1.6 Operating limits
The basic specification of the fan coil and heat exchanger is given below:
Fan coil and heat exchanger
Maximum temperature of heat vector fluid = 85°C
Minimum temperature of refrigerant fluid = 5°C
Maximum working pressure = 8 bars
Power supply voltage 230V - 50Hz
Model MV
Weight (kg)
Weight with packaging Weight without packaging
Model 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
3-2T
14 16 21 22 24 25 30 39 40 13 14 18 19 21 22 26 35 36
3-4T
15 19 27 28 30 31 37 47 48 14 17 24 25 27 28 33 43 44
3-4T/2T
15 22 33 34 36 37 44 55 56 14 20 30 31 33 34 40 51 52
4-2T
14 18 24 25 27 28 34 45 46 13 16 21 22 24 25 30 41 42
Rows
4-4T
15 21 29 30 32 33 40 52 54 14 19 26 27 29 30 36 48 50
Water content
Water content (litres)
Model
1 2 3 4 5 6 7 8 9
3
0,5 0,6 0,9 0,9 1,3 1,6 1,7 1,9 1,9
4
0,7 0,8 1,3 1,3 1,7 2,2 2,4 2,8 2,8
4T
0,2 0,2 0,3 0,3 0,4 0,5 0,5 0,6 0,6
Rows
3-4T/2T
0,4 0,4 0,6 0,6 0,8 1,0 1,0 1,2 1,2
Motor Absorption
Motor Absorption
Model
1 2 3 4 5 6 7 8 9
W
33 40 49 57 61 88 103 130 176
230 V/
50 Hz
A
0,16 0,18 0,23 0,26 0,27 0,39 0,47 0,58 0,78