Description
The addressable Conventional Zone Module GWM-
55000-845 serves for the integration of conventional
detectors into the bidirectional communication on the
ADM loop with Apollo/Discovery protocol.
The address is easily selected by means of a built-in DIL
switch. The module has an integrated dual-isolator and
is fi tted into a plastic case.
ADM loop technology with
Apollo/Discovery protocol
Integration of conventional detectors
into the ADM loop
Setting of module address by means
of address switch
Integrated dual-isolator
Specifi cations
Operating voltage Supply through loop voltage
Current consumption 4mA (quiescent)
Ambient temperature -20°C to +70°C
Dimensions L × W × H 150 × 90 × 48 (mm)
Colour white
Weight 230g
Approval VdS G201094
Order number 249075
Order name Conventional Zone Module/Anal./XP95/Apo GWM-55000-845
/