Simplicity 076154-01 User manual

Category
Measuring, testing & control
Type
User manual
ComAp InteliNano NT
®
System Controller Manual
Standby Generator System
80021813USCN
Revision B
© Briggs & Stratton, LLC.
All rights reserved.
Not for
Reproduction
Table of Contents
Fast User Guide .................................3
System Controller
...............................5
Display Screen Structure
.........................6
Alarms, Events and History
.......................7
Events.................................................. 7
Warnings ............................................... 7
Shut Downs ............................................. 7
ECU Messages .......................................... 8
Start and Stop Engine .................................8
Manual Mode ............................................ 8
Auto Mode .............................................. 8
Not for
Reproduction
ComAp, spol s.r.o.
Kundratka 2359/17
180 00, Praha 8
Czech Republic
InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013
InteliNano-NT-MRS-1.4-Fast User Guide.pdf
CAN INTERFACE
GENERATOR VOLTAGE
MEASUREMENT
T16 = Neutral
T17 = Phase 1
T18 = Phase 2
T19 = Phase 3
USB interface
L
COM
H
INTPUT TERMINALS
T10 = COM for analog inputs
T11 = binary input
T12 = binary input
T13 = binary/analog input Low Fuel Level
T14 = binary/analog input Coolan Temperature
T15 = binary/analog input Oil Pressure
OUTPUT TERMINALS
T04 = binary output Starter (6A)
T05 = binary output - Fuel Solenoid (6A)
T06 = binary output (500 mA)
T07 = binary input/output (500 mA)
POWER SUPPLY, D+
T01 = BATT -
T02 = D+
T03 = BATT +
G
ECU
DIESEL / GASOLINE ENGINE GENERATOR
LOAD
Fuel Solenoid
Battery
Sarter
Fuel Level Analog
Coolant Temperature Analog
Oil Pressure Analog
D+
-
+
Alarm
Ready To Load
Fuel Solenoid
Starter
COM
Remote Start And Load
Emergency Stop
CAN
L COM H
USB
Battery +
Battery -
D +
PC
L1
L2
L3
N
InteliNano NT
MRS Fast User Guide
Typical wiring diagram
Accessing the setup mode
Ensure the engine is stopped and the controller is in Manual mode (green LED above button Auto is turned off).
If you have not configured the custom initialization (init) screen then press and hold Stop button, then briefly press button and then Auto .
If you have already created your own init screen then press and hold Stop button and then briefly press , the custom init screen will appear, keep holding the Stop
button. Then press to switch LCD to default init screen, and then press Auto.
To move up and down in the setup menu use and buttons. Press Start button to select or Stop button for exit.
Basic settings
Input settings
Engine parameters and protections
ECU setting
Generator protections
Info
Output settings
Outputs and inputs
Output
code
Output source
Terminal assignment
O00
Not Used
T04, T05, T06, T07
O01
Starter
T04
O02
Fuel Solenoid
T04, T05, T06, T07
O03
Stop Solenoid
T04, T05, T06, T07
O04
Alarm
T04, T05, T06, T07
O07
Ready To Load
T04, T05, T06, T07
O08
Prestart
T04, T05, T06, T07
O09
ECU Power Relay
T04, T05, T06, T07
O10
Choke
T04, T05, T06, T07
O11
Glow Plugs
T04, T05, T06, T07
Normally Open Contact – output
Normally Open Contact - input
button
Normally Closed Contact – output
Normally Closed Contact – input
button
User curves
I21
I23
I25
VDO Level %
VDO 5 Bar
VDO 40-120 °C
Datcon Level %
VDO 10 Bar
VDO 50-150 °C
Datcon 5 Bar
Datcon High °C
Datcon 7 Bar
Datcon Low °C
Datcon 10 Bar
Not selected
Not selected
Not selected
Input
code
Input source
Type
Terminal assignment
I00
Not Used
binary
T07, T11, T12, T13, T14, T15
I01
Emergency Stop
binary
T07, T11, T12, T13, T14, T15
I02
Remote Start/Stop
binary
T11
I03
Remote Start And Load
binary
T11
I04
Access Lock
binary
T07, T11, T12, T13, T14, T15
I07
GCB Feedback
binary
T07, T11, T12, T13, T14, T15
I10
External Warning 1
binary
T07, T11, T12, T13, T14, T15
I11
External Warning 2
binary
T07, T11, T12, T13, T14, T15
I12
External Warning 3
binary
T07, T11, T12, T13, T14, T15
I13
External Shutdown 1
binary
T07, T11, T12, T13,T14, T15
I14
External Shutdown 2
binary
T07, T11, T12, T13, T14, T15
I15
External Shutdown 3
binary
T07, T11, T12, T13, T14, T15
I20
Low Fuel Level
binary
T07, T11, T12, T13, T14, T15
I21
Fuel Level Analog
analog
T13, T14, T15
I22
Low Oil Pressure
binary
T07, T11, T12, T13, T14, T15
I23
Oil Pressure Analog
analog
T13, T14, T15
I24
High Coolant Temperature
binary
T07, T11, T12, T13, T14, T15
I25
Coolant Temperature Analog
analog
T13, T14, T15
Dimensions
Case dimensions: 118mm x108mm x 40mm
Panel Cutout: 96mm x 96mm
WARNING!
If D+ is not used, connect this terminal to battery positive!
3
Not for
Reproduction
ComAp, spol s.r.o.
Kundratka 2359/17
180 00, Praha 8
Czech Republic
InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013
InteliNano-NT-MRS-1.4-Fast User Guide.pdf
Setpoints
Use and buttons to move or change value. Start button to select setpoint or confirm changes and Stop button to go back.
Basic settings
Setpoint
code
Setpoint name
B01
Nominal Voltage Ph-N
80 – 480 V
B02
Nominal Voltage Ph-Ph
80 – 600 V
B03
Nominal Frequency
50 Hz (1), 60 Hz (2)
B04
Connection Type
Mono Phase (1), SplitPhase (2),
3Ph3Wire (3), 3Ph4Wire (4)
B05
Units Format
Metric unit format (1), US unit
format (2)
B07
Zero Power Mode Delay
0-360 min
B08
Light Tower Mode
Disable (1), Enable (2)
B09
Nominal RPM
100-4000
Engine parameters and protections
Setpoint
code
Setpoint name
E01
Prestart Time
0-600 s
E02
Maximum Cranking Time
0-60 s
E03
Cooling Time
0-3600 s
E04
Oil Pressure Shutdown
0-10 Bar
E05
Coolant Temperature Shutdown
0 -150 °C
E06
Battery Undervoltage
8 – 40 V
E07
Warning Maintenance
0 – 10000 h
E08
Oil Pressure Starter Disengagement
Disable (1), Enable (2)
E09
Choke Time
0 – 3600 s
E10
Minimal Stabilization Time
1 – 300 s
Generator protections
Setpoint
code
Setpoint name
G01
Generator Overvoltage Shutdown
G02 – 200 %
G02
Generator Undervoltage Shutdown
0 - G01 %
G03
Generator Overfrequency Shutdown
G04 – 130 %
G04
Generator Underfrequency Shutdown
0 G03 %
To apply all changes return to the main setup menu and restart the controller by pressing the Stop button.
Alarms and Events
Events
Manual Start
Remote Start
Manual Stop
Remote Stop
Auto On
Auto Off
Power On
Island Operation
Warnings
Warning Maintenance
Low Battery
Low Fuel Level
External Warning 1
External Warning 2
External Warning 3
ECU Communication Error
Shutdowns
Emergency Stop
Overspeed
Underspeed
Low Oil Pressure
High Coolant temperature
External Shutdown 1
External Shutdown 2
External Shutdown 3
GCB Fail
Generator Overvoltage
Generator Undervoltage
Generator Overfrequency
Generator Underfrequency
Generator CCW Rotation
Start Fail
Stop Fail
Battery Flat
ECU
For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide.
Technical data
Power supply range
6-36 VDC
Power supply drop-out immunity
100 ms
Power consumption
35 295 mA
Zero Power Mode consumption
52 - 344 µA
Operating temperature
-20... 70 °C
Operating humidity
95% non-condensing (IEC/EN 60068-2-30)
Protection degree (front panel)
IP65 with GASKET 4x405 only
IP50 without gasket
Storage temperature
-30... 80 °C
Binary outputs (up to 4)
Low current outputs (2)
500 mA
High current output (2)
6 A (long term) / 10 A (short term)
Total output current
10 A (long term) / 16 A (short term)
Binary inputs (up to 6)
Input resistance
1,5 kΏ
Closed contact voltage
<2 V
Open contact voltage
>3,5 V
Analog inputs (up to 3)
Galvanic insulation
Not insulated
Electrical range
0 - 2500 kΏ
Resolution
0,1 Ώ
Precision
2 % ± 3 Ώ
Charging alternator preexcitation circuit
Excitation current
100 mA
Charging fail threshold
80 %
Generator/Mains measurements
Measurement input
3ph generator voltage
Measurement type
True RMS
Voltage range
480 V Ph-Ph (277 V Ph-N)
Max. measured voltage
340 V Ph-N
Voltage accuracy
1%
Frequency range
40 – 70 Hz
Frequency accuracy
1 %
4
Not for
Reproduction
5
Position Button Description
A Up Arrow Press button for move up or value increasing.
B Down Arrow Press button for move down or value decreasing.
C Start Button Works in MANUAL MODE only. Press this button to initiate the
start sequence of the engine. This button is also used to confirm
changes in Setup Mode.
D Engine Operation
LED
GREEN LED is blinking if the engine is starting, cooling or stopping.
When the LED is solid, the engine is running and is loaded or is
ready to load.
E Auto Button Is dedicated for switching between AUTO and MANUAL operating
mode.
F Operating Mode
LED
GREEN LED is solid, the controller is in AUTO mode. When LED is
off, the controller is in MANUAL mode.
G Stop Button Works in MANUAL MODE only. Press this button to initiate the stop
sequence of the generator when engine is running. This button is
also used to cancel changes in setup mode, to go back or to exit
and for alarm confirmation.
H Alarm LED RED LED will blink when there is one or more active warning or
active shutdown alarm(s). The LED is solid when the active shut
down alarm is confirmed and the engine can’t be started.
J Graphic Black and
White Display
128 X 64 Pixels
Stop
Auto
Start
E
A
B
C
J
H
F D
G
System Controller
The system controller, located inside the generator enclosure, is shown below. The features of the controller and
their locations are shown below.
Not for
Reproduction
6 BRIGGSandSTRATTON.COM
The first screen contains basic information about
generator voltage and frequency measurement.
Also displayed is the position (status) of the
GCB (when so configured) and a running hours
counter. When any alarms occur, the general
warning symbol will be displayed on the upper
right corner of the display.
The second screen contains detailed voltage and
frequency information.
The third screen shows engine information – oil
pressure, coolant temperature, fuel level, and
battery voltage.
The fourth screen shows the most recent alarms
or events.
Display Screen Structure
The displayed information is structured into screens. Use the up and down arrows to scroll through the screens.
Not for
Reproduction
7
Alarms, Events and History
The following alarms and records are available:
• Events
• Warnings
• Shutdowns
ECU Messages
Four records can be displayed simultaneously on the
screen. Total capacity is 10 records.
To view further history records, wait until the down
arrow stops blinking (approximately 3 seconds).
For alarm (shutdown) confirmation, press the Stop
button.
Events
Every event is saved in history with a running hours
stamp.
Warnings
Active Warning: When a warning occurs, O04
Alarm output will close and the red LED above the
Stop button will blink. The warning symbol will blink
in the upper right corner of the screen and the proper
warning symbol will be displayed in the event history
screen with a running hours stamp. Active warning
cannot be confirmed.
Inactive Warning: When a warning becomes
inactive, O04 Alarm output will open, the red LED will
stop blinking, and the warning symbol on the screen
will go out.
Shutdowns
Shutdown procedure: The InteliNano® controller
opens outputs O05 GCB Close/Open, O01 Starter,
O08 Prestart, and O02 Fuel Solenoid, and then closes
O03 Stop Solenoid to stop the engine immediately.
O04 Alarm output is closed. Active or not confirmed
protection disables starting.
Active unconfirmed shutdown: When a shutdown
occurs, the shutdown procedure will start, the red LED
above the Stop button will blink, the shutdown symbol
will blink in the upper right corner of screen, and the
proper shutdown symbol will be displayed in the event
history with a running hours stamp. The record in
history is negative. For shutdown alarm confirmation,
press the Stop button.
Active confirmed shutdown: When an active
shutdown is confirmed, the red LED stops blinking.
The record in history stays negative with a confirmation
symbol at the end. O04 Alarm output is open.
Not for
Reproduction
8 BRIGGSandSTRATTON.COM
Inactive unconfirmed shutdown: O04 Alarm
output is closed, the red LED above the Stop button
will blink. The shutdown symbol will be displayed in
the upper right corner of the screen and the proper
warning symbol will be displayed in the event history
with a running hours stamp. For shutdown alarm
confirmation, press the Stop button.
Inactive confirmed shutdown: O04 Alarm output
is opened. It is possible to start the engine when all
shutdowns are inactive and confirmed.
ECU Messages
Diagnostic messages are displayed in the event
history behind the ECU Warning symbol. For Standard
J1939, SPN (Suspect Parameter Number) and FMI
(Failure Mode Identifier) are shown. A complete list of
text diagnostic messages for each ECU can be found
on The Power Portal.
Start and Stop Engine
Manual Mode
When the green LED above the Auto button is off, the
controller is in MANUAL mode. If there is no active
shut down alarm, you can start the engine by pressing
the Start button. The green LED will blink during the
starting, cooling, or stopping procedure. While the
engine is running, the green LED will light steadily.
The generator is ready to load.
Press the Stop button to stop the engine. The first
press will open the GCB and the next press will start
the cooling and stopping procedure. If you press
this button again, the controller will stop the engine
immediately. For fast engine stop, press and hold the
Stop button until the engine stops.
Auto Mode
When the green LED above the Auto button is on, the
controller is in AUTO mode. The engine cannot be
started by pressing the Start button. The controller will
automatically start the engine when all conditions for
starting and connecting loads have been met.
NOTICE
When in AUTO mode, the engine CANNOT
be stopped by pressing the Stop button.
Not for
Reproduction
20 BRIGGSandSTRATTON.COM
Guide de démarrage rapide n’est pas disponible en Français
Not for
Reproduction
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24