 kVA UPS Cabinet
FRONT VIEW, DOORS AND COVERS REMOVED
TOP VIEW, COVER REMOVED
AC CAP ASSY.
K1
BATTERY
CONNECTION
(OPTIONAL)
F10,F11,F18,F19
F12,F13
DELAY
ALBZ
APOZ
INVERTERS (x6)
DC CAPACITERS
(BEHIND EACH INVERTER
)
RAUZ
OBEZ
IBEZ
FAN
TRANSFORMER
OUTPUT FUSES
F7, F8, F9
K3N
STATIC SWITCH
K3NZ
1- GTCZ PCA
2- SRIZ PCA
3- CRIZ PCA
4- CROZ / DO6Z PCA
5- AROZ PCA
6- ALEZ PCA
CARD CAGE:
AC OUTPUT
CAPACITORS
CHARGER & TREZ
(BEHIND PLATE)
EPOZ
FB1 TO FB8
AC CAPACITOR
ASSEMBLY
FANS
(x 8)
6
6
5
NEUTRAL
4321
123456
543
7 8
1 2
1 — 8 Introduction
EPS 6000 UPS Shared Systems
Figure EPS 6000 Major Internal Components,
1-7 Shared 750 kVA UPS Cabinet 1
Ground
C
apacitors
C
onnection
Power
Interconnect
CT (6ea)
ACPZ
ARUZ
Fuses
Relay
Battery
Connections
Output
Connections
Q5N
(optional)
Input
Connections
Bonding
jumper
Shunt
CT (4ea)
Induction Filter
(2 ea) one on
other side
AC capacitors
(2ea) one on
other side
Induction filter
(2ea) one on
other side
Cooling fans
(2ea)
BAIZ
Input fuses
F1, F2, F3
Input Filter
Capacitors
Resistors
Neutral
Connection
Choke
Ground
Connection
( - )
( + )
Front view, doors, cover and some components removed for clarity.
Static Switch
Q1
A3 B3 C3
A4 B4 C4
(+) (-)
Side View
Top view
1 — 9Introduction
User’s guide
Figure EPS 6000 Major Internal Components,
1-8 Shared 750 kVA UPS Cabinet 2
FRONT VIEW, DOORS AND COVERS REMOVED
TOP VIEW, COVER REMOVED
INVERTERS (x6)
AC OUTPUT
CAPACITORS
ALBZ
K3N
K3NZ
DC CAPACITORS
(BEHIND EACH INVERTER)
FAN
TRANSFORMER
FB9
OUTPUT FUSES
FB1 TO FB8
AC CAPACITOR
ASSEMBLY
FANS
(x 8)
6
6
5
43
21
543
7 8
1 2
FB4
FB3
FB2FB1
FB8
FB7
FB6FB5
INVERTER FUSES (BEHIND)
F24,F26,F28,F30,F32,F34
F10,F11
STATIC SWITCH
NEUTRAL
1 — 10 Introduction
EPS 6000 UPS Shared Systems
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84