mundoclima Maxi MVD V5X User manual

Type
User manual
MAXI MVD V5X
English
CL23300 to CL23307
OUTDOOR UNIT
www.mundoclima.com
Service manual
08/2016
MVD
201608 1
CONTENTS
CONTENTS
Part 1 General Information ............................................................................ 3
Part 2 Component Layout and Refrigerant Circuits ................................... 11
Part 3 Control ............................................................................................... 23
Part 4 Field Settings ..................................................................................... 37
Part 5 Diagnosis and Troubleshooting ......................................................... 43
Maxi MVD V5X
2 201608
Maxi MVD V5X
201608 3
Part 1 - General Information
Part 1
General Information
1 Indoor and Outdoor Unit Capacities ...................................................... 4
2 External Appearance .............................................................................. 6
3 Outdoor Unit Combinations ................................................................... 8
4 Combination Ratio ................................................................................. 9
Maxi MVD V5X
4 201608
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units
1.1.1 Standard indoor units
Table 1-1.1: Standard indoor unit abbreviation codes
Abbreviation
code
Type
Abbreviation
code
Type
Q1
One-way Cassette T1 High Static Pressure Duct
Q2
Two-way Cassette G Wall-mounted
Q4-A3
Compact Four-way Cassette DL Ceiling & Floor
Q4
Four-way Cassette F Floor Standing
T3
Low Static Pressure Duct Z Console
T2
Medium Static Pressure Duct
Table 1-1.2: Standard indoor unit capacity range
1.1.2 Fresh air processing unit
Table 1-1.3: Fresh air processing unit capacity range
12.5kW 14kW 20kW 25kW 28kW
125 140 200 250 280
1.2 Heat recovery ventilator
Table 1-1.4: Heat recovery ventilator capacity range
Model
HRV-200
HRV-300
HRV-400
HRV-500
HRV-800
HRV-1000
HRV-1500
HRV-2000
Capacity (m
3
/h)
200
300
400
500
800
1000
1500
2000
Capacity
Capacity
index
Q1 Q2 Q4- A 3 Q4 T3 T2 T1 G DL F Z
kW HP
1.8 0.6 18 18
18
18
2.2 0.8 22 22 22 22
22 22
22
22 22
2.8 1 28 28 28 28 28 28 28
28
28 28
3.6 1.25 36 36 36 36 36 36 36
36 36 36 36
4.5 1.6 45 45 45 45 45 45 45
45 45 45 45
5.6 2 56 56 56
56 56 56
56 56 56
7.1 2.5 71 71 71
71 71 71 71 71 71 71
8.0 3 80
80
80 80 80 80 80
9.0 3.2 90
90
90 90 90 90
10.0 3.6 100
11.2 4 112
112
112 112
112
14.0 5 140
140
140 140
140
16.0 6 160
160
160
20.0 7 200
200
25.0 9 250
250
28.0 10 280
280
40.0 14 400
400
45.0 16 450
450
56.0 20 560
560
Maxi MVD V5X
201608 5
1.3 Outdoor Units
Table 1-1.5: Outdoor unit capacity range
Part 1 - General Information
Capacity 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP
Model
(MVD-V5*/V2GN1)
X252W X280W X335W X400W X450W X500W X560W X615W
Capacity 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP
Model
(MVD-V5*/V2GN1)
X670W X730W X780W X840W X895W X950W X1000W X1065W
Outdoor unit 1 12HP 10HP 10HP 10HP 10HP 12HP 18HP 16HP
Outdoor unit 2 12HP 16HP 18HP 20HP 22HP 22HP 18HP 22HP
Capacity 40HP 42HP 44HP 46HP 48HP 50HP 52HP 54HP
Model
(MVD-V5*/V2GN1)
X1115W X1175W X1230W X1285W X1345W X1395W X1455W X1510W
Outdoor unit 1 18HP 20HP 22HP 12HP 10HP 10HP 10HP 10HP
Outdoor unit 2 22HP 22HP 22HP 12HP 16HP 18HP 20HP 22HP
Outdoor unit 3
22HP 22HP 22HP 22HP 22HP
Capacity 56HP 58HP 60HP 62HP 64HP 66HP 68HP 70HP
Model
(MVD-V5*/V2GN1)
X1565W X1615W X1680W X1730W X1790W X1845W X1900W X1960W
Outdoor unit 1 12HP 18HP 16HP 18HP 20HP 22HP 12HP 10HP
Outdoor unit 2 22HP 18HP 22HP 22HP 22HP 22HP 12HP 16HP
Outdoor unit 3 22HP 22HP 22HP 22HP 22HP 22HP 22HP 22HP
Outdoor unit 4
22HP 22HP
Capacity 72HP 74HP 76HP 78HP 80HP 82HP 84HP 86HP
Model
(MVD-V5*/V2GN1)
X2010W X2070W X2125W X2180W X2230W X2295W X2345W X2405W
Outdoor unit 1 10HP 10HP 10HP 12HP 18HP 16HP 18HP 20HP
Outdoor unit 2 18HP 20HP 22HP 22HP 18HP 22HP 22HP 22HP
Outdoor unit 3 22HP 22HP 22HP 22HP 22HP 22HP 22HP 22HP
Outdoor unit 4 22HP 22HP 22HP 22HP 22HP 22HP 22HP 22HP
Capacity 88HP
Notes:
1. The full model names can be obtained by substituting the asterisk in the model name format given in the
left-hand column of the table above with the shortened model names given in the table. For example, the
model name for the 40HP model is MVD-V5X1115W/V2GN1.
2. The combinations of units shown in the table are factory-recommended. Other combinations of units are
also possible.
Model
(MVD-V5*/V2GN1)
X2460W
Outdoor unit 1 22HP
Outdoor unit 2 22HP
Outdoor unit 3 22HP
Outdoor unit 4 22HP
Maxi MVD V5X
6 201608
2 External Appearance
2.1 Indoor Units
2.1.1 Standard indoor units
Table 1-2.1: Standard indoor unit appearance
One-way Cassette
Two-way Cassette
Q1
Q2
Compact Four-way Cassette
Four-way Cassette
Q4-A3
Q4
Low Static Pressure Duct
Medium Static Pressure Duct
T3
T2
High Static Pressure Duct
Wall-mounted
T1
G
Ceiling & Floor
Floor Standing
DL
F
Console
Z
2.1.2 Fresh air processing unit
Table 1-2.2: Fresh air processing unit appearance
Fresh Air Processing Unit
Maxi MVD V5X
201608 7
Part 1 - General Information
2.2 Heat Recovery Ventilator
Table 1-2.3: Heat recovery ventilator appearance
Heat Recovery Ventilator
2.3 Outdoor Units
2.3.1 Single units
Table 1-2.4: Single outdoor unit appearance
8/10/12HP 14/16/18/20/22HP
2.3.2 Combinations of units
Table 1-2.5: Combination outdoor unit appearance
24HP 26/28/30/32/34HP 36/38/40/42/44HP
46HP 48/50/52/54/56HP 58/60/62/64/66HP
68HP 70/72/74/76/78HP 80/82/84/86/88HP
Maxi MVD V5X
8 201608
3 Outdoor Unit Combinations
Table 1-3.1: Outdoor unit combinations
System capacity
Number
of units
Modules
1
Outdoor branch joint kit
2
kW
HP
8 10 12 14 16 18 20 22
25.2
8
1
28.0
10
1
33.5
12
1
40.0
14
1
45.0
16
1
50.0
18
1
56.0
20
1
61.5
22
1
67.0
24
2
●●
FQZHW-02N1D
73.0
26
2
78.0
28
2
84.0
30
2
89.5
32
2
95.0
34
2
100.0
36
2
●●
106.5
38
2
111.5
40
2
117.5
42
2
123.0
44
2
●●
128.5
46
3
●●
FQZHW-03N1D
134.5
48
3
139.5
50
3
145.5
52
3
151.0
54
3
●●
156.5
56
3
●●
161.5
58
3
●●
168.0
60
3
●●
173.0
62
3
●●
179.0
64
3
●●
184.5
66
3
●●●
190.0
68
4
●●
●●
FQZHW-04N1D
196.0
70
4
●●
201.0
72
4
●●
207.0
74
4
●●
212.5
76
4
●●●
218.0
78
4
●●●
223.0
80
4
●●
●●
229.5
82
4
●●●
234.5
84
4
●●●
240.5
86
4
●●●
246.0
88
4
●●●●
Notes:
1. The combinations of units shown in the table are factory-recommended. Other combinations of units are also possible.
2. For systems with two or more outdoor units, outdoor branch joints (sold separately) are required.
Maxi MVD V5X
201608 9
Part 1 - General Information
4 Combination Ratio
Table 1-5.1: Indoor and outdoor unit combination ratio limitations
Type
Minimum
combination ratio
Maximum combination ratio
Standard indoor
units only
Fresh air processing
units only
Fresh air processing units and
standard indoor units together
50% 130% 100% 100%
1
Notes:
1. When fresh air processing units are installed together with standard indoor units, the total capacity of the fresh air processing units must not exceed 30%
of the total capacity of the outdoor units and the combination ratio must not exceed 100%.
Table 1-5.2: Combinations of Indoor and outdoor units
Outdoor unit capacity
Sum of capacity indexes of
connected indoor units
(standard indoor units only)
Sum of capacity indexes of connected
indoor units (fresh air processing units and
standard indoor units together)
Maximum number of
connected indoor units
kW
HP
Capacity index
25.2
8
252
126 to 327.6 126 to 252 13
28.0
10
280
140 to 364 140 to 280 16
33.5
12
335
167.5 to 435.5 167.5 to 335 20
40.0
14
400
200 to 520 200 to 400 23
45.0
16
450
225 to 585 225 to 450 26
50.0
18
500
250 to 650 250 to 500 29
56.0
20
560
280 to 728 280 to 560 33
61.5
22
615
307.5 to 799.5 307.5 to 615 36
67.0
24
670
335 to 871 335 to 670 39
73.0
26
730
365 to 949 365 to 730 43
78.0
28
780
390 to 1014 390 to 780 46
84.0
30
840
420 to 1092 420 to 840 50
89.5
32
895
447.5 to 1163.5 447.5 to 895 53
95.0
34
950
475 to 1235 475 to 950 56
100.0
36
1000
500 to 1300 500 to 1000 59
106.5
38
1065
532.5 to 1384.5 532.5 to 1065 63
111.5
40
1115
557.5 to 1449.5 557.5 to 1115
64
117.5
42
1175
587.5 to 1527.5 587.5 to 1175
123.0
44
1230
615 to 1599 615 to 1230
128.5
46
1285
642.5 to 1670.5 642.5 to 1285
134.5
48
1345
672.5 to 1748.5 672.5 to 1345
139.5
50
1395
697.5 to 1813.5 697.5 to 1395
145.5
52
1455
727.5 to 1891.5 727.5 to 1455
151.0
54
1510
755 to 1963 755 to 1510
156.5
56
1565
782.5 to 2034.5 782.5 to 1565
161.5
58
1615
807.5 to 2099.5 807.5 to 1615
168.0
60
1680
840 to 2184 840 to 1680
173.0
62
1730
865 to 2249 865 to 1730
179.0
64
1790
895 to 2327 895 to 1790
184.5
66
1845
922.5 to 2398.5 922.5 to 1845
190.0
68
1900
950 to 2470 950 to 1900
196.0
70
1960
980 to 2548 980 to 1960
201.0
72
2010
1005 to 2613 1005 to 2010
207.0
74
2070
1035 to 2691 1035 to 2070
212.5
76
2125
1062.5 to 2762.5 1062.5 to 2125
218.0
78
2180
1090 to 2834 1090 to 2180
223.0
80
2230
1115 to 2899 1115 to 2230
229.5
82
2295
1147.5 to 2983.5 1147.5 to 2295
234.5
84
2345
1172.5 to 3048.5
1172.5 to 2345
240.5
86
2405
1202.5 to 3126.5
1202.5 to 2405
246.0
88
2460
1230 to 3198
1230 to 2460
Combination ratio =
Sum of capacity indexes of the indoor units
Capacity index of the outdoor units
MAXI MVD V5X
Maxi MVD V5X
10 201608
Maxi MVD V5X
201608 11
Part 2 - Component Layout and Refrigerant Circuits
Part 2
Component Layout and
Refrigerant Circuits
1 Layout of Functional Components ....................................................... 12
2 Piping Diagrams .................................................................................. 14
3 Refrigerant Flow Diagrams .................................................................. 17
Maxi MVD V5X
12 201608
1 Layout of Functional Components
Figure 2-2.1: top view
High p
ressure sensor
Disch
arge temperature switch
Compressor top
temperature sensor
Figure 2-2.2:
DC fan
motor
Sol
enoid valv
e SV5
(fast defrosting)
Solenoid valve SV4
(oil balance)
Solenoid valve SV2
(liquid refrigerant injection)
Low pressure switch
Discharge pipe
temperature sensor
DC inverter compressor
Unloading valve
Four-way valve
Solenoid valve SV6
(EXV bypass)
Heat exchanger
temperature sensor
High pressure switch
Crankcase heater
Outdoor ambient
temperature sensor
Electronic
expansion valve
MVD-V5X252W/V2GN1 / MVD-V5X280W/V2GN1 / MVD-V5X335W/V2GN1
front view
Maxi MVD V5X
201608 13
Part 2 - Component Layout and Refrigerant Circuits
Figure 2-2.3:
Compress
or top
temperature sensor
Compressor top
temperature sensor
Discharge temperature switch
Discharge temperature switch
Figure 2-2.4:
S
olenoid valve SV5
(fast defrosting)
DC fan motor
DC fan motor
Solenoid valve SV4
(oil balance)
Solenoid valve SV2
(liquid refrigerant injection)
Low pressure switch
Crankcase heater
DC inverter compressor
Crankcase heater
High pressure switch
DC inverter compressor
Heat exchanger
temperature sensor
Outdoor ambient
temperature sensor
Electronic
expansion valve
Solenoid valve SV6
(EXV bypass)
Four-way valve
High pressure sensor
Unloading valve
Electronic
expansion valve
MVD-V5X400W/V2GN1 / MVD-V5X450W/V2GN1 / MVD-V5X500W/V2GN1
MVD-V5X560W/V2GN1 / MVD-V5X615W/V2GN1
top view
front view
Maxi MVD V5X
14 201608
2 Piping Diagrams
Sole
noid
valve
SV7
Filte
r
Four-way
val
ve
High pressure sensor
Pressure
regulating
valve
Com
press
or
Oil
Separator
Accumulator
Sole
noi
d
valve
SV2
Electronic expansion valve
High
pressure
switch
Capi
llary t
ube
He
at exchan
ger
Check valve
Check valve
Check valve
Check
valve
Filter
Sole
noid
val
ve SV4
Sole
noid
valve
SV6
Solenoid
valve SV5
Filter
Stop valve
Stop valve
Stop valve
Capillary
tube
Li
quid pi
pe
Gas pipe
Oil balance pipe
Capillary
tube
Low pressure
switch
Filter
Filter
Soleno
id
valv
e SV2
Hea
t exc
hanger
Four-
way
val
ve
Low pressure
switch
High pressure
sensor
Pressure
regulating
valve
Compre
sso
r
Compressor
Oil
Separator
Accumulator
Capilla
ry
t
ube
Hig
h
pressur
e
switch
Ch
eck
val
ve
Filter
Stop valve
Stop valve
Stop valve
Check
valve
Check
valve
Soleno
id
valv
e SV5
Solenoid
valve SV6
Soleno
id
val
ve SV4
Capilla
ry
t
ube
Filte
r
Electro
ni
c
expans
ion valve
Electronic
expansion valve
Liquid
pipe
Gas
pipe
Oil balance pipe
Check
valve
Filter
MVD-V5X252W/V2GN1 / MVD-V5X280W/V2GN1 / MVD-V5X335W/V2GN1
Figure 2-1.1:
MVD-V5X400W/V2GN1 / MVD-V5X450W/V2GN1
Figure 2-1.2:
piping diagram
piping diagram
Maxi MVD V5X
201608 15
Part 2 - Component Layout and Refrigerant Circuits
Solenoid
valve SV2
Sole
noid
valve SV7
Heat exchanger
Four-way
valve
Low pressure
switch
High pressure
sensor
Pressure
regulating
valve
Compressor
Compressor
Oil
Separator
Accumulator
Capillary
tube
Capillary
tube
Electronic
expansion valve
High
pressure
switch
Check
valve
Filter
Stop valve
Stop valve
Stop valve
Check
valve
Check
valve
Solenoid
valve SV5
Solenoid
valve SV6
Sole
noid
valve SV4
Capillary
tube
Filte
r
Electronic
expansion valve
Liquid pipe
Gas pipe
Oil balance pipe
Check
valve
Filter
Filter
Filter
MVD-V5X500W/V2GN1/ MVD-V5X560W/V2GN1 / MVD-V5X615W/V2GN1
Figure 2-1.3: piping diagram
Maxi MVD V5X
16 201608
Key components:
1. Oil separator:
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation
efficiency is up to 99%.
2. Accumulator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.
3. Electronic Expansion Valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
4. Four-way valve:
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the heat
exchanger functions as a condenser; when open, the heat exchanger functions as an evaporator.
5. Solenoid valve SV2:
Protects the compressor. If compressor discharge temperature rises above 100°C, SV2 opens and sprays a small
amount of liquid refrigerant to cool the compressor. SV2 closes again once the discharge temperature has fallen
below 90°C.
6. Solenoid valve SV4:
Returns oil to the compressor. In single outdoor unit systems: opens once the compressor has run for 5 minutes and
closes 15 minutes later. In multiple outdoor unit systems: each unit's SV4 opens for 3 minutes every 20 minutes.
7. Solenoid valve SV5:
Enables fast defrosting. During defrosting operation, opens to shorten the refrigerant flow cycle and quicken the
defrosting process. Closed in cooling mode.
8. Solenoid valve SV6:
Allows refrigerant to bypass the expansion valves. Open in cooling mode when discharge temperature exceeds the
limit. Closed in heating mode or standby.
9. Solenoid valve SV7:
Allows refrigerant to return directly to the compressor. Open when indoor air temperature is close to the set
temperature to avoid frequent compressor on/off.
10. High and low pressure switches:
Regulate system pressure. When system pressure rises above the upper limit or falls below the lower limit, the high or
low pressure switches turn off, stopping the compressor. After 10 minutes, the compressor restarts.
Maxi MVD V5X
201608 17
Part 2 - Component Layout and Refrigerant Circuits
3 Refrigerant Flow Diagrams
Cooling operation
Figure 2-3.1: refrigerant flow during cooling operation
Sole
noid
valve SV7
M
M
M
M
Hi
gh temperature, high pressure gas
Hi
gh temperature, high pressure liquid
Low te
mperature, low pressure
Fan
on
Fan
on
Fan
off
Fan
on
Norm
al control
Filt
er
Filt
er
Norm
al control
Four-way
valve
High pressure sensor
Pressure
regulating
valve
Compres
sor
Oil
Separator
Accumulator
Sole
noid
valve SV2
Electronic expansion valve
Closed
High
pressure
switch
Capill
ary tube
He
at exchanger
Heat exchanger
Che
ck valve
Check valve
Check valve
Check
valve
Filter
Sole
noid
valve SV4
Sole
noid
valve SV6
Solenoid
valve SV5
Filter
Filter
Filter
Filter
Stop valve
Stop valve
Stop valve
Capillary
tube
"ON
"
"ON"
"OFF"
"ON"
Indo
or unit operation
Close
d
Filter
Filter
Low pressure
switch
Filter
Thermo
off
Thermo
on
Thermo
on
Oil return operation in cooling mode
Figure 2-3.2: refrigerant flow during oil return operation in cooling mode
M
M
M
M
Check
valve
High temper
ature, high pressure gas
High temper
ature, high pressure liquid
L
ow temperature, low pressure
Heat ex
changer
Heat exchanger
High pressure
sensor
Low pressure
switch
Compre
ssor
Pressure
regulating
valve
Oi
l
Separator
Accumulator
Fil
ter
Filter
Filter
Filter
Fan
on
Norm
al control
Normal control
300 steps
Elec
tronic expansion valve
Four-wa
y
valve
Filter
High
pressure
switch
"ON
"
"ON"
"OFF"
"ON"
Fil
ter
Stop valve
In
door unit operation
Filter
Filter
Capillary
tube
Stop
valve
Stop valve
Solenoi
d
valve SV7
Solenoid
valve SV2
Solenoi
d
valve SV4
Solenoi
d
valve SV6
Solenoid
valve SV5
Check
valve
Check
valve
Check valve
Filter
Filter
Fan
on
Fan
off
Fan
on
300 steps
Capillary
tube
Capillary
tube
Thermo on
Thermo
off
Thermo
off
MVD-V5X252W/V2GN1 / MVD-V5X280W/V2GN1 / MVD-V5X335W/V2GN1
Maxi MVD V5X
18 201608
Oil return operation in heating mode and defrosting operation
Figure 2-3.3: refrigerant flow during oil return operation in heating mode and during defrosting operation
M
M
M
M
High tempe
rature, h
igh pressure gas
High tempe
rature, hi
gh pressure liquid
Lo
w temperatur
e, low pressure
Fa
n
off
Hea
t excha
nger
Fa
n
off
Fa
n
off
Fa
n
off
Hea
t excha
nger
High
pressure
switch
High pressure
sensor
Low pressure
switch
Compre
ss
or
Oil
Separator
Accumulator
Electronic e
xpansi
on valve
Filt
er
Filt
er
"O
N"
"O
N"
"OFF"
"ON"
Filt
er
Stop v
al
ve
Indoo
r unit ope
ration
Filt
er
Filt
er
Sole
noi
d
valve SV7
Solenoid
valve SV4
Stop v
al
ve
Stop valve
Capillary
tube
Filter
Filter
Filter
Sole
noi
d
valve SV2
Check valve
Solenoid
valve SV5
480 steps
Filt
er
Filt
er
Capill
ary
tu
be
480 steps
480 steps
480 steps
Solenoid
valve SV6
Four-way
valve
Check
valve
Check
valve
Check
valve
Capillary
tube
Pressure
regulating
valve
Thermo on
Thermo on
Thermo
off
Heating operation
Figure 2-3.4: refrigerant flow during heating operation
M
M
M
M
High
tem
perature, high pressure gas
High
tem
perature, high pressure liquid
Low t
emp
erature, low pressure
Fa
n
on
Fan
on
Fa
n
off
Fan
on
Fil
te
r
Norm
al con
trol
Fil
te
r
Norm
al con
trol
Four-way
valve
Low pressure
switch
High pressure
sensor
Pressure
regulating
valve
Com
pressor
Oi
l
Separator
Accumulator
Elec
tronic expa
nsion valve
High
pressure
switch
Heat exchanger
Closed
Heat e
xch
anger
Ca
pilla
ry
tube
Sole
noid
valv
e SV7
Sole
noid
valve S
V2
Sole
noid
valv
e SV4
Sole
noid
valve S
V6
Solenoid
valve SV5
Stop valve
Stop va
lve
Stop va
lve
Check valve
Check
valve
Check
valve
Filter
Filter
Filter
Filter
Filter
"ON"
"ON"
"OFF"
"ON"
In
door unit
operation
Ca
pilla
ry
tube
Filter
Filter
Clos
ed
Chec
k
valve
Ca
pilla
ry
tube
Fil
te
r
Thermo on
Thermo on
Thermo
off
Maxi MVD V5X
201608 19
Part 2 - Component Layout and Refrigerant Circuits
Cooling operation
Figure 2-3.5: refrigerant flow during cooling operation
Solenoi
d
valve SV2
M
M
M
M
High tem
perature, high pressure gas
High tem
perature, high pressure liquid
Low te
mperature, low pressure
Fan
on
Fan
off
Fan
on
Heat ex
changer
Heat exchanger
Fan
on
Filte
r
Normal
control
Normal
control
Four
-way
valve
Low pressure
switch
High pressure
sensor
Pressure
regulating
valve
Compressor
Compressor
Oil
Separator
Accumulator
C
apillary
tube
Closed
High
pres
sure
switch
C
heck
valve
Filter
"ON"
"ON"
"OFF
"
"ON"
Filte
r
Filter
Filter
Stop valve
Stop valve
Stop valve
Check
valve
Check
valve
Solenoi
d
valve SV5
Solenoid
valve SV6
Solenoi
d
valve SV4
Indo
or unit operation
C
apillary
tube
Filte
r
El
ectronic
expansion valve
Electronic
expansion valve
Closed
Oil return operation in cooling mode
Figure 2-3.6: refrigerant flow during oil return operation in cooling mode
Four-
way
valve
M
M
M
M
High t
emperature, high pressure gas
High t
emperature, high pressure liquid
Low
temperature, low pressure
Fan
on
Fan
of
f
Fan
on
Hea
t exchanger
Heat exchanger
Fan
on
Filte
r
Filter
300 steps
Normal control
Normal control
Low pressure
switch
High
pressure
switch
High
pressure sensor
Pressure
regulating
valve
Compre
ssor
Compressor
Oil
Separator
Accumulator
Electro
nic
expansion valve
"ON
"
"ON"
"OFF"
"ON"
Filte
r
Stop
valve
Indo
or unit operation
Filter
Capillary
tube
Stop valve
Stop valve
Filte
r
Soleno
id
valve SV4
Soleno
id
valve SV2
Solenoid
valve SV5
Filter
Filter
Filter
Ch
eck
valve
Solenoid
valve SV6
Filte
r
Electro
nic
expansion valve
300 steps
MVD-V5X400W/V2GN1 / MVD-V5X450W/V2GN1
Maxi MVD V5X
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105