meitav-tec MIGA AB Product information

  • Hello! I've analyzed the provided wiring diagram for the meitav-tec MIGA AB system, including details for configurations with slave and master boards, various room panels, and an IR receiver. I'm familiar with the instructions about disconnecting power before wiring, mode selection, and auto-fan operation. I'm ready to answer your questions about connecting and using this system.
  • What should be done before making any changes to wiring?
    How is mode selected in a 2-pipe system?
    What happens when T3 is not connected?
LO ME NHI F2 F1 CRV N ~
PANEL
T1 T0 T2 T2 T3 T3
+12Vdc
+5Vdc
14
15
16
17
JMP1
Fuse 10A
Controller
JP8
Not in Use
Supply
230VAC
50/60Hz
ETN1000MIG
Important Notes:
Disconnect power to the main board before making any changes to jumpers, wiring the unit and/or
connecting the wall panels/IR receivers.
T1 must be connected to the MIGA boards
When T2 is connected in 2-pipe system ,mode is selected automatically by water temp. If T2 is not
connected ,panel determines the mode.
When T3 is not connected, Auto-Fan in Heat mode is active
Mode is selected from the wall panel to all the Main Boards
Air-Mixing algorithm in Heat (15 seconds every 6 minutes) when Set-point = Ambient Temp.
IR receiver and panels (options 2-4) can be connected to each MIGA and override the main panel (option
1) command. “Last Operation Rules”
ON
IRR/1
Additional IR receiver 14
15
16
JMP2
FAN (3A)
A
B
0
12V
0
A
0
12V
Wall-mount Room panel
ETN/MIGA/AB
(Can be connected to
Master board only)
B
Option 1/A
A
0
12V
B
Flush-mount Room panel
FMH/MIGA/AB
(Can be connected to
Master board only)
4x6005MA
Shield
Red
Led
Green
Led
On/Off button
Press 5 Seconds
IR Receiver
M101P/02/C
Option 2
Option 3
Option 1/B
Option 4
POWER
SUPPLY
OR
Short – 4 pipe
Open – 2 pipe
To other MIGA
Boards (Slaves)
Short – Slave
Open – Master
Heat
valve
Cool
valve
One
valve
C
N
F2
2-Pipe
Config.
(or)
4-Pipe
Config.
Multi MIGA board connection diagram
A
B
BA
MIGA Board
BA
MIGA Board
IR Receiver
(option)
ETN/MIGA/AB
(connected to
Master only)
A
B
A
To other
MIGA Boards
(Slaves) B
Master
JMP2=OPEN
Slave
JMP2=SHORT
End of line
resistor
120Ω
88
ON
Receiver
TIMER
ON/OFF
Green
Led
Receiver
Date:
Title:
MIGA AB
20/02/10
meitav-tec
Tel: +972-3-9626462
Fax: +972-3-9626620
e-mail: support@meitavtec.com Rev.1 Original 20/02/10
Print name: MIG103HZ Drawn: M.Ruchansky, P.Rechtman
Checked: S.Lukin
Approved: A.Samocha
Software: 0940xx03
Checksum: 50D3
File: MIGA-AB.vsd
/