Mitsubishi Electric fr-e700 series Installation Manuallines

Category
Power adapters & inverters
Type
Installation Manuallines
FR-E700
INSTALLATION GUIDELINE
FR-E740-016 to 300-EC
INVERTER
MITSUBISHI
ELECTRIC
700
CONTENTS
Thank you for choosing this Mitsubishi Inverter.
Please read through this Instruction Manual and the enclosed CD ROM to operate this inverter correctly
– The enclosed CD ROM contains the Installation Guideline in additional languages.
– Die CD-ROM enthält die deutsche Installationsbeschreibung.
– Il CD-ROM incluso contiene la guida di riferimento dell'installazione in lingua italiana.
– Le CD-ROM ci-joint contient cette documentation en français.
– El CD-ROM incluido contiene la pauta de la instalación en lengua española.
Приложенный CD-ROM содержит инструкцию по инсталяции на дополнительных языках.
Do not use this product until you have a full knowledge of the equipment, the safety information and the
instructions.
Please forward this manual and the CD ROM to the end user.
1
2
3
4
5
INSTALLATION OF THE INVERTER AND INSTRUCTIONS ...................................1
OUTLINE DIMENSION DRAWING............................................................................3
WIRING ......................................................................................................................4
PRECAUTIONS FOR USE OF THE INVERTER .......................................................9
FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER...............................11
PARAMETER...........................................................................................................12
TROUBLESHOOTING .............................................................................................17
6
7
Print Date Manual Number Revision
01/2008 pdp-gb 209035 First edition
For Maximum Safety
Mitsubishi transistorized inverters are not designed or manufactured to be used in equipment or systems in situations
that can affect or endanger human life.
When considering this product for operation in special applications such as machinery or systems used in passenger
transportation, medical, aerospace, atomic power, electric power, or submarine repeating applications, please contact
your nearest Mitsubishi sales representative.
Although this product was manufactured under conditions of strict quality control, you are strongly advised to install
safety devices to prevent serious accidents when it is used in facilities where breakdowns of the product are likely to
cause a serious accident.
Please do not use this product for loads other than three-phase induction motors.
Please check upon receiving of the inverter whether this instruction manual corresponds to the delivered inverter.
Compare the specifications on the capacity plate with the specifications given in this manual.
Electric Shock Prevention
Fire Prevention
Injury Prevention
Additional Instructions
Also note the following points to prevent an accidental failure, injury, electric shock, etc.
Transportation and installation
This section is specifically about safety matters
Do not attempt to install, operate, maintain or inspect the inverter until you have read through this Installation Guideline and appended
documents carefully and can use the equipment correctly. Do not use the inverter until you have a full knowledge of the equipment,
safety information and instructions. In this Installation Guideline, the safety instruction levels are classified into "WARNING" and
"CAUTION".
Assumes that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Assumes that incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may
cause physical damage only.
Note that even the level may lead to a serious consequence according to conditions. Please follow strictly the instructions
of both levels because they are important to personnel safety.
While power is on or when the inverter is running, do not open the front cover or wiring cover. Otherwise you may get an electric
shock.
Do not run the inverter with the front cover removed. Otherwise, you may access the exposed high-voltage terminals or the charging
part of the circuitry and get an electric shock.
Even if power is off, do not remove the front cover except for wiring or periodic inspection.You may access the charged inverter circuits and
get an electric shock.
Before starting wiring or inspection, check to make sure that the operation panel indicator is off, wait for at least 10 minutes after the
power supply has been switched off, and check that there are no residual voltage using a tester or the like. The capacitor is charged
with high voltage for some time after power off and it is dangerous.
This inverter must be earthed (grounded). Earthing (Grounding) must conform to the requirements of national and local safety regulations
and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable standards)
Use an neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard.
Any person who is involved in the wiring or inspection of this equipment should be fully competent to do the work.
Always install the inverter before wiring. Otherwise, you may get an electric shock or be injured.
Perform setting dial and key operations with dry hands to prevent an electric shock. Otherwise you may get an electric shock.
Do not subject the cables to scratches, excessive stress, heavy loads or pinching. Otherwise you may get an electric shock.
Do not replace the cooling fan while power is on. It is dangerous to replace the cooling fan while power is on.
Do no
t touch the printed circuit board with wet hands. You may get an electric shock
.
When measuring the main circuit capacitor capacity, the DC voltage is applied to the motor for 1s at powering off. Never touch the
motor terminal, etc. right after powering off to prevent an electric shock.
Mount the inverter to incombustible material. Mounting it to or near combustible material can cause a fire
.
If the inverter has become faulty, switch off the inverter power. A continuous flow of large current could cause a fire.
When using a brake resistor, make up a sequence that will turn off power when an alarm signal is output.
Otherwise,
the brake resistor may
excessively overheat due to damage of the brake transistor and such, causing a fire
.
Do not connect a resistor directly to the DC terminals P, N. This could cause a fire and destroy the inverter. The surface temperature of
braking resistors can far exceed 100°C for brief periods. Make sure that there is adequate protection against accidental contact and a safe
distance is maintained to other units and system parts
.
Apply only the voltage specified in the instruction manual to each terminal. Otherwise, burst, damage, etc. may occur.
Ensure that the cables are connected to the correct terminals. Otherwise, burst, damage, etc. may occur.
Always make sure that polarity is correct to prevent damage, etc. Otherwise, burst, damage, etc. may occur.
While power is on or for some time after power-off, do not touch the inverter as it is hot and you may get burnt.
Transport the product using the correct method that corresponds to the weight. Failure to observe this could lead to injuries.
Do not stack the inverter boxes higher than the number recommended.
Ensure that installation position and material can withstand the weight of the inverter. Install according to the information in the instruction
manual.
Do not install or operate the inverter if it is damaged or has parts missing. This can result in breakdowns.
When carrying the inverter, do not hold it by the front cover or setting dial; it may fall off or fail.
Do not stand or rest heavy objects on the product.
Check the inverter mounting orientation is correct.
Prevent other conductive bodies such as screws and metal fragments or other flammable substance such as oil from entering the
inverter.
As the inverter is a precision instrument, do not drop or subject it to impact.
Use the inverter under the following environmental conditions. Otherwise, the inverter may be damaged.
Temperature applicable for a short time, e.g. in transit.
WARNING
CAUTION
CAUTION
WARNING
CAUTION
CAUTION
CAUTION
Operating condition
Ambient temperature 10°C to +50°C (non-freezing)
Ambient humidity 90% RH or less (non-condensing)
Storage temperature 20°C to +65°C
Atmosphere Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude Maximum 1000m above sea level for standard operation. After that derate by 3% for every extra 500m
up to 2500m (91%)
Vibration 5.9m/s² or less
Wiring
Test operation and adjustment
Operation
Emergency stop
Maintenance, inspection and parts replacement
Disposing of the inverter
Do not install assemblies or components (e. g. power factor correction capacitors) on the inverter output side, which are not approved
from Mitsubishi.
The direction of rotation of the motor corresponds to the direction of rotation commands (STF/STR) only if the phase sequence (U, V,
W) is maintained.
Before starting operation, confirm and adjust the parameters. A failure to do so may cause some machines to make unexpected
motions.
When you have chosen the retry function, stay away from the equipment as it will restart suddenly after an alarm stop.
The key is valid only when the appropriate function setting has been made. Prepare an emergency stop switch separately to
make an emergency stop (power off, mechanical brake operation for emergency stop, etc).
Make sure that the start signal is off before resetting the inverter alarm. A failure to do so may restart the motor suddenly.
The inverter can be started and stopped via the serial port communications link or the field bus. However, please note that depending
on the settings of the communications parameters it may not be possible to stop the system via these connections if there is an error
in the communications system or the data line. In configurations like this it is thus essential to install additional safety hardware that
makes it possible to stop the system in an emergency (e.g. controller inhibit via control signal, external motor contactor etc). Clear and
unambiguous warnings about this must be posted on site for the operating and service staff.
The load used should be a three-phase induction motor only. Connection of any other electrical equipment to the inverter output may
damage the inverter as well as the equipment.
Do not modify the equipment.
Do not perform parts removal which is not instructed in this manual. Doing so may lead to fault or damage of the inverter.
The electronic thermal relay function does not guarantee protection of the motor from overheating.
Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter.
Use a noise filter to reduce the effect of electromagnetic interference and follow the accepted EMC procedures for proper installation
of frequency inverters. Otherwise nearby electronic equipment may be affected.
Take appropriate measures regarding harmonics. Otherwise this can endanger compensation systems or overload generators.
When a 400V class motor is inverter-driven, please use an insulation-enhanced motor or measures taken to suppress surge voltages.
Surge voltages attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor.
When parameter clear or all clear is performed, set again the required parameters before starting operations. Each parameter returns
to the initial value.
The inverter can be easily set for high-speed operation. Before changing its setting, fully examine the performances of the motor and
machine.
The DC braking function of the frequency inverter is not designed to continuously hold a load. Use an electro-mechanical holding
brake on the motor for this purpose.
Before running an inverter which had been stored for a long period, always perform inspection and test operation.
For prevention of damage due to static electricity, touch nearby metal before touching this product to eliminate static electricity from
your body.
Provide a safety backup such as an emergency brake which will prevent the machine and equipment from hazardous conditions if the
inverter fails.
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter,
etc. Identify the cause of the trip, then remove the cause and power on the breaker.
When the protective function is activated (i. e. the frequency inverter switches off with an error message), take the corresponding
corrective action as described in the inverter manual, then reset the inverter, and resume operation.
Do not carry out a megger (insulation resistance) test on the control circuit of the inverter.
Treat as industrial waste.
General instructions
Many of the diagrams and drawings in instruction manuals show the inverter without a cover, or partially open. Never run the inverter in
this status. Always replace the cover and follow instruction manuals when operating the inverter.
CAUTION
CAUTION
WARNING
CAUTION
CAUTION
CAUTION
CAUTION
1
1
INSTALLATION OF THE INVERTER AND INSTRUCTIONS
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to
ensure that the product agrees with your order and the inverter is intact.
1.2 Installation of the inverter
Enclosure surface mounting
1.1 Inverter Type
Symbol Voltage Class
E740 Three-phase
400V class
Symbol Type number
016
to
300
3-digit display
Capacity plate example
Rating plate example
Capacity plate
Rating plate
Serial number
Inverter type
Input rating
Output rating
Serial number
Inverter type
Note
When encasing multiple
inverters, install them in
parallel and leave clearance
as a cooling measure
.
Install the inverter vertically.
vertical
Refer to the clearances beside
Ambient temperature and humidity Clearances (front) Clearances (side)
5cm 5cm
5cm
Inverter
Measurement
position
Measurement
position
Temperature: 10°C to +50°C
Humidity: 90% RH maximum
10cm or more
1cm
or more *1
10cm or more
1cm
or more *1 1 cm
or
more *1
Leave enough clearances and
take cooling measures.
*1 When using the inverters at the
ambient temperature of 40°C or
less, the inverters can be installed
closely attached (0cm clearance).
When ambient temperature
exceeds 40°C, clearances
between the inverter should be
1cm or more (5cm or more for the
FR-E740-120 or more).
*1 5cm or more for the
FR-E740-120 or more
2
INSTALLATION OF THE INVERTER AND INSTRUCTIONS
1.3 General Precaution
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than
10 minutes, and check for residual voltage between terminal P/+ and N/ with a meter etc., to avoid a hazard of electrical
shock.
1.4 Environment
Before installation, check that the environment meets following specifications.
Ambient temperature 10°C to +50°C (non-freezing)
Ambient humidity 90% RH or less (non-condensing)
Atmosphere Free from corrosive and explosive gases, free from dust and dirt
Maximum altitude 1000m or less. After that derate by 3% for every extra 500m up to 2500m (91%)
Vibration 5.9m/s² or less
CAUTION
Install the inverter on a strong surface securely and vertically with bolts.
Leave enough clearances and take cooling measures.
Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
Install the inverter on a non-combustible surface.
3
2 OUTLINE DIMENSION DRAWING
(Unit: mm)
Inverter Type WW1 HH1 DD1
FR-E740-016
140 128
150 138
114 129.1
FR-E740-026
FR-E740-040
135 150.1FR-E740-060
FR-E740-095
FR-E740-120
220
208 147 162.1
FR-E740-170
FR-E740-230 195 260 244 190 205.1
FR-E740-300
When the FR-A7NC is mounted, a
terminal block protrudes making the
depth approx 2mm greater.
When used with plug-in option
4
3 WIRING
3.1 Terminal connection diagram
CAUTION
To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables.
After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction. Always keep the
inverter clean. When drilling mounting holes in a control box etc., take care not to allow chips and other foreign matter to enter the
inverter.
Set the voltage/current input switch in the correct position. An incorrect setting may cause a fault, failure or malfunction.
Source logic
Main circuit terminal
Control circuit terminal
Jumper
*1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1-P/+.
Earth
Motor
3-phase
AC power
supply
Main circuit
Control circuit
Terminal functions vary
with the input terminal
assignment.
(Pr. 178 to Pr. 184)
Control input signals (No voltage input allowed)
Forward
rotation start
Reverse
rotation start
High
speed
Medium
speed
Low
speed
Multi-speed selection
Output
stop
RESET
Contact input common (Sink*)
*2 When using terminals
PC-SD as a 24VDC
power supply, take care
not to short across
terminals PC-SD.
24VDC power supply/ max. 100mA load current
Contact input common(Source*)
*(Common for external power supply transistor)
Frequency setting signal (Analog)
Ter mi na l 4
input
(Current
input)
0–5VDC
0 to 5VDC
0 to 10VDC
PU
connector
Connector for plug-in
option connection Option connector
*5 It is recommended to use a 1 kΩ, 2 W
potentiometer when the frequency
setting signal is changed frequently.
Relay output
(Alarm output)
Running
Frequency detection
Terminal functions vary
by Pr. 192 “ABC terminal
function selection”
Terminal functions vary with the
output terminal assignment.
(Pr. 190 to Pr. 191)
Open collector output common
Sink/source common
Frequency
setting
potentiometer
1 kΩ,1/2 W
M
3~
Earth
Brake unit
(Option)
*6 Brake resistor (FR-ABR, MRS, MYS)
Install a thermal relay to prevent an overheat
and burnout of the brake resistor.
*4 The input area can be set
via Parameter (Pr. 267).
Set the voltage/current
input switch in the “V”
position to select voltage
input (0 to 5V/0 to 10V)
and “I” (initial value) to
select current input
(0/4 to 20mA.)
*4 Voltage/current
input switch
Relay output
USB
connector
Open collector output
Standard control terminal block
Analog signal output
(0 to 10VDC)
0–10VDC
Analog common
4 to 20mADC
*3. Terminal input specifica-
tions can be changed
by analog input specifi-
cations
Earth
*5
5
WIRING
3.2 Main circuit terminal specifications
3.2.1 Terminal arrangement of the main circuit terminal, power supply and the motor wiring
FR-E740-016 to 095 FR-E740-120, 170
FR-E740-230, 300
CAUTION
The power supply cables must be connected to R/L1, S/L2, T/L3. Never connect the power cable to the U, V, W of the inverter. Doing
so will damaged the inverter. (Phase sequence needs not to be matched.)
Connect the motor to U, V, W. At this time turning on the forward rotation switch (signal) rotates the motor in the clockwise direction
when viewed on the motor shaft.
Screw size (M4)
Jumper
Screw size
(M4) Motor
Power supply
M
3 ~
L1L2L3
Jumper
Power supply
Screw size
(M4)
Motor
M
3 ~
L1L2L3
Screw size (M4)
Schrauben (M4)
Jumper
Screw size
(230: M4,
300: M5) Motor
Power supply
M
3 ~
L1L2L3
6
WIRING
3.3 Cables and wiring lenght
3.3.1 Cable size
Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque
to decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m.
400V class (when input power supply is 440V)
The line voltage drop can be calculated by the following expression:
line voltage drop [V] =
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
Applicable Inverter Type Terminal Screw Size *4Tightening Torque [Nm] Crimping Terminal
R/L1, S/L2, T/L3 U, V, W
FR-E740-016 to 095 M4 1.5 2-4 2-4
FR-E740-120 M4 1.5 2-4 2-4
FR-E740-170 M4 1.5 5.5-4 5.5-4
FR-E740-230 M4 1.5 5.5-4 5.5-4
FR-E740-300 M5 2.5 8-5 8-5
Applicable Inverter Type
Cable Sizes
HIV, etc. [mm2] *1AWG *2PVC, etc. [mm2] *3
R/L1,
S/L2,
T/L3 U, V, W Earth Cable
Gauge
R/L1,
S/L2,
T/L3 U, V, W R/L1,
S/L2,
T/L3 U, V, W Earth Cable
Gauge
FR-E740-016 to 095 2 2 2 14 14 2.5 2.5 2.5
FR-E740-120 3.5 2 3.5 12 14 4 2.5 4
FR-E740-170 3.5 3.5 3.5 12 12 4 4 4
FR-E740-230 5.5 5.5 8 10 10 6 6 10
FR-E740-300 8 8 8 8 8 10 10 10
*1 The recommended cable size is that of the HIV cable (600V class 2 vinyl-insulated cable) with continuous maximum permissible temperature of
75°C. Assumes that the ambient temperature is 50°C or less and the wiring distance is 20m or less.
*2 The recommended cable size is that of the THHW cable with continuous maximum permissible temperature of 75°C. Assumes that the ambient
temperature is 40°C or less and the wiring distance is 20m or less.
(Selection example for use mainly in the Unite States.)
*3 The recommended cable size is that of the PVC cable with continuous maximum permissible temperature of 70°C. Assumes that the ambient
temperature is 40°C or less and the wiring distance is 20m or less.
(Selection example for use mainly in Europe.)
*4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/, P1 and a screw for earthing.
NOTE
Tighten the terminal screw to the specified torque. A screw that has been tighten too loosely can cause a short circuit
or malfunction. A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit
breakage.
Use crimping terminals with insulation sleeve to wire the power supply and motor.
3 wire resistance [mΩ/m]wiring distance [m] current [A]×××
1000
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
7
WIRING
3.3.2 Maximum permissible motor wiring length
The maximum permissible length of the motor cables depends on the capacity of the inverter and the selected carrier
frequency.
The lengths in the following table are for unshielded cables. When shielded cables are used divide the values listed in the
table by 2. Note that the values are for the total wiring length – if you connect more than one motor in parallel you must
add the lengths of the individual motor cables.
Note that the motor windings in three-phase AC motors are subject to far more stress when operated via frequency
inverters than with mains operation. The motor must have been approved by the manufacturer for operation on a
frequency inverter.
In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially
for a 400V class motor, the surge voltage may deteriorate the insulation. When the 400V class motor is driven by the
inverter, consider the following measures:
Use a "400V class inverter-driven insulation-enhanced motor" and set frequency in Pr. 72 PWM frequency selection
according to wiring length.
Limiting the voltage rise speed of the frequency inverter output voltage (dU/dT):
If the motor requires a rise speed of 500V/μs or less you must install a filter in the output of the inverter. Please contact
your Mitsubishi dealer for more details.
Setting of Pr. 72 PWM Frequency selection
(carrier frequency) 016 026 040 060 095
1 (1kHz) or less 200m 200m 300m 500m 500m
2 to 15 (2kHz to 14.5kHz) 30m 100m 200m 300m 500m
50m 50m–100m 100m
Carrier frequency 14.5kHz 8kHz 2kHz
CAUTION
Especially for long-distance wiring (particularly when employing shielded motor cables), the inverter may be affected by a charging
current caused by the stray capacitances of the wiring, leading to a malfunction of the overcurrent protective function or fast response
current limit function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
When the fast-response current limit function malfunctions, make the function invalid. When stall prevention function misoperates,
increase the stall level. (For Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention operation selection, refer to the Instruction
Manual.)
For details of Pr. 72 PWM frequency selection, refer to the Instruction Manual.
When using the automatic restart after instantaneous power failure function with wiring length exceeding 100m, select without
frequency search (Pr. 162 = "1, 11"). (Refer to the Instruction Manual).
500m or less
300m
300m
300m + 300m = 600m
Total wiring lenght (FR-E740-095 or more)
8
WIRING
3.4 Control circuit specification
3.4.1 Standard control circuit terminal layout
3.4.2 Wiring method
Strip off the sheath of the cable of the control circuit to wire.
Strip off the sheath about the size below. If the length of the sheath pealed is too long, a short circuit may occur among
neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
Use a bar terminal as necessary.
Loosen the terminal screw and insert the cable into the terminal.
Tighten the screw to the specified torque.
Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or malfunction
due to damage to the screw or unit.
3.4.3 Wiring instructions
Terminals PC, 5, and SE are all common terminals (0V) for I/O signals and are isolated from each other. Avoid
connecting the terminal PC and 5 and the terminal SE and 5 (ground). Terminal PC is a common terminal for the contact
input terminals (STF, STR, RH, RM, RL, MRS, RES).
Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and
power circuits (including the 230V relay sequence circuit).
Use two or more parallel micro-signal contacts or twin
contacts to prevent a contact faults when using contact
inputs since the control circuit input signals are micro-
currents.
Do not apply a voltage to the contact input terminals (e.g. STF) of the control circuit.
Always apply a voltage to the alarm output terminals (A, B, C) via a relay coil, lamp, etc.
It is recommended to use the cables of 0.3mm² to 0.75mm² gauge for connection to the control circuit terminals.
If the cable gauge used is 1.25mm² or more, the front cover may be lifted when there are many cables running or the
cables are run improperly, resulting in an operation panel contact fault.
The wiring length should be 30m maximum.
The level of the control signals can be switched over between positive (SOURCE) and negative (SINK) logic. The input
signals are set to source logic when shipped from the factory. To change the control logic, the jumper connector above
the control circuit terminal block must bemoved to the other position.
L[mm] Tightening torque[Nm]
Terminal A, B, C 6 0.5–0.6
Other than the above 5 0.22–0.25
Srew driver Flat blade screw driver
Tip thickness: 0,4mm × 2,5mm
AM
L
Micro signal contacts Twin contacts
Terminal screw size
M3: (Terminal A, B, C)
M2: (Other than the above)
9
4 PRECAUTIONS FOR USE OF THE INVERTER
The FR-E700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may
shorten the product life or damage the product.
Before starting operation, always recheck the following items.
Use crimping terminals with insulation sleeve to wire the power supply and motor.
Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform such wiring.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes in
a control box etc., take care not to allow chips and other foreign matter to enter the inverter.
Use cables of the size to make a voltage drop 2% maximum.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor
torque to decrease especially at the output of a low frequency.
Refer to page 6 for the recommended cable size.
The overall wiring length should be 500m maximum.
Especially for long distance wiring, the fast-response current limit function may be reduced or the equipment connected
to the inverter output side may malfunction or become faulty under the influence of a charging current due to the stray
capacity of the wiring. Therefore, note the overall wiring length. (Refer to page 6)
Electromagnetic Compatibility
Operation of the frequency inverter can cause electromagnetic interference in the input and output that can be
propagated by cable (via the power input lines), by wireless radiation to nearby equipment (e.g. AM radios) or via data
and signal lines. Install an optional filter if present to reduce air propagated interference on the input side of the inverter.
Use AC or DC reactors to reduce line propagated noise (harmonics). Use shielded motor power lines to reduce output
noise.
Do not install a power factor correction capacitor, varistor or arrester on the inverter output side. This will cause the
inverter to trip or the capacitor, varistor, or arrester to be damaged. If any of the above devices is installed, immediately
remove it.
Before starting wiring or other work after the inverter is operated, wait for at least 10 minutes after the power supply has
been switched off, and check that there are no residual voltage using a tester or the like. The capacitor is charged with
high voltage for some time after power off and it is dangerous.
A short circuit or earth fault on the inverter output side may damage the inverter modules.
– Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by
peripheral circuit inadequacy or an earth fault caused by wiring inadequacy or reduced motor insulation resistance
may damage the inverter modules.
– Fully check the to-earth insulation and inter-phase insulation of the inverter output side before power-on.
Especially for an old motor or use in hostile atmosphere, securely check the motor insulation resistance etc.
Do not use the inverter input side magnetic contactor to start/stop the inverter.
Always use the start signal (ON/OFF of STF and STR signals) to start/stop the inverter.
Across P/+ and PR terminals, connect only an external regenerative brake discharge resistor. Do not connect a
mechanical brake.
Also, never short between these terminals.
10
PRECAUTIONS FOR USE OF THE INVERTER
Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.
Application of a voltage higher than the permissible voltage to the inverter I/O signal circuits or opposite polarity may
damage the I/O devices. Especially check the wiring to prevent the speed setting potentiometer from being connected
incorrectly to short terminals 10-5.
Provide electrical and mechanical interlocks for MC1 and MC2
which are used for bypass operation.
When the wiring is incorrect or if there is a bypass circuit as shown
below, the inverter will be damaged by leakage current from the
power supply due to arcs generated at the time of switch-over or
chattering caused by a sequence error.
If the machine must not be restarted when power is restored after
a power failure, provide a magnetic contactor in the inverter's input side and also make up a sequence which will not
switch on the start signal.
If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the
power is restored.
Instructions for overload operation
When performing operation of frequent start/stop of the inverter, increase/decrease in the temperature of the transistor
element of the inverter may repeat due to a continuous flow of large current, shortening the life from thermal fatigue.
Since thermal fatigue is related to the amount of current, the life can be increased by reducing bound current, starting
current, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and
the inverter may not start. Therefore, increase the inverter capacity to have enough allowance for current.
Make sure that the specifications and rating match the system requirements.
When the motor speed is unstable, due to change in the frequency setting signal caused by electromagnetic noises
from the inverter, take the following measures when applying the motor speed by the analog signal.
– Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do not bundle them.
– Run signal cables as far away as possible from power cables (inverter I/O cables).
– Use shield cables as signal cables.
– Install a ferrite core on the signal cable (Example: ZCAT3035-1330 TDK).
Inverter
Undesirable Current
Interlock
Power
supply M
3~
11
5 FAILSAFE OF THE SYSTEM WHICH USES THE
INVERTER
When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an
inverter fault occurrence when the detection circuit or output circuit fails, etc. Although Mitsubishi assures best
quality products, provide an interlock which uses inverter status output signals to prevent accidents such as
damage to machine when the inverter fails for some reason and at the same time consider the system configuration
where failsafe from outside the inverter, without using the inverter, is enabled even if the inverter fails.
Interlock method which uses the inverter status output signals
By combining the inverter status output signals to provide an interlock as shown below, an inverter alarm can be
detected.
Backup method outside the inverter
Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure
status of the inverter itself. For example, even if the interlock is provided using the inverter fault output signal, start
signal and RUN signal output, there is a case where a fault output signal is not output and RUN signal is kept output
even if an inverter fault occurs.
Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider
the backup system such as checking up as below according to the level of importance of the system. Check the
motor running and motor current while the start signal is input to the inverter by comparing the start signal to the
inverter and detected speed of the speed detector or detected current of the current detector. Note that the motor
current runs as the motor is running for the period until the motor stops since the inverter starts decelerating even if
the start signal turns off. For the logic check, configure a sequence considering the inverter deceleration time. In
addition, it is recommended to check the three-phase current when using the current detector.
Check if there is no gap between the actual speed and commanded speed by comparing the inverter speed
command and detected speed of the speed detector.
Interlock Method Check Method Used Signals Refer to Page
Inverter protective function
operation
Operation check of an alarm contact
Circuit error detection by negative logic
Fault output signal
(ALM signal)
Refer to chapter 4 of the
Instruction Manual
Inverter runnning status
Operation ready signal check Operation ready signal
(RY signal)
Logic check of the start signal and
running signal
Start signal
(STF signal, STR signal)
Running signal (RUN signal)
Logic check of the start signal and output
current
Start signal
(STF signal, STR signal)
Output current detection signal
(Y12 signal)
System failure
Controller
Inverter Sensor
(speed, temperature,
air volume, etc.)
To the alarm detection sensor
12
6 PARAMETER
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel. For details of parameters, refer to the instruction manual.
Remarks
The parameters marked are the simple mode parameters.
The parameters marked with in the table allow its setting to be changed during operation even if "0"
(initial value) is set in Pr. 77 Parameter write selection.
Parameters
Name Setting Range Initial Value
0 Torque boost 0 to 30% 6/4/2 *1
1 Maximum frequency 0 to 120Hz 120Hz
2 Minimum frequency 0 to 120Hz 0Hz
3 Base frequency 0 to 400Hz 50Hz
4 Multi-speed setting
(high speed) 0 to 400Hz 50Hz
5 Multi-speed setting
(middle speed) 0 to 400Hz 30Hz
6 Multi-speed setting
(low speed) 0 to 400Hz 10Hz
7 Acceleration time 0 to 3600/360s 5s/10s/
15s *2
8 Deceleration time 0 to 3600/360s 5s/10s/
15s *2
9 Electronic thermal
O/L relay 0 to 500A
Rated
inverter
output
current
10
DC injection brake
operation frequency 0 to 120Hz 3Hz
11
DC injection brake
operation time 0 to 10s 0.5s
12
DC injection brake
operation voltage 0 to 30% 4%/2% *3
13
Starting frequency 0 to 60Hz 0.5Hz
14
Load pattern
selection 0 to 3 0
15
Jog frequency 0 to 400Hz 5Hz
16
Jog acceleration/
deceleration time 0 to 3600/360s 0.5s
17
MRS input selection 0, 2, 4 0
18
High speed
maximum frequency 120 to 400Hz 120Hz
19
Base frequency
voltage 0 to 1000V,
8888, 9999 8888
20
Acceleration/
deceleration
reference frequency 1 to 400Hz 50Hz
21
Acceleration/
deceleration time
increments 0, 1 0
22
Stall prevention
operation level
0 to 200%
150%
23
Stall prevention
operation level
compensation factor
at double speed
0 to 200%, 9999
9999
24 to 27
Multi-speed setting 4
speed to 7 speed 0 to 400Hz,
9999 9999
29
Acceleration/
deceleration pattern
selection 0, 1, 2 0
30
Regenerative
function selection 0, 1, 2 0
31
Frequency jump 1A 0 to 400Hz,
9999 9999
32
Frequency jump 1B 0 to 400Hz,
9999 9999
33
Frequency jump 2A 0 to 400Hz,
9999 9999
34
Frequency jump 2B 0 to 400Hz,
9999 9999
35
Frequency jump 3A 0 to 400Hz,
9999 9999
36
Frequency jump 3B 0 to 400Hz,
9999 9999
37
Speed display 0, 0.01 to 9998 0
40
RUN key rotation
direction selection 0, 1 0
41
Up-to-frequency
sensitivity 0 to 100% 10%
42
Output frequency
detection 0 to 400Hz 6Hz
Parameters
Name Setting Range Initial Value
*1 Differ according to capacities.
6%: FR-E740-026 or less
4%: FR-E740-040 to 095
3%: FR-E740-120 and 170
2%: FR-E740-230 and 300
*2 Differ according to capacities.
5s: FR-E740-095 or less
10s: FR-E740-120 and 170
15s: FR-E740-230 and 300
*3 Differ according to capacities.
4%: FR-E740-016 to 170
2%: FR-E740-230 and 300
13
PARAMETER
43
Output frequency
detection for reverse
rotation
0 to 400Hz,
9999 9999
44
Second acceleration/
deceleration time 0 to 3600/360s 5s/10s/
15s *1
45
Second deceleration
time 0 to 3600/360s,
9999 9999
46
Second torque boost 0 to 30%, 9999 9999
47
Second V/F
(base frequency) 0 to 400Hz,
9999 9999
48
Second stall
prevention operation
current 0 to 200%, 9999 9999
51 Second electronic
thermal O/L relay 0 to 500A, 9999 9999
52
DU/PU main display
data selection
0, 5, 7 to 12, 14,
20, 23 to 25,
52 to 57, 61, 62,
100
0
55
Frequency
monitoring reference 0 to 400Hz 50Hz
56
Current monitoring
reference 0 to 500A
Rated
inverter
output
current
57
Restart coasting time 0, 0.1 to 5s,
9999 9999
58
Restart cushion time 0 to 60s 1s
59
Remote function
selection 0, 1, 2, 3 0
60
Energy saving
control selection 0, 9 0
61
Reference current 0 to 500A, 9999 9999
62
Reference value at
acceleration 0 to 200%, 9999 9999
63
Reference value at
deceleration 0 to 200%, 9999 9999
65
Retry selection 0 to 5 0
66
Stall prevention
operation reduction
starting frequency 0 to 400Hz 50Hz
67
Number of retries at
alarm occurrence 0 to 10,
101 to 110 0
68
Retry waiting time 0.1 to 360s 1s
69
Retry count display
erase 00
70
Special regenerative
brake duty 0 to 30% 0%
71
Applied motor
0, 1, 3 to 6, 13 to
16, 23, 24, 40,
43, 44, 50, 53,
54
0
72
PWM frequency
selection 0 to 15 1
73
Analog input
selection 0, 1, 10, 11 1
74
Input filter time
constant 0 to 8 1
Parameters
Name Setting Range Initial Value
75
Reset selection/
disconnected PU
detection/PU stop
selection
0 to 3, 14 to 17 14
77
Parameter write
selection 0, 1, 2 0
78
Reverse rotation
prevention selection 0, 1, 2 0
79 Operation mode
selection 0, 1, 2, 3, 4, 6, 7 0
80
Motor capacity 0.1 to 15kW,
9999 9999
81
Number of motor
poles 2, 4, 6, 8, 10,
9999 9999
82
Motor excitation
current
0 to 500A
(0 to ****),
9999 *2 9999
83
Motor rated voltage 0 to 1000V 400V
84
Rated motor
frequency 10 to 120 Hz 50Hz
89
Speed control gain
(advanced magnetic
flux vector) 0 to 200%, 9999 9999
90
Motor constant (R1) 0 to 50Ω,
(0 to ****),
9999 *2
9999
91
Motor constant (R2) 0 to 50Ω,
(0 to ****),
9999 *2
9999
92
Motor constant (L1)
0 to 1000mH,
(0 to 50Ω,
0 to ****),
9999 *2
9999
93
Motor constant (L2)
0 to 1000mH,
(0 to 50Ω,
0 to ****),
9999 *2
9999
94
Motor constant (X)
0 to 100%,
(0 to 500Ω,
0 to ****),
9999 *2
9999
96
Auto tuning setting
status 0, 1, 11, 21 0
117
PU communication
station number 0 to 31
(0 to 247) 0
118
PU communication
speed 48, 96, 192, 384 192
119
PU communication
stop bit length 0, 1, 10, 11 1
120
PU communication
parity check 0, 1, 2 2
121
Number of PU
communication
retries 0 to 10, 9999 1
122
PU communication
check time interval 0, 0.1 to 999.8s,
9999 0
123
PU communication
waiting time setting 0 to 150ms,
9999 9999
124
PU communication
CR/LF presence/
absence selection 0, 1, 2 1
Parameters
Name Setting Range Initial Value
*1 Differ according to capacities.
5s: FR-E740-095 or less
10s: FR-E740-120 and 170
15s: FR-E740-230 and 300
*2 The range differs according to the Pr. 71 setting.
14
PARAMETER
125 Terminal 2 frequency
setting gain
frequency 0 to 400Hz 50Hz
126 Terminal 4 frequency
setting gain
frequency 0 to 400Hz 50Hz
127
PID control
automatic
switchover
freqeuncy
0 to 400Hz,
9999 9999
128
PID action selection 0, 20, 21, 40 to
43, 50, 51, 60,
61
0
129
PID proportional
band 0.1 to 1000%,
9999 100%
130
PID integral time 0.1 to 3600s,
9999 1s
131
PID upper limit 0 to 100%,
9999 9999
132
PID lower limit 0 to 100%,
9999 9999
133
PID action set point 0 to 100%,
9999 9999
134
PID differential time 0.01 to 10.00s,
9999 9999
145
PU display language
selection 0 to 7 1
146
Parameter for manufacturer setting. Do not set.
147
Acceleration/
deceleration time
switching frequency
0 to 400 Hz,
9999 9999
150
Output current
detection level 0 to 200% 150%
151
Output current
detection signal
delay time 0 to 10s 0s
152
Zero current
detection level 0 to 200% 5%
153
Zero current
detection time 0 to 1s 0.5s
156
Stall prevention
operation selection 0 to 31, 100,
101 0
157
OL signal output
timer 0 to 25s, 9999 0s
158
AM terminal function
selection
1 to 3, 5, 7 to 12,
14, 21, 24, 52,
53, 61, 62
1
160 User group read
selection 0, 1, 9999 0
161
Frequency setting/
key lock operation
selection 0, 1, 10, 11 0
162
Automatic restart
after instantaneous
power failure
selection
0, 1, 10, 11 1
165
Stall prevention
operation level for
restart 0 to 200% 150%
168
Parameter for manufacturer setting.
Do not set.
169
170
Watt-hour meter
clear 0, 10, 9999 9999
171
Operation hour
meter clear 0, 9999 9999
172
User group
registered display/
batch clear 9999, (0 to 16) 0
Parameters
Name Setting Range Initial Value
173
User group
registration 0 to 999, 9999 9999
174
User group clear 0 to 999, 9999 9999
178
STF terminal
function selection
0 to 5, 7, 8, 10,
12, 14 to 16, 18,
24, 25, 60, 62,
65 to 67, 9999
60
179
STR terminal
function selection
0 to 5, 7, 8, 10,
12, 14 to 16, 18,
24, 25, 61, 62,
65 to 67, 9999
61
180
RL terminal function
selection
0 to 5, 7, 8, 10,
12, 14 to 16, 18,
24, 25, 62, 65 to
67, 9999
0
181
RM terminal function
selection 1
182
RH terminal function
selection 2
183
MRS terminal
function selection 24
184
RES terminal
function selection 62
190
RUN terminal
function selection
0, 1, 3, 4, 7, 8,
11 to 16, 20, 25,
26, 46, 47, 64,
90, 91, 93, 95,
96, 98, 99, 100,
101, 103, 104,
107, 108, 111 to
116, 120, 125,
126, 146, 147,
164, 190, 191,
193, 195, 196,
198, 199, 9999
0
191
FU terminal function
selection 4
192
ABC terminal
function selection
0, 1, 3, 4, 7, 8,
11 to 16, 20, 25,
26, 46, 47, 64,
90, 91, 95, 96,
98, 99, 100, 101,
103, 104, 107,
108, 111 to 116,
120, 125, 126,
146, 147, 164,
190, 191, 195,
196, 198, 199,
9999
99
232
to
239
Multi-speed setting
(speeds 8 to 15) 0 to 400Hz,
9999 9999
240
Soft-PWM operation
selection 0, 1 1
241
Analog input display
unit switchover 0, 1 0
244
Cooling fan
operation selection 0, 1 1
245
Rated slip 0 to 50%, 9999 9999
246
Slip compensation
time constant 0.01 to 10s 0.5s
247
Constant-power
range slip
compensation
selection
0, 9999 9999
249
Earth (ground) fault
detection at start 0, 1 0
250
Stop selection 0 to 100s,
1000 to 1100s,
8888, 9999
9999
251
Output phase loss
protection selection 0, 1 1
255
Life alarm status
display (0 to 15) 0
Parameters
Name Setting Range Initial Value
15
PARAMETER
256
Inrush current
suppression circuit
life display (0 to 100%) 100%
257
Control circuit
capacitor life display (0 to 100%) 100%
258
Main circuit
capacitor life display (0 to 100%) 100%
259
Main circuit
capacitor life
measuring 0, 1 (2, 3, 8, 9) 0
261
Power failure stop
selection 0, 1, 2 0
267
Terminal 4 input
selection 0, 1, 2 0
268
Monitor decimal
digits selection 0, 1, 9999 9999
269
Parameter for manufacturer setting.
Do not make setting.
270
Stop-on contact
control selection 0, 1 0
275
Stop-on contact
excitation current
low-speed
multiplying factor
0 to 300%, 9999 9999
276
PWM carrier
frequency at stop-on
contact 0 to 9, 9999 9999
277
Stall prevention
operation current
switchover 0, 1 0
278
Brake opening
frequency 0 to 30Hz 3Hz
279
Brake opening
current 0 to 200% 130%
280
Brake opening
current detection
time 0 to 2s 0.3s
281
Brake operation time
at start 0 to 5s 0.3s
282
Brake operation
frequency 0 to 30Hz 6Hz
283
Brake operation time
at stop 0 to 5s 0.3s
286
Droop gain 0 to 100% 0%
287
Droop filter time
constant 0 to 1s 0.3s
292
Automatic
acceleration/
deceleration 0, 1, 7, 8, 11 0
293
Acceleration/
deceleration
separate selection 0 to 2 0
295
Magnitude of
frequency change
setting
0, 0.01, 0.10,
1.00, 10.00 0
298
Frequency search
gain 0 to 32767,
9999 9999
299
Rotation direction
detection selection
at restarting 0, 1, 9999 0
338
Communication
operation command
source 0, 1 0
339
Communication
speed command
source 0, 1, 2 0
Parameters
Name Setting Range Initial Value
340
Communication
startup mode
selection 0, 1, 10 0
342
Communication
EEPROM write
selection 0, 1 0
343
Communication error
count 0
450
Second applied
motor 0, 1, 9999 9999
495
Remote output
selection 0, 1, 10, 11 0
496
Remote output data 1 0 to 4095 0
497
Remote output data 1 0 to 4095 0
502
Stop mode selection
at communication
error 0,1, 2, 3 0
503
Maintenance timer 0 (1 to 9998) 0
504
Maintenance timer
alarm output set time 0 to 9998, 9999 9999
547
USB communication
station number 0 to 31 0
548
USB communication
check time interval 0 to 999.8s,
9999 9999
549
Protocol selection 0, 1 0
550
NET mode operation
command source
selection 0, 2, 9999 9999
551
PU mode operation
command source
selection 2 to 4, 9999 2
555
Current average time 0.1 to 1.0s 1s
556
Data output mask
time 0.0 to 20.0s 0s
557
Current average
value monitor signal
output reference
current
0 to 500A
Rated
inverter
current
563
Energization time
carrying-over times (0 to 65535) 0
564
Operating time
carrying-over times (0 to 65535) 0
571
Holding time at a
start 0.0 to 10.0s,
9999 9999
611
Acceleration time at
a restart 0 to 3600s,
9999 9999
645
AM 0V adjustment 970 to 1200 1000
653
Speed smoothing
control 0 to 200% 0
665
Regeneration
avoidance frequency
gain 0 to 200% 100
800
Control method
selection 20, 30 20
859
Torque current 0 to 500A
(0 to ****),
9999 *1 9999
872
Input phase loss
protection selection 0, 1 1
882
Regeneration
avoidance operation
selection 0, 1, 2 0
Parameters
Name Setting Range Initial Value
*1 The range differs according to the Pr. 71 setting.
16
PARAMETER
883
Regeneration
avoidance operation
level 300 to 800V 760VDC
885
Regeneration
avoidance
compensation
frequency limit value
0 to 10Hz,
9999 6Hz
886
Regeneration
avoidance voltage
gain 0 to 200% 100%
888
Free parameter 1 0 to 9999 9999
889
Free parameter 2 0 to 9999 9999
C1
(901)
*1 AM terminal
calibration ⎯⎯
C2
(902)
*1
Terminal 2 frequency
setting bias
frequency 0 to 400Hz 0Hz
C3
(902)
*1 Terminal 2 frequency
setting bias 0 to 300% 0%
125
(903)
*1
Terminal 2 frequency
setting gain
frequency 0 to 400Hz 50Hz
C4
(903)
*1 Terminal 2 frequency
setting gain 0 to 300% 100%
Parameters
Name Setting Range Initial Value
C5
(904)
*1
Terminal 4 frequency
setting bias
frequency 0 to 400Hz 0Hz
C6
(904)
*1 Terminal 4 frequency
setting bias 0 to 300% 20%
126
(905)
*1
Terminal 4 frequency
setting gain
frequency 0 to 400Hz 50Hz
C7
(905)
*1 Terminal 4 frequency
setting gain 0 to 300% 100%
C22
(922)
*1
Parameter for manufacturer setting. Do not set.
C23
(922)
*1
C24
(923)
*1
C25
(923)
*1
990
PU buzzer control 0, 1 1
991
PU contrast
adjustment 0 to 63 58
Pr.CL
Parameter clear 0, 1 0
ALLC
All parameter clear 0, 1 0
Er.CL
Alarm history clear 0, 1 0
Pr.CH
Initial value change
list ——
Parameters
Name Setting Range Initial Value
*1 The parameter number in parentheses is the one for use with the operation panel (FR-PA02-02) for the FR-E500 series or parameter unit
(FR-PU04/FR-PU07).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Mitsubishi Electric fr-e700 series Installation Manuallines

Category
Power adapters & inverters
Type
Installation Manuallines

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI