Hardy HI1769 Installation guide

Type
Installation guide
Hardy Process Solutions • 9440 Carroll Park Drive, Ste. 150 • San Diego, CA 92121-5201
Tel 858.278.2900 • Fax 858.278.6700 • www.hardysolutions.com[email protected]
GuidelinesforInstallingHI1769WS&‐2WSFaceplates
ATTENTION:Faceplates provided by Hardy Process Solutions are open source, unlocked, HMI
templates that may be downloaded from the Hardy website for free. All open source software, code
and scripts are provided as-is and Hardy does not warranty or provide any technical support for open
source software, code or scripts. As such, Hardy assumes no liability for potential harm or damage,
software or hardware, which may result from the use of open source software, code or scripts.
Furthermore, Hardy assumes no responsibility for their content or operation in any particular
environment.Software, code and scripts are provided as examples only and will likely need to be
modified for your particular use.
For further technical support installing, using, or modifying Faceplates; contact your nearest Rockwell
Automation Technical Support Center.
Importing add on instructions (AOI) into RSLogix® 5000: Page 2
SE Edition Instructions: Page 4
ME Edition Instructions: Page 9
2
Importing and configuring the AOI
ImportingAddOnInstructions(AOI)intoRSLogix®5000
Rightclick“AddOnInstructions”andImportthedownloaded
faceplate L5X file into your
project. For the HI 1769-WS & -2WS modules, there are two AOI instructions, one for Integer
configuration and one for Floating point configuration. Import the one or both as needed.
It should now appear under Add-On Instructions.
AddtheHI1769WS/2WSmoduletotheconfiguration.RightclickandclickonNewModuleto
addtheHI1769WSor2WStotheI/Oconfigurationstructure.
o AddtheAddOnInstructionontoarung.
3
o Createtheinstructiontags.ThiswillbeanAddOndatatypethatmatchestheAddon
instruction.
o Inp_hi1769:AssociatethislabelwiththeInputtableforthedesiredHI1769channel.
Clickanddropdownthelistandselect“AllTags”toshowalistofallcontrollertags.
o ScrolldownandfindtheHI1769moduleandexpandtomakeselectionofthechannel
desired.
4
o Out_hi1769:AssociatethislabelwiththeOutputtableforthedesiredHI1769channel.
Clickanddropdownthelistandselect“AllTags”toshowalistofall.Scrolldownand
findtheHI1769moduleandexpandtomakeselectionofchanneldesired.
AddadditionalAOIinstructionsintothemainroutineforeachHI1769module/channel.
SaveyourprojectanddownloadittothePLC.
SE Edition of the Faceplate
ImportingHardyFaceplatesintoFactoryTalk™ViewSE
OpenFactoryTalkStudioViewSiteEdition
Createanewapplication.
AddcommunicationinFactoryTalktocreatealinkbetweenFactoryTalkandRSLogix5000
Rightclickontheprojectnameintheexplorernavigationbar.
AddanewRockwellAutomationDeviceServer
Add,nameandchooseapathtoyourcontroller.
ClickApplyandOKtocreatetheshortcut.
Whencomplete,thisprocesswilllinkthetagsfromtheAOIinRSlogixtothetagsinFactoryTalk.
5
ImporttheFaceplatefileintoFactoryTalkasaGlobalObject
o RightclickonGlobalObjectsandclickon‘AddComponentintoApplication’,lookforthe
faceplatefiles(HI1769_SE_Single_Ch.ggfxandDefaultSelection.ggfx)toaddthemunder
globalobjects.

o IfmultipleHI1769modulesareused,makecopiesoftheHI1769_SE_Single_Ch.ggfxfiles
andassigndifferentnamesforeachinstrument.
o GlobalobjectscanbemodifiedallowingcustomizationoftheFaceplatetomeetspecific
userrequirements;forexample,ifonlyaweightreadingisrequired,ausercangrabthe
objectandmoveittoanothercustomdisplaythathasalreadybeencreated.
o Savechangesofanymodificationsbeforeexitingtheprogram.
Toaddfaceplatestoadisplay,rightclickonDisplays,andthenclickon‘AddComponentinto
Application’.
IfnochangesweremadetotheGlobalObjectfiles,addthesametwofilesintotheDisplay
section.IfchangesweremadetoGlobalObjectfiles,savebeforeaddingtotheDisplay
section.ChangedfilestoaddtotheDisplaysectionshouldbefoundinthedirectorywhere
saved(Typicallyc:/users/public/PublicDocuments/RSViewEnterprise/SE/HMI
Projects/<projectname>/GlobalObjects)
IfusingtheDefaultSelectiondisplayfile,changesshouldbemadetothebuttonpropertiesto
ensuretheypointtotheproperunits.
Doubleclicktoopenthe“DefaultSelection”GlobalObject.
RightclickontheHI1769buttontosetup,clickonproperties.Underthe“Action”tab,under
the“pressaction”textbox,deleteanyofthecontents.
6
Clickonthetotherightofthe“pressaction”box.GototheAllCommandsandMacros,scroll
downto“Display”.DoubleclickonDisplay.SelectthefilenameofyourHI1769faceplate.
Checkthe/TParameterstagscheckbox,Clickonthetotheright.
SelectthetagsfromthecorrectAOIunderthe“selectTags>Folder”list.(Foldersmayneedto
berefreshed).ClickOKandFinishtoclosethewindows.
Save.
Delete the Default Selection Display and add the newly saved display.
Rightclickanddeletethe“DefaultSelection”displayundertheDisplaysection.
Rightclick“Displays”andaddthe“DefaultSelection”filefoundundertheC:/Users/Public/Public
Documents/RSViewEnterprise/SE/HMIProjects/<projectname>/GlobalObjectsdirectory.
7
CreateaFactoryTalkViewSiteEdition
OpenFactoryTalkViewSiteEditionClientapplication
Createanewproject.
SelectLocalStation.
UnderNameofApplication,youwanttoconnecttoselecttheapplicationyou
createdintheprevioussection.
SelecttheInitialDisplaytobe“DefaultSelection”andclicknext.
Clicknext,next,thenfinish.
Projectwillnowstartupandthefaceplateshouldcomeupinatest
environment.
NavigatingtheFaceplate
o NavigatetheFaceplateusingthemouseandkeyboardtoentervalues.

8



Figures716
9
MEEditionoftheFaceplate
ImportingHardyFaceplatesintoFactoryTalkViewME
OpenFactoryTalkStudio.SelectMachineEdition
Createanewapplication.
AddcommunicationinFactoryTalktocreatealinkbetweenFactoryTalkandRSLogix5000
o RSLinxEnterprisealreadyappearsintheprojecttree.Expandanddoubleclickonthe
“communicationsetup”.
o Underdeviceshortcuts,addanewshortcut.
o InthePRIMARYwindowexpandthedriver,highlighttheprocessorandclickokthenyes
toapplychanges.Figure19.
o Whencomplete,thisprocesswilllinkthetagsfromtheAOIinRSlogixtothetagsin
FactoryTalk.
Importing the Faceplate Global Object
ImporttheFaceplatefileintoFactoryTalkasaGlobalObject
o RightclickonGlobalObjectsandclickon‘AddComponentintoApplication’,lookforthe
faceplatefileHI1769_ME_Single_Ch.ggfxtoaddunderglobalobjects.IfmultipleHI
1769instrumentsareused,makecopiesofthefileandassigndifferentnamesforeach
instrument.
o GlobalobjectscanbemodifiedallowingcustomizationoftheFaceplatetomeetspecific
userrequirements;forexampleifonlyaweightreadingisrequired,ausercangrabthe
objectandmoveittoanothercustomdisplaythathasalreadybeencreated.
o Savechangesofanymodificationsbeforeexitingtheprogram.
10
o IfnochangesweremadetotheGlobalObjectfiles,addthesamefileintotheDisplay
section.IfchangesweremadetoGlobalObjectfiles,savebeforeaddingtotheDisplay
section.ChangedfilestoaddtotheDisplaysectionshouldbefoundinthedirectory
wheresaved(typicallyc:/users/public/PublicDocuments/RSViewEnterprise/ME/HMI
Projects/<projectname>/GlobalObjects.
o Userswillneedtoadda“GOTODisplaybutton”
Inthepropertiesboxforthebutton,set:
DisplayfieldtotheHardydisplay.
ParameterLISTsettotheLogixAOIfolder.


11



Copyright©2020HardyProcessSolutions.AllRightsReserved.PN:17690596034601,revC 
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11