Mounting the NAE/NIE in a panel
To mount the network engine in a panel, follow
these requirements:
• Mount the panel in accordance with the
manufacturer’s instructions.
• Mount the network engine in the panel following
the guidelines in the Location considerations and
Mounting sections of this document.
Wiring Overview
Power supply, network, and
communication connections
See Figure 4 for the location of the power supply
terminal, network communication terminals,
Ethernet jack, and modem jack.
Depending on the model, the network engine
can connect to an MS/TP field bus trunk, an N2
Bus trunk, or a LonWorks network trunk. Also, all
network engines support two vendor integrations,
such as two Modbus, two M-Bus, or one of each.
Or, if a KNX integration is required, three KNX IP
Gateways are supported for one network engine.
See Table 15 for a list of all supported dual trunk
applications. The rules, guidelines, and wiring
considerations for each type of network or field bus
application are provided in tables of this document.
Power supply
Important: Install the data protection battery
before applying 24 VAC power to the network
engine. See the Installing the data protection
battery section.
In North America, use a Class 2, 24 VAC power
supply with a 50 VA minimum output. Outside North
America, use a 24 VAC SELV transformer at the
appropriate rating. The minimum input voltage for
the network engine to operate properly is 20 VAC.
See the Technical specifications section.
Use a dedicated power supply to the network
engine only. Do not connect any other loads to the
power supply. Additional loads may cause noise
interference.
Ethernet port
The Ethernet port, labeled ETHERNET, is an 8-pin
RJ-45 network port for connecting the network
engine to Ethernet IP networks. Network engine
can connect to Ethernet networks at 10 Mbps, 100
Mbps, or 1 Gbps. This Ethernet port provides IP
communications over the building network and
to any third-party integration that uses Ethernet
communication, including Modbus TCP, M-Bus TCP,
or KNX.
FC Bus terminal block
The two Field Controller (FC) Bus connections on an
NAE55 are 4-pin removable, keyed terminal blocks
labeled FC-A and FC-B.
The FC bus connections are optically isolated RS-485
ports with keyed 4-position terminal blocks that
communicate at 9.6k, 19.2k, 38.4k, or 76.8k baud.
Use an FC Bus port to integrate an N2 network,
BACnet MS/TP FC Bus trunk, or third-party network
into the Metasys system.
Note: N2, BACnet MS/TP, Modbus RTU, and
M-Bus have different protocols and network
requirements. Do not intermix N2, MS/TP,
Modbus, or M-Bus devices on the same FC Bus
port.
The SHD connections on the FC terminal blocks are
not connected to any earth ground connection.
The FC A and FC B terminal blocks are not
interchangeable.
LonWorks network terminal block
The LonWorks TP/FT-10 network connection,
available only on the network engine LonWorks
model, is a 3-wire removable, keyed terminal block.
The Shield connection on the LonWorks network
terminal block is an isolated terminal and is not
connected in the network engine. Use the LonWorks
terminal block to connect LonWorks networks to the
network engine.
Computer serial ports
The network engine has two RS-232-C serial
ports labeled RS232C A and RS232C B (Figure
4). Use either port to connect a Modbus RTU or
Zettler MXSpeak third-party integration. For more
information on how to use the serial port for third-
party vendor integration, refer to the application
note for the particular vendor integration you are
installing. Lastly, these RS-232-C serial ports do not
support external modems.
Universal Serial Bus (USB) ports
The two USB ports labeled USB A and USB B are
both configured as masters and are independent of
each other. At Release 10.0 or later, the use of a USB
port to connect an optional external modem is no
longer supported.
NAE55/NIE55 Installation Guide 5