PRODUCT DATA SHEET
SM CKDDCI 2-A.3 GB
2.2 CKD 045 DCI / GC 43 DCI
Model Indoor Unit CKD 045 DCI
Model Outdoor Unit GC 43 DCI
Installation Method CASSETTE
Characteristics Units Cooling Heating
Capacity - Nominal (Minimum ~ Maximum)
(1)
Btu/hr 41,300 (8,550 – 44,350) 46,050 (8,850 – 49,150)
kW 12.1 (2.5 – 13.0) 13.5 (2.6 – 14.4)
Power Input - Nominal (Minimum ~ Maximum)
( (1)
W 4,400 (1,400 – 5,150) 4,800 (950 – 5,600)
EER (Cooling) / COP (Heating)
(1)
W/W 2.75 2.8
Energy Efficiency Class - “D” “D”
Power Supply V/Ph/Hz 220-230/1/50
Rated Current (Nominal) A 19.5 21.3
Starting Current A <10
Circuit Breaker Rating A 32
INDOOR
Fan Type & Quantity CENTRIFUGAL x1
Fan Speed H/M/L RPM 810 650 590
Airflow
(2)
H/M/L m
3
/hr 1,600 1,330 1,200
External Static Pressure Min-Nom-Max Pa -
Sound Power Level
(3)
H/M/L dB (A) 63 57 53
Sound Pressure Level
(4)
H/M/L dB (A) 53 47 43
Moisture Removal (Nominal) L/hr 5.4
Condensate Drain Tube I.D. mm 19
Dimensions W/H/D mm 840 300 840
Weight kg 32(+6kg Panel)
Package Dimensions W/H/D mm 950 317 950
Packaged Weight kg 40(+6kg Panel)
Units per Pallet Units 6
Stacking Height Units 6
OUTDOOR
Refrigerant Control Electronic Expansion Valve
Compressor Type, Model Scroll
Motor type DCBL Inverter
Fan Type & Quantity Axial 2x 493mm
Fan Speed RPM 900-100 (continuous)
Airflow Max m
3
/hr 5,700
Sound Power Level Nom C/H dB (A) 69 70
Sound Pressure Level
(4)
Nom C/H dB (A) 56 58
Dimensions W/H/D mm 900 1255 340
Weight kg 110
Package Dimensions W/H/D mm 985 1395 435
Packaged Weight kg 120
Units per Pallet Units 3
Stacking Height Units 1
Refrigerant Type R410A
Refrigerant Charge (STD connected Tube
Length)
kg (m) 3.1 / 30
Additional Charge g/m 40
Connections
Between Units
Liquid Line In (mm) 3/8”
Suction Line In (mm) 3/4”
Max. Tubing Length m 70
Max. Height Difference m 30
Operation Control Type LCD Remote Control
Heating Elements kW BH 70W - optional
Others
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1.0 meter distance from unit.