3.1 Mounting
Mounting and setup must be carried out according to the applicable installation standards
(e.g. IEC 60079-14 or GB/T 3836.15) by qualified personnel trained in explosion protection.
The information given in the manual and the supplementary instructions must always be observed.
Variable area flowmeters must be installed in such a way that
•
there is no danger from mechanical impact effects.
•
there are no external forces affecting the indicator part.
•
the device is accessible for any necessary visual inspections and can be viewed from all sides.
•
the nameplate is clearly visible.
•
it can be operated from a location with secure footing.
3.2 Special conditions and requirements
Electrostatic charge
Friction on the surface with coating should be avoid in case there will cause the ignition by
electrostatic accumulation.
Special requirements
•
Only be connected to the certified associated apparatus, the flowmeter could be used in the explosive
atmosphere. The connection should be complied whith the requirements of the manual of the
associated apparatus. The maximum values for connection to a certified associated apparatus are
shown in the section "Electrical data".
•
The cable between the product and associated apparatus should be shielded cable with insulating
sheath. and the shield be grounded.
•
The enclosure shall be kept from the dust, but the dust shall not be blown by compressed air.
•
Users are forbidden to change the configuration to ensure the explosion protection performance of the
equipment. Any faults shall be settled with experts from the manufacturer.
•
During installation, operation and maintenance, users shall comply with the relevant requirements of
the product instruction manual,
GB3836.13-2013 "Explosive atmospheres - Part 13: Equipment repair, overhaul and reclamation",
GB/T 3836.15-2017 "Explosive atmospheres - part 15: Electrical installations design, selection and
erection",
GB/T 3836.16-2017 "Explosive atmospheres - part 16: Electrical installations inspection and
maintenance",
GB/T 3836.18-2017 "Explosive atmospheres - part 18:: lntrinsically safe electrical systems",
GB 15577-2018 "Safety regulations for dust explosion prevention and protection" and
GB50257-2014 "Code for construction and acceptance of electric device for explosive atmospheres and
fire hazard electrical equipment installation engineering".
CAUTION!
The manufacturer is not liable for any damage resulting from improper use or use other than the
intended purpose. This applies in particular to hazards due to insufficient corrosion resistance
and suitability of the materials in contact with product.
DANGER!
Components made of titanium in oxygen applications
Components made of titanium in oxygen applicationsComponents made of titanium in oxygen applications
Components made of titanium in oxygen applications
Variable area flowmeters with titanium components are NOT
NOTNOT
NOT suitable for use in explosion-
protected areas in conjunction with oxygen applications (products with an oxygen content which
is significantly above the oxygen content in the earth's atmosphere)!