D+H KA 66-TW-K Operating instructions

Type
Operating instructions
0N
0
100
200
300
400
500
600
700
800
900
500N
400N
300N
200N
100N
600N
99.823.95 1.0/06/08
© 2007 D+H Mechatronic AG, Ammersbek
Alle Maße in Millimeter. / All sizes in millimetre.
Technische Änderungen vorbehalten. /
Rights to technical modifications reserved.
D+H MechatronicAG • Georg-Sasse-Str. 28-32 • 22949Ammersbek • Tel. 40-605 65 239 • Fax 40-605 65 2 D- +49 +49 22 www.dh-partner.com
1/2
min.
max.
Ø3mm
1. 2.
B
C
A
40mm
51mm
C
Extent of supply
Drive unit with 2.5 m PVC-cable. Dependent on the type of window, different
bracket sets are available. Please order the bracket sets separately!
Instructions for use
Performance features
- applicable for daily ventilation and for SHEV according to
DIN EN 12101-2
- chain drives are equipped with micro-processor controlled motor- and
synchroelectronics BSY + for a precise synchronous run
- drive functions and features were individually programmable
(via software SW-BSY +)
- integrated 3 staged clamping protective system
passive clamping protection, because of reduced running
speed, while closing
active clamping protection with emergency shutdown and
reverse function while closing, if drives tensile load is bigger
than 150N in Closing Range II
connection of an additional closing edge, clamping protection
system on the drive is possible (Option -SKS)
- locking relief after closing
- two drive-chains for optimal power transmission into the sash frame
Running speed
Chain drive
KA 66-TW-K
Guarantee
You will get guarantee for all D+H products from verified handing
over of the system till up to 3 years after date of delivery, if mounting and
starting of the system was carried out by a distributor authorized by D+H.
The D+H guarantee will expire, if D+H components are connected with other
systems, or if D+H products are mixed with parts of other manufacturers.
2 years
Important notes
Inspection and maintenance has to be carried out according to D+H
maintenance notes. Repair of the drive unit is to be carried out exclusively by
D+H. D+H warranty and functioning guarantee is only valid with operation
on D+H smoke vent and ventilation control panels according to current
regulations which must be observed. Observe mounting instructions of
bracket set!
max. load (N)
stroke (mm)
Maximum pressure load per chain
Strictly observe maximum pressure load of the chain in order to ensure safe
and reliable performance of the chain drive!
Note: Maximum pressure load of the chain is not automatically
identical with maximum force of pressure of the drive !
Locking force (Soft Close Function)
1. Pull out covering stopper. Stick in screw driver and turn it to the right in
order to increase locking pressure.
2. Put covering stopper in again after adjustment.
3. Repeat on other drive side.
If factory-set locking pressure of ca. 150 N is not sufficient, it can be infinitely
increased up to ca. 250 N.
at Closure Range I
Safety notes
Operating voltage 230 VAC!
Observe maximum pressure load of the chain (see diagram below)!
Danger of violent pressure
in handaccessible area.
Do not exchange L+N and connect PE (protective conductor) otherwise
mal-function and destruction of drive possible!
Changing of cable outlet from left to right not possible. Observe safety
instructions. Mounting has to be carried out by electro- specialists only.
Only for inside mounting suitable. Use always rain detectors with danger of
rain (e.g. at domelights or roof windows).
Observe enclosed
red safety slip!
12.2 mm/s
16.1 mm/s)
(with tensile force (1/2 nominal load)
11,8 mm/s
5 mm/s
5 mm/s
- Closure Range -
III III
77 mm
23 mm
stroke
Type
1275
1625
650
1000
312,5
312,5
500
800
KA 66-TW065-K
KA 66-TW1-K
<
_
<
_
ABC
2/2
99.823.95 1.0/06/08
Technical data
Power supply 230 VAC, ±15%, 50 Hz
Power 60 VA
(see pressure load diagram)
- with pressure (nominal load) 12.2 mm/s (see Running speed)
nominal locking force 1 000 N
rating life >10 000 double strokes
operating factor 30 % (with cycle time 10 minutes)
housing aluminum
protective system IP 32 (only in connection with covering stoppers
delivered with bracket sets)
temperature range 5 (-5 to +75°C)
fire stability 30 min / 300°C
connection 2.5 m silicone cable
stroke length see type plate
locking relief
Running direction OPEN
Delivery status
Force of pressure 2x 300 N* +20% switch-off reserve
running time
- with tensile force (½ nominal load) 16.1 mm/s
force Closure Range III 2x 300 N + 20% switch-off reserve
force Closure Range II 2x 150 N safety switch-off force
force Closure Rrange I 2x 150 N - 2x 250 N (potentiometer) factory-set 150 N
running time Closure Range III 11.8 mm/s
running time Closure Range I and II 5 mm/s
anodized
activated
Running direction CLOSE
(see Running speed)
(see Running speed)
(see Running speed)
active clamping protection activated* (factory-set: 3 stroke repeatings)
Connection
yellow
green
Data
A
Data
B
*
yellow
green
Data
A
Data
B
*
KA 66-TW-K
KA 66-TW-K-SA/-SZ
with potential-free
position indication contact
* Programming connection
in the drive (terminal cover
opposite from connecting-
cable must be demounted).
* programmable with software SW-BSY+