Danfoss Wireless Floorheating Installation guide

Type
Installation guide
CFM/CFS CFR CFZ
Danfoss A/S 03/2001 DKCD VI.88.M2.22
088R0227
INSTRUCTIONS FOR INSTALLATION
The floor heating system consists of:
- Master controller CFM
- Slave controller CFS (if > 8 heating outputs)
- Room thermostats CFR
- Setback programmer CFZ (optional)
Master controller CFM
This controller governs the individual heat outputs via
wireless communication with the associated CFR.
Connection of 8 heating outputs is possible.
If more heating outputs are required, connect one or
max. two slave controllers CFS, each with connections
for 8 outputs. This allows max. 24 heating outputs to be
controlled.
The master/slave should be installed above the mani-
folds or near pump relay. Ensure easy access to plugs
and terminals. See instruction drawing on the opposite
page.
If two slave controllers are connected, move the jumper
in “slave 2” to position 2. See instruction drawing.
The connection cable for the CFS is 1 m (3.5 ft). Cable
lengths of up to 100 m can be used. Longer lengths
available from electrical suppliers.
Alarm
2 options available with respect to alarms given by the
CFM:
-Internal acoustic alarm can be selected by moving the
jumper marked “buzzer” from OFF to ON. See installa-
tion drawing.
-External alarm can be connected to the external alarm
relay marked %.
Technical data
Max. ambient temperature 140°F.
Voltage 24 AC, 60 Hz, 75 VA
Enclosure IP40
Room thermostat CFR
Before mounting the CFR(s), each must be assigned to
the CFM controller.
See the instructions that come with the room thermostat.
It is important to mark the CFR, e.g. with room or number,
to know where in the building it belongs. Labels are sup-
plied.
Zone regulator CFZ (Optional)
The setback programmer governs a maximum of 6 mas-
ter zones. For each zone an individual timing program
can be set. For reading and operating convenience, it is
recommended to place the CFZ at eye level.
The connection cable is 5 m (16 ft). Cable lengths up to
100 m (328 ft) are allowed. Additional lengths available
from electrical suppliers.
230 VAC:
T0.5 A+F4 A
Typical wiring diagram
%
Dry Contact
External Alarm
Boiler / Circulator
End Switch
Power In
24 V ac, 75VA
Power In
24 V ac, 75VA
External
Antenna
Pump: 115V, 1 phase,
60 Hz, 3A max.
T 1.25 A protects outputs
T 0.5 A protects controller
L1
L2
L1
L2
Putting into operation
LED for CFM
LED for CFS 1
LED for CFS 2
Fig.1
Fig. 2
Column and row LEDs show the
operating mode of the outputs.
Light: heat is “ON” to the room.
No light: heat is “OFF” to the
room
Example: When the LEDs of
the 4th column and the 1st
row are lit, heat is supplied to
output 4 of the CFM.
LED row for outputs
Assigning CFR to output(s)
-Connect the room thermostat (fig. 1) to the CFM, via the black
installation cable. The first vacant output in the registration
field will flash. Other vacant outputs will be lit, while outputs al-
ready registered will not be lit (fig. 2).
-If OK is pressed briefly, the room thermostat will be assigned
to the first available output causing the LED to go off (fig. 2).
If the CFR is to be assigned with more than one output, go to
these outputs by means of the +/- keys and confirm by press-
ing OK briefly.
When the installation cable is removed, the red LED under-
neath the battery cover (fig. 1) will flash for at least 3 minutes
(Thermostat in test mode).
Removal of assigned room thermostat
The CFR and the CFM must not be connected.
-Hold OK for 5 sec, the first LED in the row for assigned CFR(s)
will flash (fig. 2). Other LEDs for assigned CFR(s) will flash.
-Use the +/- keys to go to the CFR to be removed (it will flash).
-Confirm removal by pressing OK for 5 sec.. The LED light will
go off.
Test of CFR
If a defect in a CFR is suspected, the following test may be
carried out:
-Set the thermostat to the highest temperature.
-Move the function switch located on the right side of the
thermostat to a new position.
-If the LED underneath the battery cover (fig. 1) flashes quickly
within the first minute, the CFR is in order.
Transmission interval
A CFR transmits regularly. When a signal is received by the
CFM, two quick flashes are seen. Subsequently, the normal
operating mode will be displayed.
Operation
During normal operation, the status of the CFM outputs are
shown.
If the status of the outputs of the CFS is to be shown, scroll by
means of the +/- keys. After approx. 10 sec. the system reverts
to the output status of the CFM.
Troubleshooting
FCC ID: PGBTYPE-CFR , CAN 3934104209
This device complies with Part 15 of the FCC Rules and with
RSS-210 of Industry Canada and with RSS-210 of Industry
Canada:
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received,
including interference that may cause undesired operation.
Warning: Changes or modifications to this unit not expressly
approved by the party responsible for compliance could void
the user’s authority to operate the equipment.
In the event pump zoning is used a
separate relay box, CPR, is needed
(Part 088HPRLY)
Max. 4 outputs per relay box. If 5-8
outputs are required then two relay
boxes are needed. Wire controller
outputs to relay box according to
typical wiring diagram. Electrical
specifications for zoning circulator
pump: Single phase, 115 V, 60 Hz,
and max. 3 A.
Pump Zoning Relay
Max. load for
CFM 6W,
max. Load
for CFS 3W
CFM controller output array
blinks specifically from a
row and column(s)
Alarm symbol in zone
controller, CFZ flashes
Acoustic alarm buzzes
(provided jumper is set to
ON)
Constant light in LED array
LED on back of room
thermostat does not blink
during test mode
Slave controller row(s) and
entire columns lit on master
output array
CFM controller output array
blinks rapidly for 3 minutes
specifically from a row and
column(s)
All output LED lights are
unresponsive
Lack or excessive heat
to floor heating system
Room temperature is
below 6
o
C (43
o
F)
No heat
No heat
Lack or excessive heat
to floor heating system
None
If signal is
continuosly
poor contact
Danfoss
Distance between room and
master is too far.
Degradation of signal due to
reinforced concrete or foil faced
insulation between floors.
External antenna mounted close
to metal parts or wires.
Master control is placed in
metal enclosure.
Interference from electronic
equipment using the same
frequency, 433.92Mhz (i.e. baby
monitors, portable or wireless
headphones)
Low battery
Problem in heating system or
signal to thermostat
Blown fuse in master/slave
Loose wire connection between
master and slave controller
Defective zone actuator
Lack of heated fluid to system
No heat
Faulty battery
Bad contacts between battery
and thermostat
Defective room thermostat
Improper wiring
Master controller is defective
Normal operation during
test of room thermostat
· Reposition thermostat in room
until signal is clear.
· Reposition external antenna,
however if signal is still unclear
move external antenna to the
same floor as thermostat(s)
· Reposition room thermostat and
run test mode
· Mount external antenna if not
already installed.
· Eliminate interfering electronic
equipment
· Replace battery and test
thermostat
· Check heating supply to the
system and the circulator pump
· Check master control, CFM, is
properly wired.
· First check actuators for proper
wiring then replace fuse in
master/slave controller, 1.25A
· Check wire and connection
between master and slave
· Replace zone actuator
· Check heating supply to the
system and the circulator pump
· Replace battery, Lithium AA 3.6V
· Adjust connection in thermostat to
ensure better contact to battery
· Replace room thermostat
Refer to I
NSTRUCTIONS FOR
INSTALLATION
· Check wiring of power to CFM
· Replace master controller
Appearance Problem Reason / Cause Solution Comments
  • Page 1 1
  • Page 2 2

Danfoss Wireless Floorheating Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI