Daniel Model 2470 Solarflow Plus Owner's manual

Type
Owner's manual
MODEL 2470
SOLARFLOW PLUS
__________________________________________
DANIEL MEASUREMENT AND CONTROL
HOUSTON, TEXAS
"AGA-3 DUAL"
HHDT EPROM 8-2470-178
LC EPROM 8-2470-173
LD EPROM 8-2470-172
Part Number: 3-9003-009
REVISION Q
MAY 1997
MODEL 2470 SOLARFLOW PLUS ENRON AGA-3 DUAL __________________________
MAY 1997
DANIEL INDUSTRIES, INC.
Model 2470 SolarFlow Plus
ENRON AGA-3 Dual Meter Run
Application Manual
NOTICE
DANIEL INDUSTRIES, INC. AND DANIEL MEASUREMENT ANC CONTROL ("DANIEL")
SHALL NOT BE LIABLE FOR TECHNICAL OR EDITORIAL ERRORS IN THIS MANUAL
OR OMISSIONS FROM THIS MANUAL. DANIEL MAKESNO WARRANTIES, EXPRESS
OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THIS MANUAL
AND, IN NO EVENT, SHALL DANIEL BE LIABLE FOR ANY SPECIAL OR
CONSEQUENTIAL DAMAGES INCLUDING, BUT NOT LIMITED TO, LOSS OF
PRODUCTION, LOSS OF PROFITS, ETC.
PRODUCT NAMES USED HEREIN ARE FOR MANUFACTURER OR SUPPLIER
IDENTIFICATION ONLY AND MAY BE TRADEMARKS/REGISTERED TRADEMARKS OF
THESE COMPANIES.
COPYRIGHT © 1997
BY DANIEL MEASUREMENT AND CONTROL
HOUSTON, TEXAS, U.S.A.
All rights reserved. No part of this work may be reproduced or
copied in any form or by any means - graphic, electronic or
mechanical - without first receiving the written permission of
Daniel Measurement and Control, Houston, Texas, U.S.A.
PREFACE i
__________________________ MODEL 2470 SOLARFLOW PLUS ENRON AGA-3 DUAL
MAY 1997
WARRANTY
Daniel Measurement and Control ("Daniel") warrants all equipment manufactured by it to be free
from defects in workmanship and material, provided that such equipment was properly selected
for the service intended, properly installed, and not misused. Equipment which is returned,
transportation prepaid to Daniel within twelve (12) months of the date of shipment (eighteen (18)
months from date of shipment for destinations outside of the United States), which is found after
inspection by Daniel to be defective in workmanship or material, will be repaired or replaced at
Daniel’s sole option, free of charge, and return-shipped at lowest cost transportation. All
transportation charges and export fees will be billed to the customer. Warranties on devices
purchased from third party manufacturers not bearing a Daniel label shall have the warranty
provided by the third party manufacturer.
Extended warranty - Models 2470, 2480 and 2500 are warranted for a maximum of twenty-four
(24) months. The Danalyzer valves are warranted for the life of the instrument and the columns
for five years.
The warranties specified herein are in lieu of any and all other warranties, express or implied,
including any warranty of merchantability or fitness for a particular purpose.
Daniel shall be liable only for loss or damage directly caused by its sole negligence. Daniel’s
liability for any loss or damage arising out of, connected with, or resulting from any breach
hereof shall in no case exceed the price allocable to the equipment or unit thereof which gives
rise to the claim. Daniel’s liability shall terminate one year after the delivery of the equipment
except for overseas deliveries and extended warranty products as noted above.
In no event, whether as a result of breach of warranty or alleged negligence, shall Daniel be
liable for special or consequential damages, including, but not limited to, loss of profits or
revenue; loss of equipment or any associated equipment; cost of capital; cost of substitute
equipment, facilities or services; downtime costs; or claims of customers of the purchaser for
such damages.
ii PREFACE
MODEL 2470 SOLARFLOW PLUS ENRON AGA-3 DUAL __________________________
MAY 1997
TABLE OF CONTENTS
Section Page
SECTION 1 INTRODUCTION
1.0 INTRODUCTION ..........................................1-1
1.1 Scope of this Manual ......................................1-1
1.2 SolarFlow Plus and HHDT Eproms for the Enron
AGA-3 Dual Meter Application ..............................1-2
1.3 Installation Configuration for the Enron Dual
Meter Run AGA-3 Application with One DP
Transmitter per Meter Tube ................................1-3
SECTION 2 CALCULATIONS
2.0 ENRON DUAL AGA-3 (AGA-3 DUAL) CALCULATION MODULE .....2-1
2.1 Flow Rate ..............................................2-1
2.2 Orifice Flow Constant (C
f
) ..................................2-2
2.3 Calculation Cycles ........................................2-3
SECTION 3 CONNECTIONS AND SETTINGS
3.0 FIELD WIRING CONNECTIONS ..............................3-1
3.1 Analog Input Connections ..................................3-1
3.2 Status Input Signal Connections ..............................3-4
3.3 Output Signal Connections ..................................3-5
3.3.1 Form-A Relay Output ...................................3-5
3.3.2 TTL-Level Signal Termination Board Pin Numbers ...............3-6
3.3.3 Analog Output Connection ................................3-6
3.4 Slide Switch Settings ......................................3-7
3.4.1 Changed Slide Switch Settings
for PC Board 3-2470-008 ................................ 3-10
SECTION 4 SETUP LOCATION MENU
4.0 SETUP LOCATION MENU ...................................4-1
SECTION 5 SECURITY CODE LIST
5.0 SECURITY CODE LIST .....................................5-1
TABLE OF CONTENTS iii
__________________________ MODEL 2470 SOLARFLOW PLUS ENRON AGA-3 DUAL
MAY 1997
SECTION 6 SETUP UNIT MENU
6.0 SETUP UNIT MENU ........................................6-1
6.1 General Submenu ........................................6-1
6.2 Inputs Submenu .........................................6-2
6.3 Outputs Submenu ........................................6-3
6.4 Scales Submenu ..........................................6-4
6.5 Config Submenu .........................................6-5
6.6 Factors Submenu .........................................6-7
6.7 Setpoints Submenu .......................................6-7
SECTION 7 DISPLAY MENU
7.0 DISPLAY MENU ...........................................7-1
SECTION 8 CALIBRATE UNIT MENU
8.0 CALIBRATE UNIT MENU ...................................8-1
8.1 Accepting and Rejecting Calibration ...........................8-1
8.2 PRES ALL .............................................8-2
8.3 DIFF BIAS .............................................8-2
8.4 Others .................................................8-2
SECTION 9 MONITOR MENU
9.0 MONITOR MENU ..........................................9-1
SECTION 10 CHANNEL ASSIGNMENTS
10.0 ENRON AGA-3 DUAL CHANNEL ASSIGNMENTS ............... 10-1
10.1 User Report (Channel Zero) ................................ 10-1
10.2 Channel 1 Through 18 Assignments .......................... 10-2
10.3 Channel 19 Through 28 Assignments ......................... 10-3
10.4 Channel 29 Through 98 Assignments ......................... 10-4
SECTION 11 DATA LOG LIST
11.0 DATA LOG LIST ......................................... 11-1
11.1 One-Hour Log Interval ................................... 11-1
11.2 Twenty-Four Hour Log Interval ............................. 11-2
iv TABLE OF CONTENTS
MODEL 2470 SOLARFLOW PLUS ENRON AGA-3 DUAL __________________________
MAY 1997
SECTION 12 ALARM LIST
12.0 ALARM LIST ............................................ 12-1
LIST OF ILLUSTRATIONS
Figure 1 - Installation Configuration for the ENRON AGA-3
Dual Meter SolarFlow Plus Application with
One Differential Pressure Transmitter per Tube .................1-3
Figure 2 - Model 2470 Slide Switch Locations
(PC Board Assembly Part No.3-2470-000) .....................3-8
Figure 3 - Model 2470 Slide Switch Locations
(PC Board Assembly Part No.3-2470-008) .....................3-9
APPENDICES
Appendix A Modbus Communications - ENRON Register Assignments
AGA-3 Dual ENRON Application ......................... A-1
TABLE OF CONTENTS v
__________________________ MODEL 2470 SOLARFLOW PLUS ENRON AGA-3 DUAL
MAY 1997
This page intentionally left blank.
vi TABLE OF CONTENTS
MODEL 2470 SOLARFLOW PLUS ENRON AGA-3 DUAL __________________________
MAY 1997
1.0 INTRODUCTION
1.1 SCOPE OF THIS MANUAL
A SolarFlow Plus unit delivered from the factory is fitted with a set of erasable, programmable,
read-only memories (EPROMs) configured for the application or applications for which the
SolarFlow Plus is intended. The Hand Held Data Terminal (HHDT) provided with a SolarFlow
Plus unit is compatible with the same application or applications.
Basic reference information on the Model 2470 SolarFlow Plus system is provided in the System
Reference Manual (Daniel part number 3-9000-451). The System Reference Manual includes
sections on system hardware, software, installation, and operating procedures for both the
SolarFlow Plus computer and the HHDT.
Information on each application of the Model 2470 SolarFlow Plus is provided in a separate
application manual. The application manual also provides references to the System Reference
Manual whenever more detailed information is available in the reference manual. The application
manual together with the System Reference manual, provides a complete information package
for a specific installation of the Model 2470 SolarFlow Plus system.
This application manual provides specific information on a Model 2470 SolarFlow Plus unit and
the associated HHDT configured for the ENRON dual-meter AGA-3 application. Because an
individual configuration of a SolarFlow Plus unit may differ in some respects from the basic
system, information provided by the basic reference manual and this application manual may also
differ. When differences are noted, the information contained in the application manual takes
precedence.
SECTION 1
1-1
____________________________________________________ MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL
MAYMAY 19971997
This applications manual includes sections on:
- Calculation modules for the ENRON AGA-3 dual-meter run application
- Field wiring connections for applicable inputs and outputs
- SETUP LOCATION menu parameters for the Hand Held Data Terminal (HHDT)
- SETUP UNIT menu parameters for the HHDT
- DISPLAY, CALIBRATE UNIT, and MONITOR menus for the HHDT
- Default user report listing
- Channel assignments for the unit
- Default data log list
- Default security codes
1.2 SOLARFLOW PLUS AND HHDT EPROMS FOR THE ENRON AGA-3
DUAL-METER APPLICATION
The Model 2470 SolarFlow Plus unit configured for the ENRON AGA-3 dual-meter application
is fitted with the following EPROMs.
LC EPROM, Daniel part number 8-2470-173
LD EPROM, Daniel part number 8-2470-172
The Hand Held Data Terminal is fitted with:
HHDT EPROM, Daniel part number 8-2470-178
INTRODUCTION
1-2
MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL ____________________________________________________
MAYMAY 19971997
1.3 INSTALLATION CONFIGURATION FOR THE ENRON DUAL METER RUN
AGA-3 APPLICATION WITH ONE DP TRANSMITTER PER METER TUBE
The SolarFlow Plus ENRON dual-meter run AGA-3 application is designed for installations with
two orifice-meter tubes. The application has:
- One differential pressure (DP) transmitter per tube
- One static pressure transmitter per tube
- A common temperature transmitter
- A common specific gravity input
Figure 1 shows the installation configuration for the transmitters in the ENRON dual-meter
AGA-3 application.
DP1 P1
][
SG T
||
DP2 P2
][
Figure 1. Installation Configuration for the ENRON AGA-3
Dual Meter SolarFlow Plus Application with One
Differential Pressure Transmitter per Tube
SECTION 1
1-3
____________________________________________________ MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL
MAYMAY 19971997
This page intentionally left blank.
INTRODUCTION
1-4
MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL ____________________________________________________
MAYMAY 19971997
2.0 ENRON DUAL AGA-3 (AGA-3 DUAL) CALCULATION MODULE
This manual supports a SolarFlow Plus computer configured to calculate orifice-meter
measurements in accordance with the American Gas Association (AGA) Gas Measurement
Committee Report No.3 (AGA-3), Orifice Metering of Natural Gas, (ANSI/API 2530 Second
Edition, September 1985). Supercompressibility is calculated in accordance with AGA Standard
NX-19 - Manual for the Determination of Supercompressibility Factors for Natural Gas.
2.1 FLOW RATE
In general, the equation for calculating flow rate is:
Where:
Q
h
= corrected flow rate in thousands of standard cubic feet per hour (MCF/HR)
C
f
= orifice flow constant calculated using the equation in 2.2
h
w
= differential pressure in inches of water
P
f
= static pressure in pounds per square inch, absolute (PSIA)
SECTION 2
2-1
____________________________________________________ MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL
MAYMAY 19971997
2.2 ORIFICE FLOW CONSTANT (C
f
)
The equation for calculating the orifice flow constant (C
f
) is:
Where:
F
b
= basic orifice factor
F
g
= specific gravity factor
F
pv
= supercompressibility factor
F
tf
= flowing temperature factor
F
ry
= result of multiplying: F
pb
,F
tb
,F
r
,Y,F
a
Where:
F
pb
= pressure base factor
F
tb
= temperature base factor
F
r
= Reynolds number factor
Y = expansion factor
F
a
= orifice thermal expansion factor
NOTE:NOTE: F
pv
calculations are limited to adjusted pressures of 0 to 2000
pounds per square inch (PSI) and adjusted temperatures of -40 to
240 degrees Fahrenheit (
o
F).
The calculation methods of Channels 59, 63, 70, and 74 have been modified especially for
ENRON. They represent the average extension factors for the last hour or last day over the
flowing time period. The Extension Factor is defined as the square root of the product of
differential pressure and static pressure, i.e.
CALCULATIONS
2-2
MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL ____________________________________________________
MAYMAY 19971997
2.3 CALCULATION CYCLES
During normal SolarFlow Plus operation, calculations are performed continuously. Each
complete set of calculations is based on a calculation cycle. The time required to complete a
calculation cycle depends on processor speed and the extent of data communication required by
the application calculation module.
The SolarFlow Plus computer calculates the critical part of the flow rate calculation, extension
factor, ( h
w
.
P
f
)
.5
, every half second. The computer calculates the factors included in the flow
constant (C
f
), at an interval defined by the application program, typically every 15 to 25 seconds.
The factors in C
f
that are dependent upon sampled input values use the average of the 0.5-second
samples in each calculation.
For example, if an application takes 20 seconds to calculate a new C
f
value, a total of 40
extension factors are calculated during the C
f
calculation interval. In addition, 40 samples of
each analog input are obtained and averaged during the same period of time. SolarFlow Plus
sums up and averages the individual extension factors then multiplies the result by the latest
calculated value of C
f
to produce an updated value for flow rate.
At the end of each flow rate calculation cycle, SolarFlow Plus updates channel values that are
dependent on the calculated value of flow rate, such as flow rate, and total volume.
SECTION 2
2-3
____________________________________________________ MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL
MAYMAY 19971997
This page intentionally left blank.
CALCULATIONS
2-4
MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL ____________________________________________________
MAYMAY 19971997
3.0 FIELD WIRING CONNECTIONS
NOTE: Before connecting analog inputs to the SolarFlow Plus unit, make
sure slide switch settings are in accordance with section 3.3.3.
3.1 ANALOG INPUT CONNECTIONS
Analog inputs for the dual-meter AGA-3 application of the Model 2470 SolarFlow Plus are
connected in accordance with the table below.
NOTE: Configurations for this application include the static pressure and
DP transmitters associated with meter 1 installed within the Model
2470 enclosure with all other transmitters installed externally, or
with all transmitters installed externally. The following information
furnishes necessary details for wiring both internal and external
transmitters.
A field wiring diagram is provided in the Model 2470 System Reference Manual.
SECTION 3
3-1
____________________________________________________ MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL
MAYMAY 19971997
CH TRANSMITTER TYPE WIRE
COLOR
TB1
PIN NO.
SIGNAL TYPE
20 INTERNAL, static pressure,
Meter tube No.1
(factory installed)
White (Blue)
(1)
Green (Black)
(1)
Black (Red)
(1)
23
25
26
Signal in +
Analog ground
8to10VDC
or
20 EXTERNAL, static pressure,
Tube No.1 (to be installed by
user)
Blue
Black
Red
Shield
23
26
25
24
Signal in +
Analog ground
8to10VDC
Earth ground
21 INTERNAL, differential
pressure (DP), Meter tube No.1
(factory installed)
Violet
Black
Gray
27
30
29
Signal in +
Analog ground
8to10VDC
or
21 EXTERNAL, DP, Meter tube
No.1 (to be installed by user)
Blue
Black
Red
Shield
27
30
29
28
Signal in +
Analog ground
8to10VDC
Earth ground
22 EXTERNAL, common
temperature (to be installed by
user)
Blue
Black
Red
Shield
31
34
33
32
Signal in +
Analog ground
8to10VDC
Earth ground
23
(2)
EXTERNAL, static pressure,
Meter tube No.2 (to be installed
by user)
Blue
Black
Red
Shield
35
38
37
36
Signal in +
Analog ground
8to10VDC
Earth ground
24
(2)
EXTERNAL, DP, Meter tube
No.2 (to be installed by user)
Blue
Black
Red
Shield
39
42
41
40
Signal in +
Analog ground
8to10VDC
Earth ground
25 External common specific
gravity
(3)
(to be installed by
user)
(4)
43
46
Signal in +
Analog ground
26 None, jumper pin 47 to 50 Black
Black
47
50
Signal in +
Analog ground
CONNECTIONS AND SETTINGS
3-2
MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL ____________________________________________________
MAYMAY 19971997
NOTES:NOTES: (1) SolarFlow Plus units fitted with Statham 36PG series static
pressure transmitters are wired with the Blue, Black, and
Red wires.
(2) If SolarFlow Plus is configured as a single meter run, install
a jumper wire from pin 35 to 38 for channel 23 and a
jumper wire from pin 39 to pin 42 for channel 24.
(3) Live SG is optional; see Status Input Channel No.9.
(4) The wire for connecting the specific gravity transmitter is
user supplied.
(5) Any analog inputs not used must have their respective
"Signal in" terminal jumpered to their "Analog ground"
terminal.
SECTION 3
3-3
____________________________________________________ MODELMODEL 24702470 SOLARFLOWSOLARFLOW PLUSPLUS ENRONENRON AGA-3AGA-3 DUALDUAL
MAYMAY 19971997
3.2 STATUS INPUT SIGNAL CONNECTIONS
This application supports two status input conditions that are activated by means of a dry contact
closure between the status input channel and common. The following details the pin-out
arrangement for the status inputs.
CH DESCRIPTION LABEL TB1
PIN NO.
SIGNAL TYPE
1 Status 1 60
51
Spare input
Common
2 Status 2 61
52
Spare input
Common
3 Status 3 62
53
Spare input
Common
4 Status 4 63
54
Spare input
Common
9 Fixed SG option FIXED 64
59
Status in (Open) indicates FIXED
specific gravity to be used
Common (Shorted) indicates LIVE
specific gravity to be used
10 Single or Dual
Pressure
Transmitter
DUAL TRAN 65
58
Status in (Open) indicates use of
dual pressure inputs
Common (Shorted) indicates use of
a single pressure input*
16 Status 5 66
57
Spare input
Common
17 Status 6 67
56
Spare input
Common
18 Status 7 68
55
Spare input
Common
* When a single pressure transmitter is chosen, the front panel LCD displays this as 023
AUX PRES while the HHDT will continue to display this as 023 METER PRES 2.
CONNECTIONS AND SETTINGS
3-4
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72