PLUS+1 Compliant JS7000 Y-Axis Joystick Function Block
User Manual
JS7000_Y Function Block
L1123424
·
Rev AA
·
May 2011
9
JS7000_Y Function Block Configuration Values
Input Type Range Description
LatchInFlt BOOL —— The function block sets a Fault condition when it receives an invalid input.
The block disables the Out signal that is related to the abnormal input.
The LatchInFlt (Latch Input Fault) sets when the block enables the signal after the condition clears.
T—The block enables the Out signal only after you repower the controller.
F—The block immediately enables the Out signal.
CalWindow —— 0–3000 The CalWindow (Calibration Window) sets the width of three calibration windows.
These windows center on the default CalHi, CalMid, and CalLow calibration values.
For more information, see About Calibration Windows and Default Calibration Values
on page 11.
The default calibration values are set in the Memory page. They are the Default inputs to the three Non-Volatile
Memory Dynamic with Default components in this page.
During autocalibration, input voltages must be within these windows for the function block to capture them as
valid calibration values.
The CalWindow value is set as percentage of SnsrPwr.
1000 = 10%
CalDetectTm —— 0–65535 The CalDetectTm (Calibration Detect Time) sets the time during autocalibration that input voltages must remain
in each calibration window for the function block to capture them as valid CalHi, CalMid, and CalLow calibration
values.
1000 = 1 s
Dband_Hi —— 0–4999 The Dband_Hi (Deadband High) sets the width of an upper deadband.
An input voltage within this band produces a +100% output.
This deadband extends below the CalHi calibration value.
The function block sets the width of the Dband_Hi as a percentage of the difference between the CalHi and
CalMid calibration values.
For more information, see About Calibration Values and Deadbands
on page 13.
1000 =10%
Dband_Mid —— 0–4999 The Dband_Mid (Deadband Middle) sets the width of a middle deadband.
An input voltage within this band produces a 0% output.
This deadband has an upper and lower half. The upper half extends above the CalMid calibration value. The
lower half extends below the CalMid calibration value.
The function block sets the width of the upper half of Dband Mid as a percentage of the difference between the
CalHi and CalMid calibration values.
The function block sets the width of the lower half of Dband Mid as a percentage of the difference between the
CalMid and CalLow calibration values.
For more information, see About Calibration Values and Deadbands
on page 13.
1000 =10%