Vertiv Liebert ITA2 Installation guide

Category
Uninterruptible power supplies (UPSs)
Type
Installation guide

Vertiv Liebert ITA2 is a battery cabinet that can be used to extend the battery life of your Liebert ITA2 UPS. The battery cabinet is designed to be used with 8-10kVA, 60Hz, 208/220V UPS systems. It can accommodate up to 12 batteries, which can provide up to 10 minutes of runtime at full load. The battery cabinet is also equipped with a battery management system that monitors the status of the batteries and provides alarms in the event of a problem.

Here are some of the benefits of using a Vertiv Liebert ITA2 battery cabinet:

  • Extended battery life: The battery cabinet can extend the battery life of your UPS by up to 10 minutes, giving you more time to safely shut down your equipment in the event of a power outage.

Vertiv Liebert ITA2 is a battery cabinet that can be used to extend the battery life of your Liebert ITA2 UPS. The battery cabinet is designed to be used with 8-10kVA, 60Hz, 208/220V UPS systems. It can accommodate up to 12 batteries, which can provide up to 10 minutes of runtime at full load. The battery cabinet is also equipped with a battery management system that monitors the status of the batteries and provides alarms in the event of a problem.

Here are some of the benefits of using a Vertiv Liebert ITA2 battery cabinet:

  • Extended battery life: The battery cabinet can extend the battery life of your UPS by up to 10 minutes, giving you more time to safely shut down your equipment in the event of a power outage.
Liebert® ITA2Battery Cabinet 8-10kVA, 60Hz,
208/220V
Installation Manual
Contacting Vertiv for Support
To contact Vertiv Services for information or repair service in the United States, call 800-543-2378. Vertiv
Services offers a complete range of startup services, repair services, preventive maintenance plans and service
contracts.
For repair or maintenance service outside the 48 contiguous United States, contact Vertiv Services, if available in
your area.
For Vertiv Services to assist you promptly, have the following information available:
Part Numbers:
Serial Numbers:
Rating:
Date Purchased:
Date Installed:
Location:
Battery Voltage:
Battery Reserve Time:
Vertiv |Liebert
® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | i
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.0 INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Rear Panel Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1.1 Environmental Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.1 Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Unpacking and Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Attaching and Removing the Bezel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Mechanical Installation—Tower. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.5 Mechanical Installation—Rack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Connecting One Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.6.1 Installing Battery Insulating Plates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.6.2 Installing the Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6.3 Connecting Battery Cabinet Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.7 Connecting Additional Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
FIGURES
Figure 1 Liebert ITA2 Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Figure 2 Rear panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Figure 3 Attaching the bezel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 4 Installing support bases with support base extension. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Figure 5 Tower installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Figure 6 Attach the brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 7 Install the battery cabinet in the rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 8 Standard rack installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Figure 9 Battery insulating plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Figure 10 Cables between Liebert ITA2 and battery cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Figure 11 Cable the UPS to two battery strings in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 12 Battery extension cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
TABLES
Table 1 Environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Table 2 Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Vertiv |Liebert
® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | ii
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 1
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your Liebert ITA2
Battery Cabinet. Read this manual thoroughly, paying special attention to the sections that apply to your
installation, before working with the UPS. Retain this manual for use by installing personnel.
WARNING
Risk of electrical shock. Can cause personal injury and death.
Special safety precautions are required for procedures involving handling, installation and maintenance of
the UPS system. Only properly trained and qualified personnel wearing appropriate personal protective
equipment should be involved in installing the Liebert ITA2 battery system or preparing the system for
installation.
Special care must be taken when working with the batteries associated with this equipment. When
connected together, the battery terminal voltage is potentially lethal. Be constantly aware that the battery
system contains high DC as well as AC voltages. Check for voltage with AC and DC voltmeters before
making contact.
Observe all DC safety precautions before working on or near the DC system.
Follow all battery safety precautions when installing, charging or servicing batteries. In addition to the
hazard of electric shock, gas produced by batteries can be explosive, and sulfuric acid can cause severe
burns.
The following precautions must be observed when working on batteries:
Remove watches, rings and other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source prior to connecting or disconnecting battery terminals.
Determine whether the battery is grounded. If it is grounded, remove source of ground. Contact
with any part of a grounded battery can result in electrical shock. The likelihood of such shock will
be reduced if such grounds are removed during installation and maintenance.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container
resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately with water.
WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment damage,
personal injury and death.
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and recycled or
discarded in accordance with federal, state and local regulations. Because lead is a toxic substance, lead-
acid batteries must be recycled rather than discarded.
Do not dispose of a battery in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 2
NOTICE
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits
provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and
radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause
harmful interference to radio communications. Operation of this unit in a residential area may cause harmful interference
that the user must correct at his own expense.
WARNING
Risk of electric shock. Can cause personal injury and death.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved
for use in fighting electrical fires.
WARNING
Risk of heavy unit falling over. Can cause equipment damage, injury and death.
Exercise extreme care when handling battery cabinets to avoid equipment damage or injury to personnel.
The battery system cabinets weigh approximately 112 lb. (51kg).
Locate the center of gravity symbols and determine unit weight before handling each cabinet. Test
lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
WARNING
Risk of electric shock. Can cause equipment damage, personal injury and death.
The area around the battery system must be kept free of puddles of water, excess moisture and debris.
Observe all precautions in the relevant operation and maintenance manual before as well as during all
installation and maintenance procedures. Observe all battery safety precautions before working on or
near the battery.
This equipment contains several circuits that are energized with high voltage. Only test equipment
designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with
an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is
turned Off, dangerously high potential electric charges may exist at the capacitor banks and at the
batteries.
All power and control wiring must be installed by a properly trained and qualified electrician. All power
and control wiring must comply with the NEC and applicable local codes.
When performing maintenance with any part of the equipment under power, service personnel and test
equipment must be standing on rubber mats. The service personnel must wear insulating shoes for
isolation from direct contact with the floor (earth ground).
One person should never work alone, even if all power is disconnected from the equipment. A second
person should be standing by to assist and to summon help in case of an accident.
NOTE
Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or IEC 60601-1 is
required). Medical applications such as invasive procedures and electrical life support equipment are subject to
additional terms and conditions.
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 3
1.0 INTRODUCTION
The Liebert ITA2 Battery Cabinet (ITA2-BCI0020K03) provides DC input power the Liebert ITA2 UPS. Read this
manual carefully before installing or operating the battery system.
The battery cabinet may be installed either in a rack or in a tower configuration. A maximum of five battery
strings can be connected to a Liebert ITA2 UPS.
Figure 1 Liebert ITA2 Battery Cabinet
1.1 Rear Panel Features
There are two battery ports and a battery output breaker on the rear of each battery cabinet, see Figure 2. Two
RJ-45 communication ports on the back of each battery cabinet permit communication with the Liebert ITA2
UPS.
Figure 2 Rear panel
1.1.1 Environmental Conditions
Table 1 lists the environmental conditions of the installation area.
1. Battery Port A 2. Battery Output Breaker 3. Battery Port B 4. RJ-45 Communication Port, 2
Table 1 Environmental conditions
Environmental Conditions Range
Operating Temperature, °F (°C) 32~122 (0 ~ 50)
Storage Temperature, °F (°C) -13 ~ 122) (-25 ~ 50)
Relative Humidity 5%RH ~ 95%RH (non-condensing)
Altitude, ft. (m) 9800 (3000), no derating
12
3
4
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 4
2.0 INSTALLATION
2.1 Preparation
2.1.1 Installation Environment
The Liebert ITA2 Battery Cabinet must be installed in an environment meeting the following requirements:
• Well-ventilated
No direct sunlight on the system
Free from water, heat source and flammable and explosive substances
Free from dust, volatile gases and corrosive materials
Tools Required
Phillips screwdriver: install the rack rails
Flat-blade screwdriver, install the extension cable
2.2 Unpacking and Inspection
1. Unpack the battery cabinet and inspect its appearance. If any damage is found, notify the carrier immediately and report it
to your Vertiv representative.
2. Check against the delivery list to ensure that the items delivered match the order.
2.3 Attaching and Removing the Bezel
To attach the battery cabinets plastic bezel:
1. Obtain the bezel from the accessories package.
2. Align the bezel with the front panel of the battery cabinet as shown in Figure 3.
3. Press the fittings on both sides of the bezel into the rectangular holes on the battery cabinet.
Figure 3 Attaching the bezel
To remove the bezel, press the two concave surfaces of the bezel, and pull it away from the cabinet.
1. Battery
Cabinet
2. Rectangular Hole 3. Bezel
2
1
3
2
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 5
2.4 Mechanical Installation—Tower
1. Obtain the support base and extensions from the UPS accessories package.
2. Assemble the support bases and the support base extensions as shown in Figure 4. Four support bases are required for a
UPS.
Figure 4 Installing support bases with support base extension
3. Place the battery cabinets and the UPS on the support bases, as shown in Figure 5.
Figure 5 Tower installation
4. Attach the bezel to each battery cabinet, see 2.3 - Attaching and Removing the Bezel.
1. Support Base 2. Support Base Extensions 3. Connectors
1. Liebert ITA2 UPS 2. Liebert ITA2 Battery Cabinets, 4 3. Support Base
1
1
2
3
1
2
3
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 6
2.5 Mechanical Installation—Rack
NOTICE
Risk of improper transport. Can cause damage to the UPS or battery cabinets.
Never attempt to lift or move the Liebert ITA2 or battery cabinets with the rack brackets. The brackets and screws are not
designed to be used to lift the units.
NOTICE
Risk of improper installation. Can make rack top-heavy and cause a tipping hazard.
The battery cabinets are heavier than the Liebert ITA2 UPS. Vertiv recommends installing the battery cabinets as near the
bottom of the rack as possible to maintain a low center of gravity. Install the UPS above the battery cabinets as shown in
Figure 8.
Each battery cabinet must be installed on its own set of rack-mount rails because the rail kit is not designed to support the
weight of more than one battery cabinet.
1. Install the guide rails, refer to Liebert ITA2 8~10kVA UPS user manual, SL-00030, which shipped with the UPS and is
available at Vertiv’s Web site: www.vertivco.com
2. Take out the brackets and M4 × 10 screws from the accessories, and attach the brackets to the battery cabinet, one on
each front corner of the cabinet, as shown in Figure 6.
Figure 6 Attach the brackets
3. Place the battery cabinet on the guide rails and push it completely into the rack along the guide rails.
4. Use M5 × 16 screws to attach the battery cabinet to the rack, as shown in Figure 7.
Figure 7 Install the battery cabinet in the rack
1. Rack 2. Battery Cabinet 3. Bracket, 2 4. Screws, 4 per Bracket 5. Guide Rail, 1 per Side
1
1
2
3
1. Screws, 8
2. Brackets, 2
3. Liebert ITA2 Battery Cabinet
3
1
2
45
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 7
Figure 8 Standard rack installation
2.6 Connecting One Battery Cabinet
Do not reverse the polarity of the battery cables.
Before replacing the battery cabinet and connecting the battery cables, ensure the battery breaker on the rear of
the battery cabinet is open (Off).
2.6.1 Installing Battery Insulating Plates
The battery terminals need insulating plates to guarantee the sufficient insulation distance between the battery
external cables connection to protect against faults such as arcing and short circuits.
Figure 9 Battery insulating plate
To install the insulating plates:
1. Crimp the user external cable on the battery terminals.
2. Crimp the battery insulating plates, and use the screws to fasten the OT terminals and insulating plates together onto the
terminal block.
1. Liebert ITA2 UPS 2. Battery Cabinets, 4
NOTE
The installation sequence of the OT terminals and insulating plates must be strictly observed, otherwise the user
external cables connection will be separated.
1
2
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 8
2.6.2 Installing the Battery Cabinet
1. Before installation, inspect the appearance and accessories of the battery, and cabinet and if there are any signs of
damage, contact Vertiv Services at 800-543-2378.
2. Maintain at least 10mm clearances between the front, rear, side panels of the battery and the wall or adjacent equipment
to keep well-ventilated.
3. Maintain some clearances between the top of the battery and the upper baffle to facilitate monitoring and maintenance of
the battery.
4. Install the batteries from the bottom to the top to minimize any tipping hazard. Place the battery well to avoid shake and
impact.
2.6.3 Connecting Battery Cabinet Cables
When more than one string is installed, use the factory-provided cable to connect the battery cabinets, use the
factory-provided cable shown in Figure 10, Terminals A of the first string connects to the UPS. Terminal B of the
first string will connect to Terminal A of the second string.
Figure 10 Cables between Liebert ITA2 and battery cabinets
The cable connections between the battery cabinet and the UPS are shown in Figure 11.
1. Communication Cable 2. Power Cable (UPS to Battery String 1) 3. Terminal A of
Battery Module 1
4. Terminal A of
Battery Module 1
5. Terminal A of Battery Module 1;
Battery String 2
6. Terminal B of Battery Module 2;
Battery String 2
1
2
3
CABLES FOR UPS TO ONE BATTERY STRING
CABLES FOR ADDITIONAL BATTERY STRINGS
1
4
5
6
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 9
Figure 11 Cable the UPS to two battery strings in parallel
1. PE (Battery Ground) on UPS 2. BAT - on UPS 3. BAT N on UPS 4. BAT + on UPS
5. Extension Cable 6. Terminal A, Battery Cabinet 1 7. Terminal B, Battery Cabinet 1 8. Terminal A, Battery Cabinet 2
9. Terminal B, Battery Cabinet 2 10. Terminal A, Battery Cabinet 3 11. Terminal A, Battery Cabinet 4 12. Communication Port 1
of Battery Cabinet 3
13. RJ-45 Communication Cables 14. Communication Port 2
of Battery Cabinet 1
15. Communication Port 1
of Battery Cabinet 1
REPO
1
2
3
4
6
7
8
9
10
11
12
14
15
13
13
5
5
6
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 10
2.7 Connecting Additional Battery Cabinets
The factory-provided extension cable has a PP45 connector on each end, as shown in Figure 12. It connects the
battery strings in parallel to extend the backup time of the UPS. The factory-provided communication cable has
an RJ-45 terminal on each end for communicating with the battery cabinets.
Figure 12 Battery extension cable
To connect power cables:
1. Verify that the battery breakers are in the open (Off) position before connecting or disconnecting battery cables.
2. If the Liebert ITA2 UPS has been connected to a battery cabinet, remove the connection cables.
3. Connect the extension cable to the corresponding battery ports on the two battery cabinets. Verify that the connector
colors align and press the cable in firmly to fully seat the connectors
4. Tighten the captive screws on the extension cable to prevent the extension cable from loosening.
5. Connect the communication cable to the RJ-45 port on the battery cabinet to the UPS as shown in Figure 11.
Figure 11 shows two battery strings connected in parallel.
To connect the battery cabinets to the Liebert ITA2 UPS, refer to the UPS user manual, SL-00030, which
shipped with the UPS and is available at Vertiv’s Web site: www.vertivco.com ,
1. Port B 2. Communication Cable 3. Port A 4. Power Cable
1
2
3
4
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 11
3.0 SPECIFICATIONS
Table 2 Battery cabinet specifications
Item Description
Battery Type Sealed, lead-acid, maintenance-free
Battery Capacity 12V/9Ah
Battery Cells Per Cabinet. 16
Rated Voltage per Cabinet 192VDC
Dimensions, W × D × H, in. (mm)
Net (One Cabinet) 16.9 x 19.7 x 5.1 (430 × 500 × 130)
Shipping
(2 Cabinets per Carton) 32.4 x 32.4 x 29.5 ( 822.5 x 823 750)
Weight, Approximate, lb. (kg)
Net (One Cabinet) 115 (52.2)
Shipping
(2 Cabinets per Carton) 306.4 (139)
Vertiv | Liebert® ITA2 208/220V Battery Cabinet Installation Manual | Rev. 0 | 01/18 | 12
TECHNICAL SUPPORT / SERVICE
Web Site
www.vertivco.com
Monitoring
liebert.monitoring@vertivco.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
LOCATIONS
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43085
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2016 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners.
While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to
change without notice.
This document may contain confidential and/or proprietary information of Liebert Corporation, and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction,
disclosure, or use without specific authorization from Liebert Corporation is strictly prohibited.
SL-26250_REV0_01-18
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

Vertiv Liebert ITA2 Installation guide

Category
Uninterruptible power supplies (UPSs)
Type
Installation guide

Vertiv Liebert ITA2 is a battery cabinet that can be used to extend the battery life of your Liebert ITA2 UPS. The battery cabinet is designed to be used with 8-10kVA, 60Hz, 208/220V UPS systems. It can accommodate up to 12 batteries, which can provide up to 10 minutes of runtime at full load. The battery cabinet is also equipped with a battery management system that monitors the status of the batteries and provides alarms in the event of a problem.

Here are some of the benefits of using a Vertiv Liebert ITA2 battery cabinet:

  • Extended battery life: The battery cabinet can extend the battery life of your UPS by up to 10 minutes, giving you more time to safely shut down your equipment in the event of a power outage.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI