10-1
TROUBLESHOOTING
SM VAR 1-A.1 GB
10. TROUBLESHOOTING
No. SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
1
Power supply indicator
(Red LED) does not light
up.
No power supply.
Check power supply. If power
supply is OK, check display
and display wiring, if OK,
replace PCB.
2
Indoor fan does not start
(Green LED lights up).
1. PCB problem
2. Capacitor
3. Fan motor
1. Switch to HIGH speed and
check indoor FAN motor
voltage to be higher then
198VAC, please also make
sure ther is no obstical
jamming the fan in this case
remove it.
In case that the voltage
is it’s significanly lower
replace PCB.
2. In case the fan is not
blocked and the voltage is
ok Replace the indoor fan
capacitor
3. If it still want run replace
the indoor fan motor
3
Indoor fan works when unit
is OFF.
PCB problem. Replace controller.
4
Compressor does not
start.
Electronics control
problem or protection.
Perform diagnostics, and
follow the actions described
below.
5
Compressor stops during
operation and Green LED
remains on.
1.OK temperature is in
set point
2.Electronic control or
power supply problem.
1.OK
2. Perform diagnostics, and
follow the actions described
below.
6
Compressor is ON but
outdoor fan does not work.
1. OK, unit is in High
pressure protection
2. PCB Problem or
outdoor fan capacitor/
motor.
1. OK
2. Switch unit to COOL mode,
HIGH speed with 16°C set
point (cooling) . Check outdoor
motor power supply voltage to
be higher than 198 VAC. If OK
replace capacitor, if it still wont
run replace motor.
In case the voltage is lower
then 198 VAC replace and the
main poer supply is higher
replace PCB.