Vacon VACON NXP Air cooled Installation guide

Type
Installation guide

This manual is also suitable for

vacon nxp
ac drives
ip00 modules
frames fr10 to fr14
installation manual
2 • vacon
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
INDEX
Document code: DPD00888A
Date: 17.01.2012
1. GENERAL .................................................................................................................................. 4
1.1 Type code ................................................................................................................................ 5
2. PRODUCT HANDLING ............................................................................................................... 6
2.1 Product type designation codes ............................................................................................. 6
2.2 Receipt of delivery .................................................................................................................. 6
2.2.1 Frames FR10 to FR12 ..................................................................................................... 6
2.2.2 Frames FR13 and FR14 ................................................................................................... 8
2.3 Receiving, unpacking and storing the product....................................................................... 9
2.4 Lifting the modules ................................................................................................................ 9
2.5 Lifting AC chokes ................................................................................................................. 10
3. REQUIREMENTS ..................................................................................................................... 11
3.1 Environmental requirements ............................................................................................... 11
3.2 Cabinets................................................................................................................................ 11
3.2.1 Cabinet installation for frames FR10 to FR12 .............................................................. 11
3.2.2 Cabinets for frames FR13 and FR14 ............................................................................. 12
4. INSTALLING AC CHOKES ........................................................................................................ 15
4.1 Installing AC chokes: Frames FR10 to FR12 ....................................................................... 16
4.2 Installing AC chokes: Frames FR13 and FR14 ..................................................................... 17
5. INSTALLING POWER MODULE ................................................................................................ 18
5.1 Preparing the enclosure ...................................................................................................... 18
5.1.1 Mounting dimensions for frames FR10 to FR12 ........................................................... 18
5.1.2 Mounting dimensions for frames FR13 and FR14 ........................................................ 19
5.2 Mounting the modules ......................................................................................................... 20
5.2.1 Mounting the power modules for frames FR10 to FR12 ............................................... 20
5.2.2 Mounting the modules for frames FR13 and FR14 ....................................................... 21
5.3 Grounding the power modules ............................................................................................. 21
6. INTERNAL CONNECTIONS ...................................................................................................... 23
6.1 Connecting internal power cables, FR10 to FR12 ................................................................ 23
6.2 Establishing internal busbar or cable connections, FR13 and FR14 ................................... 24
7. INSTALLING CONTROL UNIT .................................................................................................. 26
7.1 Mounting the control unit ..................................................................................................... 26
7.2 Connecting power supply and internal control cables ........................................................ 28
7.2.1 Frames FR10 and FR11 ................................................................................................. 28
7.2.2 Frame FR12 ................................................................................................................... 30
7.2.3 Frame FR13 ................................................................................................................... 31
7.2.4 Frame FR14 ................................................................................................................... 32
7.2.5 Control connections from NFE units to inverter module(s) ......................................... 32
8. PREPARING FOR EXTERNAL POWER CONNECTIONS ............................................................. 36
8.1 Installing mounting plate and input terminals in frames FR10 to FR12 ............................. 36
8.2 Routing the supply busbars in frames FR13 and FR14 ........................................................ 37
8.3 Installing fuses ..................................................................................................................... 38
vacon • 3
24-hour support +358 (0)40 837 1150 • Email: [email protected]m
1
8.3.1 Fuse installation instructions ....................................................................................... 40
8.4 Installing EMC grounding, FR10 to FR12 ............................................................................. 41
8.5 Installation of ferrite rings (option) on the motor cable ...................................................... 41
8.6 Connecting input and output power ..................................................................................... 42
9. AIR COOLING AND VENTILATION ............................................................................................ 43
9.1 Arranging ventilation of the enclosure ................................................................................ 43
9.2 Steering the internal air flow ............................................................................................... 45
9.3 Heat dissipation .................................................................................................................... 46
9.4 Temperatures measured during test run ............................................................................ 47
10. APPENDICES .......................................................................................................................... 48
10.1 Dimensional drawings, Power modules .............................................................................. 48
10.2 Dimensional drawings, AC chokes ....................................................................................... 53
10.3 Control unit .......................................................................................................................... 55
10.4 Optic fibre cables, signal listing and connections ............................................................... 56
10.4.1 FR10, FR11 and FR13 .............................................................................................. 56
10.4.2 FR12 and FR14 ........................................................................................................ 57
10.5 Additional fuse recommendations (Ferraz Chawmut) ......................................................... 58
4 • vacon GENERAL
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
1
1. GENERAL
This manual provides instructions for the installation of NXP FR10 to FR14 frequency converters in a
cabinet, switchgear, or any other enclosure. If you wish to receive your Vacon NXP drive cabinet-
mounted by the factory contact your nearest distributor.
Vacon NX drives of frames FR10 to FR12 embody 1 (FR10 and FR11) or 2 (FR12) power modules.
NX frames FR13 and FR14 are built of 2 to 4 non-regenerative front-end (NFE) units and 1 (FR13) or 2
(FR14) inverter units. Parallelly mounted chokes are also included in the delivery.
The NXP modules are available as both 6-pulse (standard) and 12-pulse (optional) supply versions.
The NXP product series frames FR10…FR14 comprise the following frequency converters:
Type code
(partial)
Frame size
Nominal
current [I
l
]
Type code
(partial)
Nominal
current [I
l
]
Voltage range 400500V Voltage range 525690V
NXP 0385 5 FR10 385A NXP 0261 6 FR10 261A
NXP 0460 5 FR10 460A NXP 0325 6 FR10 325A
NXP 0520 5 FR10 520A NXP 0385 6 FR10 385A
NXP 0590 5 FR11 590A NXP 0416 6 FR10 416A*
NXP 0650 5
FR11
650A
NXP 0460 6
460A
NXP 0730 5 FR11 730A NXP 0502 6 FR11 502A
NXP 0820 5 FR12 820A NXP 0590 6 FR11 590A*
NXP 0920 5 FR12 920A NXP 0650 6 FR12 650A
NXP 1030 5 FR12 1030A NXP 0750 6 FR12 750A
NXP 1150 5 FR13 1150A NXP 0820 6 FR12 820A*
NXP 1300 5 FR13 1300A NXP 0920 6 FR13 920A
NXP 1450 5
FR13
1450A
NXP 1030 6
1030A
NXP 1770 5 FR14 1770A NXP 1180 6 FR13 1180A*
NXP 2150 5 FR14 2150A NXP 1500 6 FR14 1500A
NXP 1900 6 FR14 1900A
NXP 2250 6 FR14 2250A*
Table 1. Vacon NXP frequency converters, frames FR10…FR14
*Max ambient temperature +35ºC
The frequency converters can be installed in any enclosure that fulfils the requirements specified in
chapter 3
. In the illustrations in this manual, Rittal TS8 is used as an example enclosure.
Installing NX FR10…FR14 frequency converters in an enclosure involves the following steps:
Installing the AC choke(s) (chapter 4)
Installing and grounding of power module(s) (chapter 5)
Establishing the internal power connections between
a) the AC choke(s) and the power module (frames FR10…FR12) (chapter 6.1) or
b) the AC chokes, the NFE units and the inverter units (frames FR13 and FR14)
Installing the control unit (chapter 7)
Preparing for input and output power connections (chapter 8)
Arranging air-cooling and ventilation (chapter 9).
General instructions for product handling are given in chapter 2. Dimensional drawings are found in
chapter 10.
For more information about the use of the products, refer to the NXC User's manual downloadable at
www.vacon.com. For detailed drawings of the converters installed in Rittal TS8 cabinets, please contact
your local Vacon partner.
GENERAL vacon • 5
24-hour support +358 (0)40 837 1150 • Email: [email protected]m
1
NOTE: The installation of the frequency converters must be done by certified electricians.
Safety regulations for electrical work must be followed during the installation work.
NOTE: Safe operation and full service lifetime of the product can be guaranteed only if the
installation instructions in this manual are followed.
NOTE: The product warranty is not valid if the product is handled in a way that does not comply
with the instructions in this manual and the product's User's Manual.
1.1 Type code
NXP 0000
A 0 N 0 SSF A1A20000C3
5
Option boards; each slot is represented by two characters where:
A = basic I/O board, B = expander I/O board,
C = fieldbus board, D = special board
Hardware modifications; Supply - Mounting - Boards
SSF = 6-pulse connection; air-cooled; standard board
TSF = 12-pulse connection; air-cooled; standard board
Brake chopper
0 = No brake chopper
1 = With integrated brake chopper
EMC emission level:
N = No EMC em
ission protection; requires cabinet assembly to
comply with level L
T = fulfils standard EN61800-3 for IT networks
Enclosure class:
0 = IP00 (module only)
Control keypad:
A = standard (alpha-numeric)
Product range: NXP
Nominal current (low overload)
e.g. 1300 = 1300A etc.
Nominal mains voltage (3-phase):
5 = 380500Vac, 6 = 525690Vac
Figure 1. NXP IP00 drives type code
6 • vacon PRODUCT HANDLING
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
2
2. PRODUCT HANDLING
2.1 Product type designation codes
Product type designation codes are found on the power module and the control unit. For an explanation
of the type designation codes, refer to the NXP/C User's Manual.
2.2 Receipt of delivery
2.2.1
Frames FR10 to FR12
The standard delivery includes:
Power module(s) with one integrated control unit; The power module in FR12 with the integrated
control unit is referred to as
Power module 1
the other one as
Power module 2
later in this manual
AC choke(s)
FR12 units only:
optical cable set for internal control connections between control unit and power
modules
IP00 Module Installation Manual
NXP/C User's Manual.
Summary (check the type code of the components):
Mains voltage 380-500V
6-pulse units
Mains voltage 380-500V
12-pulse units
FC type
# of chokes
FC type
# of chokes
NXP0385 5 1*CHK0400 NXP0385 5 2*CHK0261
NXP0460 5 1*CHK0520 NXP0460 5 2*CHK0261
NXP0520 5 1*CHK0520 NXP0520 5 2*CHK0261
NXP0590 5 2*CHK0400 NXP0590 5 2*CHK0400
NXP0650 5 2*CHK0400 NXP0650 5 2*CHK0400
NXP0730 5 2*CHK0400 NXP0730 5 2*CHK0400
NXP0820 5 2*CHK0520 NXP0820 5 2*CHK0520
NXP0920 5 2*CHK0520 NXP0920 5 2*CHK0520
NXP1030 5 2*CHK0520 NXP1030 5 2*CHK0520
Table 2. Summary of components for FR10 and FR12, 380-500 V
Mains voltage 525-690V
6-pulse units
Mains voltage 525-690V
12-pulse units
FC type
# of chokes
FC type
# of chokes
NXP0261 6 1*CHK0261 NXP0261 6 2*CHK0261
NXP0325 6 1*CHK0400 NXP0325 6 2*CHK0261
NXP0385 6 1*CHK0400 NXP0385 6 2*CHK0261
NXP0416 6 1*CHK0400 NXP0416 6 2*CHK0261
NXP0460 6 1*CHK0520 NXP0460 6 2*CHK0400
NXP0502 6 1*CHK0520 NXP0502 6 2*CHK0400
NXP0590 6
2*CHK0400
NXP0590 6
2*CHK0400
NXP0650 6 2*CHK0400 NXP0650 6 2*CHK0400
NXP0750 6 2*CHK0400 NXP0750 6 2*CHK0400
NXP0820 6 2*CHK0400 NXP0820 6 2*CHK0400
Table 3. Summary of components for FR10 to FR12, 520-690 V
PRODUCT HANDLING vacon • 7
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
2
The following optional equipment is delivered on request:
Door installation kit NXDRA02B for installing the control panel on the enclosure door.
Control unit with fixing plate. See also chapter 7.
Cable set, including seven optical cables and a 24V connecting cable, readily connected to the
power module and the control unit. Standard length: 2.3m
AC choke
Power module
Control unit
Fibre optic cables and
24V connecting cable
Power module
Control
unit
Figure 2. Parts included in delivery; Left: AC choke, Middle: Power module (1 or 2) with separate control unit,
Right: Power module with integrated control unit (FR10 to FR12 only)
8 • vacon PRODUCT HANDLING
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
2
2.2.2
Frames FR13 and FR14
The standard delivery includes:
1 or 2 NXI inverter modules
2 to 4 NXN non-generative front-end (NFE) units with 2 or 3 modules mounted in brackets
Control unit with fixing plate. See also chapter 7.
AC choke per each NFE unit
FR14 only:
dU/dt filter (optional; 1 per inverter module)
Cable set for NFE's and inverter modules
Optical cable set for internal control connections between control unit and power modules
IP00 Module Installation Manual
NXP/C User's Manual.
Mains voltage 380-500V
Summary (check the type code of the components):
6-pulse units
FC type
Inverter unit
# of NXN
units
# of chokes
NXP1150 5
1*NXI1150 5
2*NXN0650 5
2*CHK0650 6
NXP1300 5 1*NXI1300 5 3*NXN0650 5 3*CHK0520 6
NXP1450 5 1*NXI1450 5 3*NXN0650 5 3*CHK0520 6
NXP1770 5 2*NXI1150 5 4*NXN0650 5 4*CHK0520 6
NXP2150 5 2*NXI1150 5 4*NXN0650 5 4*CHK0650 6
Mains voltage 380-500V
12-pulse units
FC type
Inverter unit
# of NXN
units
# of chokes
NXP1150 5 1*NXI1150 5 2*NXN0650 5 2*CHK0650 6
NXP1300 5 1*NXI1300 5 4*NXN0650 5 4*CHK0520 6
NXP1450 5 1*NXI1450 5 4*NXN0650 5 4*CHK0520 6
NXP1770 5 2*NXI1150 5 4*NXN0650 5 4*CHK0520 6
NXP2150 5 2*NXI1150 5 4*NXN0650 5 4*CHK0650 6
Table 4. Summary of components for FR13 and FR14, 380-500 V
Mains voltage 525-690V
6-pulse units
FC type
Inverter unit
# of NXN
units
# of chokes
NXP0920 6 1*NXI0920 6 2*NXN0650 6 2*CHK0520 6
NXP1030 6 1*NXI1030 6 2*NXN0650 6 2*CHK0520 6
NXP1180 6 1*NXI1180 6 2*NXN0650 6 2*CHK0650 6
NXP1500 6 2*NXI0920 6 3*NXN0650 6 3*CHK0520 6
NXP1900 6 2*NXI0920 6 4*NXN0650 6 4*CHK0520 6
NXP2250 6 2*NXI1180 6 4*NXN0650 6 4*CHK0650 6
Mains voltage 525-690V
12-pulse units
FC type
Inverter unit
# of NXN
units
# of chokes
NXP0920 6 1*NXI0920 6 2*NXN0650 6 2*CHK0520 6
NXP1030 6 1*NXI1030 6 2*NXN0650 6 2*CHK0520 6
NXP1180 6
1*NXI1180 6
2*NXN0650 6
2*CHK0650 6
NXP1500 6 2*NXI0920 6 4*NXN0650 6 4*CHK0520 6
NXP1900 6 2*NXI0920 6 4*NXN0650 6 4*CHK0520 6
NXP2250 6 2*NXI1180 6 4*NXN0650 6 4*CHK0650 6
Table 5. Summary of components for FR13 and FR14, 520-690 V
The following optional equipment is delivered on request:
Door installation kit NXDRA02B for installing the control panel on the enclosure door.
Cable set, including seven optical cables and a 24V connecting cable, readily connected to the
power module and the control unit. Standard length: 2.3m
PRODUCT HANDLING vacon • 9
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
2
2.3 Receiving, unpacking and storing the product
The product is delivered packed in a plywood case, which can be recycled or destroyed by burning.
Instructions for receiving, handling and storing the product, as well as the general warranty terms can
be found in the NXP/C User’s manual.
2.4 Lifting the modules
The modules can be lifted by the holes on top. Place the lifting hooks symmetrically in at least two
holes. The maximum allowed lifting angle is 45 degrees.
The lifting equipment must be able to carry the weight of the module. For frames FR10 to FR12, see
Figure 3 and for frames FR13 and FR14 see chapter 3.2.2.
FR10: 123 kg
FR11: 210 kg
FR12: 2*123 kg
max 4
figure28.fh8
2*NXN: 140 kg
3*NXN: 210 kg
1*NXI: 300 kg
Figure 3. Lifting the power module
NOTE! The power module can temporarily rest on the cooling fan assembly, but shocks or non-
vertical forces may cause damage to the fans.
10 • vacon PRODUCT HANDLING
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
2
2.5 Lifting AC chokes
The AC choke can be lifted by the two eyebolts on top of the unit. The weight of the AC choke varies
from 53 kg to 130 kg depending on the type (see Figure 4).
Figure 4. Lifting the AC choke
figure3.fh8
Choke Weight
CHK0261 53 kg
CHK0400 84 kg
CHK0520 115 kg
CHK0650 130 kg
REQUIREMENTS vacon • 11
24-hour support +358 (0)40 837 1150 • Email: [email protected]m
3
3. REQUIREMENTS
3.1 Environmental requirements
Refer to Vacon NXP/C User's Manual (document code ud01011) for information on required operating
temperature, humidity, etc. The User's Manual also states the free space required around the
enclosure.
NOTE! EN60439-1 specifies the ambient temperature for enclosed products at 35°C (24h aver-
age)/40°C (maximum). The ventilation and cooling of the installation room must be suffi-
cient to keep the temperature below this level.
For information on the heat dissipation of the product and the required cooling air, refer to section 9.3
and the Vacon NXP/C User's Manual.
3.2 Cabinets
3.2.1
Cabinet installation for frames FR10 to FR12
Vacon IP00 power modules of frames FR10…FR12 can be installed in cabinets. The cabinets have to
meet the following requirements.
Width: Min. 600 mm
Depth: Min. 600 mm (or min. 490 mm if the control unit is installed in
another position than at the front of the power unit)
Height: Min. 1800 mm if the AC choke is installed beneath the power
module, otherwise min. 1500 mm
Mechanical requirements: The cabinet must be able to support a total equipment weight of 275
kg (if the power module and the AC choke are installed in the same
cabinet).
Protection class: This manual applies to IP21.
Construction: According to EN60439-1
Ventilation openings: Refer to section 9.1.
Table 6. Cabinet data for FR10
Width: Min. 800 mm
Depth: See Table 6.
Height: See Table 6.
Mechanical requirements: The cabinet must be able to support a total equipment weight of 350
kg (if the power module and the AC choke are installed in the same
cabinet).
Protection class: This manual applies to IP21.
Construction: According to EN60439-1
Ventilation openings: Refer to section 9.1.
Table 7. Cabinet data for FR11
Width: Min. 1200 mm
Depth: See Table 6.
Height:
See Table 6.
Mechanical requirements: The cabinet must be able to support a total equipment weight of 550
kg (if the power modules and the AC chokes are installed in the
same cabinet).
Protection class: This manual applies to IP21.
Construction: According to EN60439-1
Ventilation openings: Refer to section 9.1.
Table 8. Cabinet data for FR12
12 • vacon REQUIREMENTS
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
3
Cabinet A
DC busbars
1 1
2 2
4
Cabinet B
DC busbars
3
3.2.2
Cabinets for frames FR13 and FR14
The power section of frames FR13 and FR14 comprise 2 to 4 non-generative front-end (NFE) units, AC
chokes, inverter units and dU/dt-filters (required for FR14). Several cabinets are, therefore, needed.
Example installations as well as cabinet requirements are presented below:
1 = NFE units 2 = AC chokes 3 = FI13 (inverter unit) 4 = dU/dt-filter
This installation applies to
converter types:
NXP1150 5
NXP0920 6
NXP1030 6
NXP1180 6
Required cabinet width: Min. 600 mm (Cabinet A) + 800 mm (Cabinet B)
Required cabinet height: Min. 2200 mm
Required weight carrying
capacity:
NXP1150 5: 480 kg (Cab.A); 540 kg (Cab.B)
NXP0920 6: 450 kg (Cab.A); 540 kg (Cab.B)
NXP1030 6: 450 kg (Cab.A); 540 kg (Cab.B)
NXP1180 6: 480 kg (Cab.A); 540 kg (Cab.B)
Protection class:
This manual applies to IP21.
Construction: According to EN60439-1
Ventilation openings: Refer to section 9.1.
Table 9. Cabinet data
This installation applies to
converter types:
NXP1300 5 (6-pulse)
NXP1450 5 (6-pulse)
Required cabinet width: Min. 800 mm (Cab.A) + 800 mm (Cab. B)
Required cabinet height: Min. 2200 mm
Required weight carrying
capacity:
635 kg (Cab.A); 590 kg (Cab.B)
Protection class: This manual applies to IP21.
Construction:
According to EN60439-1
Ventilation openings: Refer to section 9.1.
Table 10. Cabinet data
Cabinet A
1 1 1
22 2
DC busbars
4
Cabinet B
DC busbars
3
REQUIREMENTS vacon • 13
24-hour support +358 (0)40 837 1150 • Email: [email protected]m
3
This installation applies
to converter types:
NXP1300 5 (12-pulse)
NXP1450 5 (12-pulse)
Required cabinet width:
Min. 600 mm (Cab.A) + 800 mm (Cab.
B) + 600 mm (Cab.C)
Required cabinet height: Min. 2200 mm
Required weight carrying
capacity:
450 kg (Cab.A and C); 540 kg (Cab.B)
Protection class:
This manual applies to IP21.
Construction: According to EN60439-1
Ventilation openings: Refer to section 9.1.
Table 11. Cabinet data
This installation applies to converter type: NXP1500 6 (6-pulse)
Required cabinet width: Min. 800 mm (Cab.A) + 800 mm (Cab. B) + 800 mm (Cab. C)
Required cabinet height: Min. 2200 mm
Required weight carrying capacity: 635 kg (Cab.A); 540 kg (Cab.B); 540 kg (Cab. C)
Protection class: This manual applies to IP21.
Construction: According to EN60439-1
Ventilation openings: Refer to section 9.1.
Table 12. Cabinet data
Cabinet A
DC busbars
1 1
2 2
Cabinet C
DC busbars
1 1
2 2
4
Cabinet B
DC busbars
3
Cabinet A
1 1 1
22 2
DC busbars DC busbars
4
Cabinet C
4
Cabinet B
DC busbars
3
3
14 • vacon REQUIREMENTS
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
3
This installation applies to converter
types:
NXP1770 5
NXP2150 5
NXP1500 6 (12-pulse)
NXP1900 6
NXP2250 6
Required cabinet width: Min. 600 mm (Cab.A and D) + 800 mm (Cab. B and C)
Required cabinet height:
Min. 2200 mm
Required weight carrying capacity: NXP1500 6 (12-pulse): 450 kg (Cab.A and D); 540 kg (Cab.B and C)
NXP1770 5: 450 kg (Cab.A and D); 540 kg (Cab.B and C)
NXP1900 6: 450 kg (Cab.A and D); 540 kg (Cab.B and C)
NXP2150 5: 480 kg (Cab.A and D); 540 kg (Cab.B and C)
NXP2250 6: 480 kg (Cab.A and D); 540 kg (Cab.B and C)
Protection class: This manual applies to IP21.
Construction: According to EN60439-1
Ventilation openings: Refer to section 9.1.
Table 13. Cabinet data
Cabinet A
DC busbarsDC busbars
1 1
2 2
Cabinet D
1 1
2 2
DC busbars
4
Cabinet C
4
Cabinet B
DC busbars
3
3
INSTALLING AC CHOKES vacon • 15
24-hour support +358 (0)40 837 1150 • Email: [email protected]m
4
4. INSTALLING AC CHOKES
Type code
(partial)
Frame size
Choke type
(6-pulse)
Choke type
(12-pulse)
Voltage range 400500V
NXP 0385 5 FR10 CHK0400 2*CHK0261
NXP 0460 5 FR10 CHK0520 2*CHK0261
NXP 0520 5 FR10 CHK0520 2*CHK0261
NXP 0590 5 FR11 2*CHK0400 2*CHK0400
NXP 0650 5 FR11 2*CHK0400 2*CHK0400
NXP 0730 5 FR11 2*CHK0400 2*CHK0400
NXP 0820 5 FR12 2*CHK0520 2*CHK0520
NXP 0920 5 FR12 2*CHK0520 2*CHK0520
NXP 1030 5 FR12 2*CHK0520 2*CHK0520
NXP 1150 5 FR13 2*CHK0650 2*CHK0650
NXP 1300 5 FR13 3*CHK0520 4*CHK0520
NXP 1450 5 FR13 3*CHK0520 4*CHK0520
NXP 1770 5 FR14 4*CHK0520 4*CHK0520
NXP 2150 5 FR14 4*CHK0650 4*CHK0650
Voltage range 525690V
NXP 0261 6 FR10 CHK0261 2*CHK0261
NXP 0325 6 FR10 CHK0400 2*CHK0261
NXP 0385 6 FR10 CHK0400 2*CHK0261
NXP 0416 6 FR10 CHK0400 2*CHK0261
NXP 0460 6
FR11
CHK0520
2*CHK0400
NXP 0502 6
FR11
CHK0520
2*CHK0400
NXP 0590 6 FR11 2*CHK0400 2*CHK0400
NXP 0650 6 FR12 2*CHK0400 2*CHK0400
NXP 0750 6 FR12 2*CHK0400 2*CHK0400
NXP 0820 6 FR12 2*CHK0400 2*CHK0400
NXP 0920 6 FR13 2*CHK0520 2*CHK0520
NXP 1030 6 FR13 2*CHK0520 2*CHK0520
NXP 1180 6
FR13
2*CHK0650
2*CHK0650
NXP 1500 6 FR14 3*CHK0520 4*CHK0520
NXP 1900 6 FR14 4*CHK0520 4*CHK0520
NXP 2250 6 FR14 4*CHK0650 4*CHK0650
Table 14. Choke types
16 • vacon INSTALLING AC CHOKES
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
4
4.1 Installing AC chokes: Frames FR10 to FR12
The recommended location for the AC choke is the bottom part of the enclosure, where it should be
installed close to the rear wall. For a possible later installation of a fuse switch, it may be practical
to install the AC choke somewhat to the left.
Fasten the choke on an assembly plate or using mounting rails.
Figure 5. Installing AC choke
NOTE! An upper support plate must be installed above the choke if the cabinet is transported in
horizontal position. A possible fixed support plate must be equipped with air circulation
holes. See
Figure 36 on page 45.
INSTALLING AC CHOKES vacon • 17
24-hour support +358 (0)40 837 1150 • Email: [email protected]m
4
4.2 Installing AC chokes: Frames FR13 and FR14
Check the needed amount and type of chokes e.g. in Table 14 and in chapter 3.2.2. Place the chokes
on the bottom of the enclosure as shown in Figure 6.
Fasten the choke on an assembly plate or using mounting rails.
NOTE! An upper support plate must be installed above the choke if the cabinet is transported in
horizontal position. The support plate must be equipped with air circulation holes. See
Figure 36 on page 45.
figure29.fh8
Terminals pointing
outwards
Terminals pointing
outwards
Figure 6. Installing AC choke (2 chokes); frames FR13 and FR14
Figure 7. Installing AC choke (3 chokes); frames FR13 and FR14
18 • vacon INSTALLING POWER MODULE
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
5
5. INSTALLING POWER MODULE
5.1 Preparing the enclosure
To facilitate a possible future replacement of boards as well as other service work, it is recom-
mended that the power module be mounted on rails.
5.1.1
Mounting dimensions for frames FR10 to FR12
Fasten mounting rails to the sides of the cabinet at distances given under F (from the top) and G
(from the bottom) in the table below. Leave a space (A) between the module and the walls on both
sides for the internal cooling air circulation.
Figure 8. Preparing the enclosure for the power module
The power module should be fastened to the rear side of the enclosure as shown in Figure 10. For
this purpose, install two fixing bars on the rear wall of the cabinet at appropriate levels.
Note the following dimensions that are essential for placing the power module. All dimensions in
mm
:
A
B
C
D
E
F
G
50* 100 1120 550 (290) 116 (44) 918 850 (590)
Table 15.
A = Minimum distance to the side walls or adjacent components. * = Note that the two cabinets, in
which the modules of frame FR12 are installed, require no clearance between them.
B = Minimum distance from the top of the cabinet; This space is needed for the power cables (see
Figure 14).
A
E
B
C
D
A
F
G
INSTALLING POWER MODULE vacon • 19
24-hour support +358 (0)40 837 1150 • Email: [email protected]m
5
C = Module height
D = Minimum distance from the bottom of the enclosure if the AC choke is installed at the bottom
of the enclosure. If the choke is installed in another location, the distance must not, however,
be smaller than what is given in parentheses
E = Minimum distance from the cabinet door; This is to enable the control unit to be installed in
front of the power module. The number in parentheses designates the minimum distance from
the door if the control unit is installed in any other location.
F = Minimum distance from the mounting rails to top of the cabinet.
G = Minimum distance from the mounting rails to the bottom of the cabinet. If the choke is
installed in another location, the distance must not, however, be smaller than what is given in
parentheses
See also the dimensional drawings in chapter 10.
5.1.2
Mounting dimensions for frames FR13 and FR14
Figure 9. Preparing the enclosure for the modules
Note the following dimensions that are essential for placing the modules. All dimensions in
mm
:
A
B
C
175 1050 600 (300)
Table 16. Dimensions
A = Minimum distance from the top of the cabinet; This space is needed for the fuses and busbars
B = Module height
C = Minimum distance from the bottom of the enclosure if the AC choke is installed at the bottom
of the enclosure. If the choke is installed in another location, the distance must not, however,
be smaller than what is given in parentheses
See also the dimensional drawings in chapter 10.
figure31.fh8
A
B
C
20 • vacon INSTALLING POWER MODULE
Telephone +358 (0)201-2121 • Fax +358 (0)201-212 205
5
5.2 Mounting the modules
5.2.1
Mounting the power modules for frames FR10 to FR12
NOTE! If the space around the power module is narrow, lead the internal power cables along
the wall and fasten them in brackets before mounting the power module. See chapter
6.1.
Fasten the power module to the rear wall of the enclosure utilising the fixing holes in the frame.
Figure 10. Mounting the power module, FR10
NOTE! If the power module is installed before the AC choke, the centre of gravity is very high at
this stage. Support the enclosure thoroughly during the assembly.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60