Tags Section 14 (72)
Tag Parameters: Historical Logging
Historical Logging If enabled, the values of the tag will be logged in a circular file.
This is a non-volatile logging. The data is stored in the flash file system. All the data is
stored in the same file, the maximum number of values that can be saved is from ~314572
to ~996147, depending on the resources storage setup of the Flexy. When maximum size
is reached, the oldest data will be erased first.
Logging Deadband Defines the deadband of the incremental recording of the tag. Setting a negative value
will disable it.
Logging Interval Defines the interval, in seconds, for the tag recording. Setting 0will disable it.
Can be used at the same time as logging deadband.
Tag Parameters: Real-time Logging
Real-time Logging If enabled, the values of the tag will be logged in memory.
Real-time logging is different than historical logging because the data is saved in a circular
memory buffer. The other difference is that incremental recording is not possible, only
fixed interval recording can be performed.
Time Span Defines the total logging window time in seconds.
Logging Interval Defines the interval, in seconds, of the tag recording.
Tag Parameters: Tag Visibility
Published Value The value published by the Flexy could be the same as the tag value or could be modified
with a scale factor and an offset.
Modbus TCP visibility If enabled, the tag will be visible.
Each tag in the Flexy can be accessed through a Modbus TCP master.
Register The address of the register, starting with 1.
Only the register address has to be specified, the type of tag (coil, contact, input register
or holding register) is obtained from the tag type (analog or boolean) and the tag read-
only or read/write property (obtained from the IO server).
Use 32-bit format If checked then 2 consecutive 16 bits registers will be reserved and the value will be an
output as a 4 bytes IEEE float in those 2 registers (standard Modbus float representation).
If the tag is published as integer it may need to be scaled to fit the 16 bits Modbus register.
This operation will be applied to the tag value before publishing it.
SNMP visibility If enabled, the tag can be seen by the SNMP manager.
KPI If enable, the tag name, value and description will appear in the summary page.
OID The base OID is already defined, the only parameter is the last part of the OID.
Tag groups Allows the grouping of tags into group (from A to D).
5.1.2.3 Configuration of an Alarm Tag
The configuration of an alarm for a specific tag can be done either by clicking on the “Configure
Alarm actions” button (when a tag has been selected) or on the alarm icon located in the tag row.
Send an Email
Email upon Checks the alarm states triggering an email (ALM, ACK, RTN, END).
Format as short message In some cases, it is useful to have the whole message sent in the subject field.
For example: if the email should be routed as an SMS.