LSC APS Installation guide

Category
Electrical wallplates
Type
Installation guide

This manual is also suitable for

LSC APS, a versatile and feature-rich device, offers a range of capabilities to enhance your lighting control experience:

  • Modular Design: The unit comprises two detachable sections, allowing for convenient mounting and separate storage of the electronics section until the installation site is ready.

  • Easy Installation: Designed for straightforward mounting, either directly to a wall or using optional Unistrut brackets, the LSC APS simplifies the installation process.

  • Comprehensive Connectivity: Connect various lighting loads with 10-amp or 25-amp hardwired output versions, providing flexibility for diverse lighting setups.

LSC APS, a versatile and feature-rich device, offers a range of capabilities to enhance your lighting control experience:

  • Modular Design: The unit comprises two detachable sections, allowing for convenient mounting and separate storage of the electronics section until the installation site is ready.

  • Easy Installation: Designed for straightforward mounting, either directly to a wall or using optional Unistrut brackets, the LSC APS simplifies the installation process.

  • Comprehensive Connectivity: Connect various lighting loads with 10-amp or 25-amp hardwired output versions, providing flexibility for diverse lighting setups.

Wall-Mount GEN VI and APS Installation Guide
All electrical work must be carried out by a suitably qualified person. Illustrations below show APS units. GEN VI units are similar.
The unit is comprised of two sections. The front section (containing all of
the electronics) is attached to the rear section by two hinges located at
the bottom and the front section can be completely detached from the
rear section to allow better access to the mounting points and the supply
and load cable terminations. This also allows the rear section to be
mounted and connected whilst the front section is safely stored until all
other trades have completed their work and the area is safe and clean.
Disassembly
To completely detach the front
section, remove the 4 large
screws as shown then unfold
the front section. Use a 10mm
spanner to remove the 2 nuts
holding the metal support straps
and lift the straps off the bolts.
Replace the nuts to retain the
fibre washers. Carefully unfold
the front section to the fully open
position.
Disconnect the 3-phase cable to
the front section from the input
terminal block on the rear section
and un-bolt the earth connection.
Cut the cable tie that secures the
3-phase input cable.
For hardwired output versions only
10-Amp output
versions
Un-plug the load
connector plugs
from the load
terminal blocks on
the rear section.
These
connections are
tight and will need
to be prised out.
The front section can now be removed from the rear section by sliding it sideways off the split hinges.
Mounting the Rear Panel and Power Connections
Mount the rear section either directly to the wall or to Unistrut
observing the minimum clearances (sides 150mm, top and
bottom 155mm). Unistrut brackets are available from LSC.
Remove the cable access knockouts where required.
Connect the 3-phase input power and earth to the input
terminal block and earth stud.
For GEN VI Dimmers only: The rating of the neutral
conductor feeding the dimmer must be at least 1.25 times that
of rated limit of any of the active phase conductors. This is
because various combinations of dimmer drive will result in a
neutral current higher than the line current due to the phase
control characteristics of these type of dimmers. For example,
a 40Amp 3 phase supply must have a neutral rated at 50Amps.
Connect all of the load cable earths to the earth stud.
For 10-amp output hardwired output versions only.
Connect the L & N load cables to the load terminal blocks.
For 25-amp output hardwired output versions only.
Position the load cables in the rear section so that they can be
connected when the terminal block when the front section is re-
fitted.
Rear Panel Spacing
Test all load circuits.
Reassembly.
Ensure that the 3-phase power to the unit is OFF.
Slide the front section onto the rear section hinges. If access is tight, the screw and washer that restrict the side movement of the front
section can be removed to allow the from section to slide onto the hinges. Replace the screw and washer once the hinges are engaged.
For 10-Amp hardwired output versions only. Plug the load connector plugs into the load terminal blocks.
For 25-Amp hardwired output versions only. Replace the output terminal block then connect the L & N load cables to it.
Re-connect the 3-phase input cable of the front section to the input terminal block on the rear section, bolt the earth connection and cable tie
the input cable to the rear section.
Lift up the front section and re-attach the metal support straps. Close the front section ensuring no load or mains cable can become
damaged then re-attach the 4 large screws that secure the front section to the rear section.
Warning: Do not megger test any load circuits when they are connected to the unit electronics.
LSC Control Systems ©
+61 3 9702 8000
www.lsccontrol.com.au
Version 1.2
September 2022
Optional
Unistrut
brackets
P1 P2 P3 N E
Min 150 mm
Min 155 mm
Slip Hinges
underneath
Remove two large
screws to open
Remove two large
screws to open
Cut cable tie
Disconnect 3-phase
power and earth that
feeds the front section
Load terminal
blocks
Load connector plugs
shown partially
disconnected
Remove
10mm nut
Support
strap
APW6/25A
Input terminal
block
  • Page 1 1

LSC APS Installation guide

Category
Electrical wallplates
Type
Installation guide
This manual is also suitable for

LSC APS, a versatile and feature-rich device, offers a range of capabilities to enhance your lighting control experience:

  • Modular Design: The unit comprises two detachable sections, allowing for convenient mounting and separate storage of the electronics section until the installation site is ready.

  • Easy Installation: Designed for straightforward mounting, either directly to a wall or using optional Unistrut brackets, the LSC APS simplifies the installation process.

  • Comprehensive Connectivity: Connect various lighting loads with 10-amp or 25-amp hardwired output versions, providing flexibility for diverse lighting setups.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI