Omega FST-200 and FST-300 Series Owner's manual

Type
Owner's manual

Omega FST-200 and FST-300 Series are general-purpose flow switches providing reliable detection of low or no-flow in relatively clean, non-coating media. The FST-200 Series is designed for liquid flow measurement, with a set point range of .04 to 3 fps (.012 to .91 mps) and a repeatability of ±.5% of set point at fixed temperature. The FST-300 Series, on the other hand, is intended for gas flow measurement, with a set point range of 1 to 90 fps (.3 to 27 mps) and a repeatability of ±.5% of set point at fixed temperature.

Omega FST-200 and FST-300 Series are general-purpose flow switches providing reliable detection of low or no-flow in relatively clean, non-coating media. The FST-200 Series is designed for liquid flow measurement, with a set point range of .04 to 3 fps (.012 to .91 mps) and a repeatability of ±.5% of set point at fixed temperature. The FST-300 Series, on the other hand, is intended for gas flow measurement, with a set point range of 1 to 90 fps (.3 to 27 mps) and a repeatability of ±.5% of set point at fixed temperature.

1
2
3
INTRODUCTION/TABLEOFCONTENTS StepOne
Offered in liquid and gas sensor types, the general purpose flow switch provides reliable low or noflow
detectionofrelativelyclean,noncoatingmediawithone1Arelayoutput.Liquidexamplesincluedwaterand
aceticacid.AvailableinPolypropylenePPSorPVDF,theshortflowsensorisusedinpipeorductingfrom½”
to11/2”,andthelongflowsensorisusedin2”andup.Theflowswitchsetpointmaybeadjustedfrom0.,04
to3 fps in liquids or 1 to 90fpsingasesasalowflow alarm.The flowsensorisbestappliedinapplications
withrelativelyconstanttemperatures.
NewFeatures
RuggedPolypropylenePPSorPVDFsensorforcorrosiveliquidsandgasses.
AdjustablesetpointwithLEDforflowornoflowstatusindication.
60VArelayselectableNOorNCviapowersupplywiringpolarity
SolidStatesensorisnotdamagedbyoverrangingflowvelocities.
TableofContents
Specifications:........................................................................................................................................................4
MakeaFailSafeSystem:...........................................................................................................................4
Dimensions: .........................................................................................................................................................5
Configurations:...........................................................................................................................................5
SafetyPrecautions:................................................................................................................................................6
Introduction: .........................................................................................................................................................7
Technology:................................................................................................................................................7
InitializingSequenceforFST200Series:...................................................................................................7
SetPoints:..................................................................................................................................................7
Installation: .........................................................................................................................................................8
Wiring: .........................................................................................................................................................9
SupplyVoltage:..........................................................................................................................................9
SignalOutput:............................................................................................................................................9
WiringtoanOmegaEngineeringController:.............................................................................................9
WiringtheRelayOutput:..........................................................................................................................10
WiringasaPChannelorNChannelOutput:..........................................................................................11
Calibration: .......................................................................................................................................................12
SetPoint:..................................................................................................................................................12
Maintenance:.......................................................................................................................................................13
CleaningProcedure:..................................................................................................................................13
TestingtheSensor(FST200SeriesOnly):...............................................................................................13
TestingtheSensor(FST300SeriesOnly):...............................................................................................14
4
SPECIFICATIONS StepTwo
Setpointrange: FST200:.04to3fps(.012to.91mps)
FST300:1to.90fps(.3to27mps)
Factorysetpoint: FST200:.2fps(.06mps)
FST300:10fps(3mps)
Repeatability: ±.5%ofsetpoint@fixedtemp.
Responsetime: 110seconds
Setpointadjust.: Potentiometer
LEDindication: FlowStatus
Viscosityrange: 1200centipoise(FST200seriesonly)
SupplyVoltage: 1436VDC
Consumption: 70mAmaximum
Contacttype: (1)SPSTrelay
Contactrating: 60VA,1Amax
Contactoutput: SelectableNO/NC
Processtemp.: F:32°to140°
C:to60°
Electronicstemp. F:‐40°to140°
C:‐40°to60°
Pressure: 150psi(10bar)@25°C.,derated@1.667
psi(.113bar)per°C.Above25°C.
Sensorrating: NEMA4X(IP65)
SensorMaterial: FST211/221/321/323: PPPPS
FST212/222/322/324: PVDF
Cablejacketmat.: FST211/221/321/323: PP
FST212/222/322/324: PFA
Cabletype: 4conductor,#22AWG(shielded)
Cablelength: 10’(3m)
Processmount: 3/4"NPT(3/4”G/Rp)
Mount.Gasket: FKM(Gversiononly)
Classification: Generalpurpose
CEcompliance: EN61326EMC
EN610101safety

Make a FailSafe System:Design a failsafe system that accommodates the possibility of switch and/or
power failure.OMEGA ENGINEERING recommends the use of redundant backup systems and alarms in
additiontotheprimarysystem.Addingaredundantalarmswitchtothesystemisacosteffectivemeans
topreventcostlyrundryissues.

5
DIMENSIONS StepThree
LongSensor(FST221/222/323/324)
ShortSensor(FST211/212/321/322)
Configurations(LiquidFlowSwitches):
Part
Number
Length
Material
(body)
Material
(cable)
Thread
(insidexoutside)
FST211SPST Short(3”) PPPPS Polypropylene ¾”NPTx¾”NPT
FST212SPST Short(3”) PVDF PFA ¾”NPTx¾”NPT
FST221SPST Long(4.5”) PPPPS Polypropylene ¾”NPTx¾”NPT
FST222SPST Long(4.5”) PVDF PFA ¾”NPTx¾”NPT
Configurations(GasFlowSwitches):
Part
Number
Length
Material
(body)
Material
(cable)
Thread
(insidexoutside)
FST321SPST Short(3”) PPPPS Polypropylene ¾”NPTx¾”NPT
FST322SPST Short(3”) PVDF PFA ¾”NPTx¾”NPT
FST323SPST Long(4.5”) PPPPS Polypropylene ¾”NPTx¾”NPT
FST324SPST Long(4.5”) PVDF PFA ¾”NPTx¾”NPT
Note:Theaboveproductsshipwithastandard10’cablelength.Adding‐25”totheendofthepartnumber
indicatesthattheproducthasa25’cablelength(ex.FST211SPST25).Adding‐50”totheendofthepart
numberindicatesthattheproducthasa50’cablelength(ex.FST321SP
ST50).

6
SAFETYPRECAUTIONS StepFour
Aboutthis Manual:PLEASEREADTHE ENTIRE MANUALPRIOR TOINSTALLING OR USINGTHIS PRODUCT.
ThismanualincludesinformationonallmodelsofOmegaEngineeringThermalDispersionFlowSwitches:FST
200andFST300series.Pleaserefertothepartnumberlocatedontheswitchlabeltoverifytheexactmodel
whichyouhavepurchased.
User’s Responsibility for safety:Omega Engineering manufactures a wide range of flow switches and
technologies, while each of these sensors is designed to operate in a wide variety of applications; it is the
user’sresponsibilitytoselectasensormodelthatisappropriatefortheapplication,install itproperly,perform
tests of the installed system, and maintain all components. The failure to do so could result in property
damageorseriousinjury.
Proper Installation and Handling:Because this is an eclectically operated device, only properly trained
staffshouldinstalland/orrepairthisproduct.Use apropersealantwithallinstallations. Note: Alwaysinstall
the 3/4” FKM gasket with all versions of Flow switches withmetric threads. The G threaded version will not
seal unless the gasket is properly installed. Never over tighten the sensor within the fitting, beyond a
maximumof80inchpoundstorque.Alwayscheckforleakspriortosystemstartup.
Material Compatibility:The FST200 and FST300 series sensors are available in two different wetted
materials. Models FST211/221/321/323 are made of Polypropylene (PP) with PPS tips. Models FST212/
222/322/324 are made of Polyvinylidene Fluoride (PVDF). Make sure that the model you have selected is
compatible with the application liquid. To determine the chemical compatibility between the sensor and its
applicationliquids,refertoanindustryreferencesuchastheCompassCorrosion.
WiringandElectrical:Thesupplyvoltageusedtopowerthesensorshouldneverexceedamaximumof36
voltsDC.Electricalwiringofthesensorshouldbeperformedinaccordancewithallapplicablenational,state,
andlocalcodes.
Flammable,ExplosiveandHazardousApplications:DONOTUSETHEFST200orFST300SERIESGENERAL
PURPOSEFLOWSWITCHESINHAZAROUSLOCATIONS.
Warning
Theratingfortherelayis60VA,1Ampmax.
Omega Engineering’s Thermal Dispersion flow switches are not recommendable for use with
electricallychargedapplicationliquids.Formostreliableoperation,theliquidbeingmeasuredmay
needtobeelectricallygrounded.
Thesensingtipofthesensormustalwaysbesubmersedintheliquidandneverexposedtoair.
Theliquidtemperaturemustremainconstantandnotchangethroughouttheprocess.

7
INTRODUCTION StepFive
Technology:TheThermalDispersionflowswitchesmeasureliquidorgastemperaturetodeterminechanges
in flow velocity.As fluid flows across the sensing tips, the temperature is reduced proportionately as a
functionoftheflowrate.Whenatemperatureorvelocityshiftreachestheuserdefinedsetpoint,theswitch
changesstateindicatingtheappropriateflowcondition(flowofnoflow).
OMEGAENGINEERING’s sophisticatedelectronics convert thetemperatureshift intoa signalwhich indicates
whetheraflowornoflowconditionoccurs.Dependingonhowthesensoriswired,thissignalmaybewired
fornormallyopenornormallyclosedcircuits.
OMEGAENGINEERING’sThermalDispersionflowswitcheshavenomovingpartstoclogorfoul,makingthem
suitableforaverity ofapplications,includingnoncoatingandnonscalingliquids.TheFST200seriesdirectly
measuremassflowandcanoperateoverboardrangeofliquidsfrom0.4to1.2specificgravityand1to300
cp.
InitializingSequenceforFST200ser
ies:Whentheflowswitchispoweredupwhilesubmersed,theFST200
series will immediately indicate flow before switching to its correct state.A time delay may be used to
eliminatetheinitializationsequence.OmegaEngineering’sthermaldispersionrelaycontrollersfeaturea0to
60secondti
medelayforyourconvenience.
SetPoints:TheFST200seriesliquidflowswitchsetpointisfactorycalibratedto0.2fpsandtheFST300gas
flowswitcharesetto10fps.Toconvertfeet/sectoGPM,pleaserefertothechartbelow.
FST200Series
FlowRatevs.Velocity
(gpmvs.fps)
FST300Series
FlowRatevs.Velocity
(scfmvs.fps)

8
Installation StepSix
The FST200 series flow switch must always be in contact with
the liquid being measured. The FST300 series flow switch must
never be submersedin liquid.Both flow switches feature a 3/4”
NPTthreadswhich will allowittobe used with varioustypesof
fittings.Besuretochecktheinsertiondepthofth
eflowswitchin
thefittingafteritisinstalled.Seethediagramtotherightforthe
recommendedinsertiondepth.
Thetwotipofthesensoraretobeperpendiculartothe
flow(asseentotheright).Nevermountthetipswith
oneinfromtoftheothe
r.
When using any type of fitting, the orientation as well as the
insertiondepth ofthe flowswitchin thepipeis critical. Seethe
diagramtotherightfortherecommendedorientation.

Warning
Theflowswitchtipshaveathinplasticwallwhichmaybedamagedifdroppedorinstalledimproperly.
The FST200series flowswitch isdesigned foruse in liquid. For bestresults, avoid installing theFST200
serieswherebubblesarepresentorwherethetipsoftheswitchmaybeoutoftheliquid.
TheFST300seriesflow switchisdesigned for usin gas applications. Forbest results, avoidinstalling the
FST300serieswhereitmaybesubmersedinliquid.
Always install the FKM gasket with all versions of the model FST212/222/322/324. The G threaded
versionwillnotsealunlessthegasketisproperlyinstalled.
The two temperature probes (tips) must always be perpendicular to the flow (see the flow at the same
time).

9
WIRING StepSeven
Supply Voltage:The supply voltageto theThermal Dispersion flow switch should never exceed a minimum
outputof14VDCormaximumoutputof36VDC.
Required Cable Length:Determine the length of the cable required between the Thermal Dispersion flow
switch and its point of termination. Allow enough slack to ensure the easy installation, removal and/or
maintenance of the sensor. The cable length may be extended up to a maximum of 1000 ft, using a well
insulated14to20gaugeshieldedfourconductorcable.
WireStripping:Usinga10gaugewirestripper,carefullyremovetheouterlayerofinsulationfromthelast1
1/4” ofthe sensor’scable. Unwrapand discardthe exposed foil shieldfromaround thesignal wires,leaving
the drain wire attached if desired. With a 20 gauge wire stripper, remove the last 1/4” of the colored
insulationfromthesignalwires.
SignalOutput(RelaySwitching):
Allows the sensor to switch a small load on or off
directly, using an internal relay rated below 60 VA.
TheNO/NCstatusissetby thepolarityofthevoltage
feedingtheredandblackwires.Thegreenwireisthe
commonfortherelayandthewhitewireistheNOor
NC,dependingonthepolarityofredandblack.
NormallyOpenWiring:
WiringtoanOmegaEngineeringController:
LVCN131/141SeriesController
FLCN100SeriesController

10
WIRING StepSeven
WiringtheRelayOutput:TheFlowswitchrelayoutputcanbewiredasadrycontacttoaVDCorVACpower
source. The flow switch does require 1436 VDC power to operate the sensor and switch the relay. All
installationsbelowidentifyadryswitchstateasthenormalpositionoftherelay.
SwitchingaNormallyOpenDCLoad(OpenduringFlow,ClosedduringNoFlow):
The Red wire connects to Positive (+) of the power
supplyandtheBlackwireconnectstoNegative().The
LOAD can be attached to either the Green or White
wires.Completeth
ecircuitbyconnectingtheGreento
(+) VDC power or White to () VDC power (see
illustrationtotheright).
SwitchingaNormallyClosedDCLoad(ClosedduringFlow,OpenduringNoFlow):
The Black wire connects to positive (+) of the power
supplyandtheRedwireconnectstoNegative().Th
e
Load can be attached to either the Green or White
wires. Complete the circuit by connecting the Green
to (+) VDC power or White to () VDC power (see
illustrationtotheright).
SwitchingaNormallyOpenACLoad(OpenduringFlow,ClosedduringNoFlow):
TheRedwire connects toPositive(+)of theDC power
supplyandtheBlackwireconnectstoNegative().The
LOADcanbeattachedtotheGreenwireandtheHotof
the VAC power. Connect the white to the Neutral of
the VAC power (see illustration to the right).Low
voltageVACislessthan36VAC.
SwitchingaNormallyClosedACLoad(ClosedduringFlow,OpenduringNoFlow):
The Black wire connects to Positive (+) of the DC
powersupply andthe Redwire connects toNegative
().TheLOAD canbe att
achedtotheGreenwire and
theHot oftheVAC power.Connect the Whiteto the
Neutral of the VAC power (see illustration to the
right).LowvoltageVACislessthan36VAC.
ForallSensorWiringdiagramsabove:
SensorPower:RedandBlackWires(36VDCMax.)
Rela
yRating: GreenandWhiteWires(60VA,1AMax.)

11
WIRING StepSeven
WiringasaPChannelorNChanneloutput:TheFlowswitchcanbesubstitutedforeitheraPChannel(PNP,
Sourcing)outputorNChannel(NPN,sinking)output.
NormallyOpenDCLoadasaPChannelOutput(OpenduringFlow,ClosedduringNoFlow):
To wire as a NO PChannel o
utput follow the
directions below. The Red Wire connects to Positive
(+) of the power supply and the Black wire connects
toNegative().TheGreenwireisjumpingtotheRed
wire while the White wireis connectedto the LOAD.
JumpertheLOADbacktotheNegative()tocomplete
thecircui
t.
NormallyClosedDCLoadasaPChannelOutput(ClosedduringFlow,OpenduringNoFlow):
To wire as a NC PChannel output, follow the
directionsbelow. TheBlackwire connectsto Positive
(+)ofthepowersupplyandtheRedwireconnectsto
Negative (). The Green wire is jumping to the Black
wire while the White wireis connectedto the LOAD.
JumpertheLOADbacktotheNegative()tocomplete
thecircuit.
NormallyOpenDCLoadasaNChannelOutput(OpenduringFlow,ClosedduringNoFlow):
To wire as a NO NChannel output, follow the
directions below. The Red wire connects to Positive
(+) of the power supply and the Black wire connects
toNegative().ThewhitewireisjumpingtotheBlack
wirewhile theGreenwire is connectedto theLOAD.
JumpertheLOADbacktothePositive(+)tocomplete
thecircuit.
NormallyClosedDCLoadasaNChannelOutput(ClosedduringFlow,OpenduringNoFlow):
To wire as a NC NChannel output, follow the
directionsbelow. TheBlackwire connectsto Positive
(+) of the directions below. The Black Wire connects
toNegative ().The white wire is ju
mping to theRed
wire while the White wireis connectedto the LOAD.
JumpertheLOADbacktoPositive(+)tocompletethe
circuit.
ForallSensorWiringdiagramsabove:
SensorPower:RedandBlackWires(36VDCMa
x.)
RelayRating: GreenandWhiteWires(60VA,1AMax.)

12
CALIBRATION StepEight
Set Point:If the preset factory calibrationis notadequate for your application,follow the calibration steps
listedbelow.
Note: The switch’s internal LED will be on when the switch detects noflow and will off when the switch
detects flow, regardless of the polarity of the Red and Black wires.Reversing the Red and Black wires will
reversethepolarityoftherelayswitch,butnottheinternalLED.
1. Install the fitting and flow switch as described in the Installation section of this manual. Turn the flow
switch and controller power on and adjust the flow rate to the application setting. If the medium to be
sensed is likely to be subject to any temperature variation, the flow switchshould be set as the highest
normaltemperaturelikelytobeencountered.
2. Locate the potentiometer knob at the top of the flow switch. The red LED is visible through the
potentiometer.Theadj
ustmentisasingleturn270°potentiometer.Theinitialresponsetimeoftheflow
switchafteradjustmentis1to10seconds.Adjustthepotentiometerinslowincrementsandwaitforthe
response.
a. LEDisON‐IftheLEDison,slowlyadjustthepotentiometercounterclockwise,withasmallflathead
screwdriveruntiltheLEDturnoff.
b. LED is OFF‐
If the LED is off, slowly adjust the potentiometer clockwise. with a small flat head
screwdriveruntilthelightturnson.
3. AdjustthepotentiometerbackandforthwheretheLEDisswitching,eventuallysettlingforwheretheLED
isOFF(thisisthelowflowstatefortheswitch).
a. Iftheflowisincreased,theLEDwillremainOFFindicatingaflowcondition
b. Iftheflowisdecrease,theLEDwillturnONindicatinganoflowcondition.
4. Verifythatthenewcalibrationiscorrectbyloweringthesystemflowratebelowthesetpointandcheckto
seethattheredLEDturnson.ThenincreasetheflowrateabovethesetpointandverifythattheredLED
turnsoffaccordingly.
FST200SeriesFlowSwitch
(LiquidOnly)
Potentiometer
Location
FST300FlowSwitch
(GasOnly)

13
MAINTENANCE StepNine
General:TheFlowswitchrequiresnoperiodicmaintenanceexcept tocleanoffanydepositsorscalingfrom
the sensor tip as necessary. It is the responsibility of the user to determine the appropriate maintenance
schedule,basedonthespecificcharacteristicsoftheapplicationliquids.
CleaningProcedure:
1. Power: Make sure that all power to the sensor, controller and/or power supply is completely
disconnected.
2. Sensor Removal: Make sure that the flow is off and the pressure is down prior to removing the Flow
switch.Carefully, remove the sensor from the installation. Replace the sensor with a 3/4” NPT plug to
insure that the liquid doe
s not leak out during this procedure. Do not reinstall the Flow switch if the
threadsaredamaged.
3. Cleaningthe sensor: Use a soft bristle brush and mild detergent, carefully wash the Thermal Dispersion
flowswitch.Donotuseharshabrasivessuchassteelwoolorsandpaper,whichmig
htdamagethesurface
sensor.Donotuseincompatiblesolventswhichmaydamagethesurfacesensor.Donotuseincompatible
solventswhichmaydamagethesensor’sPP/RytonorPVDFplasticbody.
4. Sensor Installation: Follow the appropriate steps of installation as outlined in the installation section of
thismanual.
TestingtheSensor(FST200SeriesOnly):
1. Immersingtheswitch:Placetheswitchinacupofwater.Makesurethetipsaresubmersedinthewater.
2. Power: Turn on power to the switch with Red to (+) and Black to ().You can reverse the polarity if
desired.
3. NoFlow/Flow Test: With the switch setting still in the cup, wait until the Red LED turns ON (noflow
condition).
a. SwirltheswitchinthecupandwaituntiltheRedLEDturnOFF(flowcondition).
b. Stopswirlingthesensorand letitrestinthecupwaitingfortheRed LEDtoturnONagain(noflow
condition).
c. Repeattheabovetwosteps.
4. RelayTest: Connect amultimeter(settoreadOhms)totheWhite andGreenWires.Performtheabove
NoFlow/Flowtestwiththemultimeterconnecttoobservetheactuationoftherelay.
a. With Red to (+) and Black to (), the multimeter will reada small resistanceduring noflow (closed
relay)andOLduringaflowcondition(openrelay).
b. Reverse Polarity [Red to () and Black to (+)] to see the multimeter read OL during a noflow state
(openrelay)andasmallresistanceduringaflowcondition(closedrelay).
TheNoFlow/Flowtestdeterminesiftheswitchiscapableofsensingthechangesbetweennoflowandflow.
TheRelaytestdeterminestheabilityoftherelaytoswitchbetweenanoflowandflowcondition.Thisisthe
basictesttodeterminefunctionalityofthesensor.

14
MAINTENANCE StepNine
TestingtheSensor(FST300SeriesOnly):
1. Creatinga NoFlow TestPoint: The purpose ofthis step is tocreate anoflow statefor thesensor to be
tested against.Sincethis isa low flow switch, even abuildings HVAC system can create a flow that the
sensorcanread.
a. Placetheswitchonatableandplaceanemptycupoverthesensingtips.
b. Thecupwillactlikeashieldtoprotectthesensorfromairflow.
2. Power: Turn on power to the switch with Red to (+) and Black to ().You can reverse the polarity if
desired.
3. NoFlow/FlowTest:Withtheswitch setting still under thecup,waituntiltheRedLED turnsON(noflow
condition).
a. Remove the cup and move the sensor in air and observe when the Red LED turn OFF (flow
condition).
b. Place thesensor onthe tableand placethe cup over thesensor andletit rest waitingfor the
RedLEDtoturnONagain(noflowcondition).
c. Repeattheabovetwosteps.
4. RelayTest: Connect amultimeter(settoreadOhms)totheWhite andGreenWires.Performtheabove
NoFlow/Flowtestwiththemultimeterconnecttoobservetheactuationoftherelay.
a. With Red to (+) and Black to (), the multimeter will read a small resistance during noflow
(closedrelay)andOLduringaflowcondition(openrelay).
b. Reverse Polarity [Red to () and Black to (+)] to see the multimeter read OL during a noflow
state(openrelay)andasmallresistanceduringaflowcondition(closedrelay).
TheNoFlow/Flowtestdeterminesiftheswitchiscapableofsensingthechangesbetweennoflowandflow.
TheRelaytestdeterminestheabilityoftherelaytoswitchbetweenanoflowandflowcondition.Thisisthe
basictesttodeterminefunctionalityofthesensor.

15

16
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Omega FST-200 and FST-300 Series Owner's manual

Type
Owner's manual

Omega FST-200 and FST-300 Series are general-purpose flow switches providing reliable detection of low or no-flow in relatively clean, non-coating media. The FST-200 Series is designed for liquid flow measurement, with a set point range of .04 to 3 fps (.012 to .91 mps) and a repeatability of ±.5% of set point at fixed temperature. The FST-300 Series, on the other hand, is intended for gas flow measurement, with a set point range of 1 to 90 fps (.3 to 27 mps) and a repeatability of ±.5% of set point at fixed temperature.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI