DSE DSE9130, DSE9150, DSE9155, DSE9255 User manual

  • Hello! I am an AI chatbot trained to assist you with the DSE DSE9130 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
DSE
®
The 2 Amp, 3 Amp and 5 Amp
Battery Chargers have been
designed to be permanently
connected to a battery, keeping it
charged to maximum capacity.
The chargers can be either
mounted via DIN rail or to the
chassis, using the fixing holes that
are built into the case. The chargers
stylish design includes an LED
indicator on the front that shows
when the charger is in a normal or
overload condition.
The chargers will continue to
operate during cranking and
running. All chargers can accept
multiple AC voltage connections.
The DSE battery chargers are
expertly designed using high-grade
components and capacitors
allowing the units to function more
efficiently, providing a longer and
more reliable life-span than other
chargers in their class. Their in-
built robustness makes them ideal
for the rigours of a wide variety of
markets including heavy and light
industrial environments.
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITY
B
S EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30
o
C
BS EN 60068-2-2
Bb/Be Dry Heat +55
o
C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three
major axes
5
Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55
o
C
@
95% RH 48 Hours
B
S EN 60068-2-78
C
ab Damp Heat Static 40
o
C
@ 93% RH 48 Hours
S
HOCK
B
S EN 60068-2-27
T
hree shocks in each of three major axes
1
5 gn in 11 mS
ISSUE 5
CHARGE OUTPUT AC POWER SUPPLY
FEATURE LIST TO SUIT A WIDE VARIETY
OF APPLICATIONS

DSE9000
CHARGE BOOST INPUT
(Not available for DSE9150 & DSE9155)
N/C VOLT FREE CHARGE FAIL OUTPUT
(Not available for DSE9150)
1 1
COMPATIBLE WITH ALL DSE MODULES
1ph
N
DSE9130
,
DSE915
0,
DSE9
155
&
DSE
9255
C
O
M
P
AC
T
B
AT
T
ERY
C
H
AR
G
E
R
S
2
AM
P,
3
AM
P
&
5
AM
P
O
PT
I
O
N
S
F
E
A
T
U
R
E
S
ADVANCED FEATURES

Constant current- maximum
current available during charge
recovery phase
Constant voltage
Chargers automatically return to
float mode when charging is
complete

Makes the chargers ideal for all
battery types

Reverse polarity protection,
short circuit protection and
current limiting
Automatic recovery after the
removal of fault conditions

Boosts and equalises cell
charge improving battery
performance and life
Simple boost connection using
on-board terminals

Once the battery is fully
charged the chargers switch to
Eco-Power to save energy
KEY BENEFITS
Suitable for a wide range of
battery types
No moving parts for longer
battery charger life
Switched mode design
Charge fail output
Minimum 80% efficiency
throughout full operating range

Multiple modules can be linked
together to provide larger current
output
DSE9150 - 3 A 12 V
DSE9130 - 5 A 12 V
DSE9155 - 2 A 30 V
DSE9255 - 5 A 24 V
DEEP SEA ELECTRONICS PLC UK
Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com
DEEP SEA ELECTRONICS INC USA
3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com
055-059/10/10 (7)
RELATED MATERIALS
TITLE PART NO’S
DSE9000 Series Installation Instructions 053-049
DSE9000 Series Operator Manual 057-085
D
S
E
9
1
3
0
,
D
S
E9
1
5
0
,
D
S
E9
1
5
5
&
D
S
E9
2
5
5
C
OM
P
A
C
T
B
AT
TE
R
Y
C
H
A
R
GE
R
S
2
A
M
P,
3
A
M
P
&
5
A
M
P
O
P
T
I
O
NS
®
DSE
F
E
AT
U
R
E
S
Registered in England & Wales No.01319649
VAT No.316923457
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change
the details shown on this data sheet without prior notice. The contents are intended for guidance only.
SPECIFICATION
AC SUPPLY
FREQUENCY RANGE
48 Hz to 64 Hz
DSE9130 & DSE9255 VOLTAGE RANGE
90 V to 305 V (L-N)
DSE9150 VOLTAGE RANGE
90 V to 265 V (L-N)
DSE9155 VOLTAGE RANGE
85 V to 265 V (L-N)
DC OUTPUT
DSE9130 OUTPUT
5 A DC 12 V DC at 13.7 V DC
DSE9150 OUTPUT
3 A DC 12 V DC at 13.7 V DC
DSE9155 OUTPUT
2 A DC 30 V DC at 34.3 V DC
DSE9255 OUTPUT
5 A DC 24 V DC at 27.4 V DV
RIPPLE AND NOISE
<1%
EFFICIENCY
>80%
REGULATION
LINE
<0.001% Vo
LOAD
1% Vo
PROTECTIONS
Short Circuit
Over Voltage
Over Current
Reverse Polarity
DIMENSIONS
DSE9150 DIMENSIONS
108 mm x 101 mm x 49 mm
4.2” x 4” x 1.9”
WEIGHT
0.16 kg
DSE9130, DSE9155 & DSE9255
DIMENSIONS
136 mm x 140 mm x 63 mm
5.4” x 5.5” x 2.5”
WEIGHT
0.5 kg
OPERATING TEMPERATURE RANGE
-30 °C to +55 °C
-22 °F to +122 °F
STORAGE TEMPERATURE RANGE
-40
o
C to +85
o
C
-40 °F to +185 °F
DSE9000 Series Battery Charger Operator Manual ISSUE 13
DEEP SEA ELECTRONICS PLC
DSE9000 SERIES BATTERY CHARGER
OPERATOR MANUAL
Document Number: 057-085
Author: Ashley Senior
DSE9000 Series Battery Charger Operator Manual
2
Deep Sea Electronics Plc
Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND
Sales Tel: +44 (0) 1723 890099
Sales Fax: +44 (0) 1723 893303
E-mail: sales@deepseaplc.com
Website: www.deepseaplc.com
DSE9000 Series Battery Charger Operator Manual
© Deep Sea Electronics Plc
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents
Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication
should be addressed to Deep Sea Electronics Plc at the address above.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.
Amendments since last publication
Issue
. No.
Comments
1 Added Efficiency curve of 2A charger
2 Updated specs table of 3.7A charger
3 Added 5A DSE9255 charger and 9250-002 277V input charger
7 Added DSE9155 30V 2A charger
8 Added 10A charger
8.1 Added Indication (LED) for 10A chargers
8.2 Added detail regarding -002- chargers asnd cabinet/industrial chargers
9 Added 9400 series
9.1 Corrected specs for 9140
10 Removed all DSE9400 series chargers, added DSE9470
11 Added new DSE9400 series Chargers
12 Changes to add DSE9150 12V 3A
13
Updated DSE9470 and DSE9480 to -003 (MKII) and added DSE9472MKII and
DSE9481 MKII
Typeface : The typeface used in this document is Arial. Care should be taken not to mistake the upper
case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.
DSE9000 Series Battery Charger Operator Manual
3
1
BIBLIOGRAPHY .................................................................................................. 5
1.1
INSTALLATION INSTRUCTIONS ....................................................................................... 5
1.2
MANUALS .......................................................................................................................... 5
3
SPECIFICATIONS ............................................................................................... 7
3.1
PART NUMBERING ............................................................................................................ 7
3.1.1
DSE9100 CHASSIS MOUNT BATTERY CHARGERS .................................................. 7
3.1.2
DSE9200 CHASSIS MOUNT BATTERY CHARGERS .................................................. 8
3.1.3
DSE9400 MKII SERIES CHASSIS MOUNT BATTERY CHARGERS ............................ 9
3.1.4
DSE907 INDUSTRIAL / DSE908 CABINET MOUNTED BATTERY CHARGERS ........ 10
3.2
COMMON ELECTRICAL SPECIFICATIONS .................................................................... 11
3.3
COMMUNICATION PORT USAGE .................................................................................. 12
3.3.1
USB CONNECTION ................................................................................................... 12
3.3.2
RS485 ........................................................................................................................ 13
3.5
OUTPUT SPECIFICATIONS ............................................................................................. 15
3.5.1
DSE9130 12V 5A ....................................................................................................... 15
3.5.2
DSE9140 12V 10A ..................................................................................................... 16
3.5.3
DSE9150 12V 2A ....................................................................................................... 17
3.5.4
DSE9150 12V 3A ....................................................................................................... 18
3.5.5
DSE9155 30V 2A ....................................................................................................... 19
3.5.6
DSE9250 24V 3.7A .................................................................................................... 20
3.5.7
DSE9255 24V 5A ....................................................................................................... 21
3.5.8
DSE9260 24V 10A ..................................................................................................... 22
3.5.9
DSE9470 (MKII) 24V/12V 10A .................................................................................... 23
3.5.10
DSE9472 (MKII) 24V/12V 5A ...................................................................................... 25
3.5.11
DSE9480 (MKII) 12V 10A ........................................................................................... 26
3.5.12
DSE9481 (MKII) 12V 5A ............................................................................................. 28
3.6
DIMENSIONS AND MOUNTING ....................................................................................... 29
3.6.1
DSE907 12V 10A INDUSTRIAL BATTERY CHARGER .............................................. 29
3.6.2
DSE908 12V & 24V 10A CABINET MOUNTED BATTERY CHARGER ....................... 30
3.6.3
DSE9130 12V 5A ....................................................................................................... 31
3.6.4
DSE9150 12V 2A ....................................................................................................... 32
3.6.5
DSE9150 12V 3A ....................................................................................................... 33
3.6.6
DSE9140 12V 10A ..................................................................................................... 34
3.6.7
DSE9155 30V 2A ....................................................................................................... 35
3.6.8
DSE9250 24V 3.7A .................................................................................................... 36
3.6.9
DSE9255 24V 5A ....................................................................................................... 37
3.6.10
DSE9260 24V 10A ..................................................................................................... 38
3.6.11
DSE9470 (MKII) 24V/12V 10A .................................................................................... 39
3.6.12
DSE9472 (MKII) 24V/12V 5A ...................................................................................... 40
3.6.13
DSE9480 (MKII) 12V/24V 10A .................................................................................... 41
3.6.14
DSE9481 (MKII) 12V/24V 5A ...................................................................................... 42
3.7
APPLICABLE STANDARDS............................................................................................. 43
4
INSTALLATION ................................................................................................. 44
4.1
BATTERY SUITABILITY ................................................................................................... 44
4.2
USER CONNECTIONS ..................................................................................................... 44
4.2.1
DSE9130, DSE9140, DSE9250, DSE9255 & DSE9260 .............................................. 45
4.2.2
DSE9150 .................................................................................................................... 45
4.2.3
DSE9155 .................................................................................................................... 46
4.2.4
DSE9470 MKII, DSE9472 MKII, DSE9480 MKII, DSE9481 MKII .............................. 47
4.3
TYPICAL WIRING DIAGRAM ........................................................................................... 49
4.3.1
DSE9150 .................................................................................................................... 49
4.3.2
DSE9155 & DSE9200 SERIES ................................................................................... 50
4.3.3
DSE9470 MKII, DSE9472 MKII, DSE9480 MKII, DSE9481 MKII ............................... 51
5
INDICATIONS .................................................................................................... 52
5.1
DSE907............................................................................................................................. 52
5.2
DSE908............................................................................................................................. 52
5.3
DSE9130, DSE9150, DSE9155, DSE9250 & DSE9255 ..................................................... 53
5.4
DSE9140 & DSE9260 ....................................................................................................... 54
DSE9000 Series Battery Charger Operator Manual
4
5.5
DSE9470 MKII, DSE9472 MKII, DSE9480 MKII, DSE9481 MKII ....................................... 55
5.5.1
STATUS ..................................................................................................................... 55
5.5.2
CHARGE MODE ........................................................................................................ 55
5.5.3
FAULT CONDITIONS ................................................................................................. 55
6
OPERATION ...................................................................................................... 56
6.1
OPERATION OF DSE9100 SERIES / DSE9200 SERIES .................................................. 56
6.1.1
PROTECTION ............................................................................................................ 56
6.1.2
PSU MODE ................................................................................................................ 56
6.1.3
CHARGE MODE ........................................................................................................ 56
6.1.4
BOOST MODE ........................................................................................................... 57
6.2
OPERATION OF DSE9400 MKII SERIES ......................................................................... 58
6.2.1
PROTECTION ............................................................................................................ 58
6.2.2
DIGITAL INPUT .......................................................................................................... 59
6.2.3
VOLTAGE ADJUSTMENT POTENTIOMETER ........................................................... 59
6.2.4
PSU MODE ................................................................................................................ 59
6.2.5
CHARGE MODE ........................................................................................................ 60
6.2.6
TEMPERATURE COMPENSATION ........................................................................... 61
7
FAULT DIAGNOSIS ........................................................................................... 62
8
MAINTENANCE, SPARES, REPAIR AND SERVICING ................................... 63
9
WARRANTY ...................................................................................................... 63
10
DISPOSAL ...................................................................................................... 63
10.1
WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) ............................... 63
10.2
ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES) ........................................... 63
Bibliography
5
1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained
from the DSE website www.deepseaplc.com
1.1 INSTALLATION INSTRUCTIONS
Installation instructions are supplied with the product in the box and are intended as a ‘quick start
guide only.
DSE PART
DESCRIPTION
053-049 DSE9200 / DSE9400 Series Battery Charger Installation Instructions
053-123 DSE9150 Battery Charger Installation Instructions
1.2 MANUALS
DSE PART
DESCRIPTION
057-159 DSE9400 Series Battery Charger Configuration Suite Manual
Introduction
6
2 INTRODUCTION
NOTE: This document DOES NOT contain details of theobsolete DSE9210 and DSE9240
battery chargers. For further details of these units, please contact Deep Sea Electronics.
This document details the installation requirements of the DSE9000 series range of battery chargers.
The manual forms part of the product and should be kept for the entire life of the product. If the
product is passed or supplied to another party, ensure that this document is passed to them for
reference purposes.
This is not a controlled document. You will not be automatically informed of updates. Any future
updates of this document will be added to the DSE website at www.deepseaplc.com.
The DSE9000 series modules are intended for mounting within a customer enclosure or panel (DIN
rail mounting or fastened by screws/bolts).
DSE also supply some of the battery chargers as completed units, factory mounted into enclosures for
wall or floor mounting.
The DSE9000 series chargers fulfill the most common functions required of a charger in the
generating set industry. Combining protected outputs, intelligent charging and power supply operation
with a robust enclosure.
Specifications
7
3 SPECIFICATIONS
3.1 PART NUMBERING
3.1.1 DSE9100 CHASSIS MOUNT BATTERY CHARGERS
9130 - 001 - 00
NOTE: For descriptions of other Hardware Revisions, please contact
support@deepseaplc.com
NOTE: The DSE9150 12V 2A is now obsolete, replaced with DSE9150 12V 3A.
NOTE: The DSE9150 12V 3A only available in Variant -00 (13.7V for lead acid batteries)
NOTE: For variant 03 (For other battery types), the float voltage can be adjusted between
12.5V and 15V for DSE9130 12V 5A chargers (25V - 30V for DSE9250 24V 3.7A chargers). This
change must be made at the DSE factory. Ensure the correct variant (and float voltage if
applicable) is specified on ordering. Consult your battery manufacturer for further details of
required float voltage.
Product type
Variant
Hardware revisions
First version hardware
001
00
For 9 or 18 cell NICAD batteries*
12V charger set to 13.0V
24V charger set to 26.0V
01
For 10 or 20 cell NICAD batteries*
12V charger set to 14.5V
24V charger set to 29.0V
02
For other battery types*
Specify required float voltage on ordering**
03
DSE9130 12V 5A
9130
DSE9140 12V 10A
9140
DSE9155 30V 2A
9155
For lead acid batteries
12V charger set to 13.7V
24V charger set to 27.4V
DSE9150 12V 2A
9150
DSE9150 12V 3A
9150
Specifications
8
3.1.2 DSE9200 CHASSIS MOUNT BATTERY CHARGERS
9130 - 001 - 00
NOTE: For descriptions of other Hardware Revisions, please contact
support@deepseaplc.com
NOTE: - The DSE9250 battery charger is now obsolete, details provided for information
only.
NOTE: For variant 03 (For other battery types), the float voltage can be adjusted between
12.5V and 15V for DSE9130 12V 5A chargers (25V - 30V for DSE9250 24V 3.7A chargers). This
change must be made at the DSE factory. Ensure the correct variant (and float voltage if
applicable) is specified on ordering. Consult your battery manufacturer for further details of
required float voltage.
Product type
Variant
Hardware revisions
First version hardware
001
00
For 9 or 18 cell NICAD batteries*
12V charger set to 13.0V
24V charger set to 26.0V
01
For 10 or 20 cell NICAD batteries*
12V charger set to 14.5V
24V charger set to 29.0V
02
For other battery types*
Specify required float voltage on ordering**
03
DSE9250 24V 3.7A
9250
DSE9255 24V 5A
9255
DSE9260 24V 10A
9260
For lead acid batteries
12V charger set to 13.7V
24V charger set to 27.4V
Specifications
9
3.1.3 DSE9400 MKII SERIES CHASSIS MOUNT BATTERY CHARGERS
9470 - 001 - 00
NOTE: For descriptions of other Hardware Revisions, please contact
support@deepseaplc.com
NOTE: For hardware versions 003 and above, voltage and current levels can be user
configured via DSE Configuration Suite PC Software.
Part number 9470-001-00 is fixed at 24V 10A.
Part number 9480-001-00 is fixed at 12V 10A.
NOTE: DSE9400 series battery chargers are customer configurable via the DSE
Configuration Suite PC Software.
For further details, you are referred to DSE Publication: 057-159 DSE9400 Series Battery
Charger Configuration Suite Manual.
Product type
Variant
Hardware revisions
First version hardware 001
00
DSE9470 12/24V 10A
9470
Standard
DSE9472 24V/12V 5A
9472
DSE9480 24V/12V 10A 9480
DSE9481 24V/12V 5A 9481
Specifications
10
3.1.4 DSE907 INDUSTRIAL / DSE908 CABINET MOUNTED BATTERY CHARGERS
NOTE: The DSE907 / DSE908 Industrial / Cabinet Mounted Battery Chargers are now
obsolete, replaced by DSE9460 / DSE9461 Enclosed Battery Chargers.
See the preceeding page for details of part numbering of chassis mounted battery chargers.
Industrial / Cabinet mounted battery chargers are 9000 series battery chargers factory fitted into wall
mounted enclosures. For details see the section entitled Dimensions and Mounting elsewhere in
this document.
0907-002-
INDUSTRIAL BATTERY CHARGER 12V 5A 220-250V
0908-001-
CABINET MOUNTED BATTERY CHARGER 12V 10A
0908-001-21 CABINET MOUNTED BATTERY CHARGER 24V 10A
0907 - 001 - 00
When ordering Industrial / Cabinet mounted battery chargers, ensure you specify the type of batteries
that are to be charged. If you do not specify this, the chargers will be preset to charge Lead Acid type
batteries.
Product type
Variant
Hardware revisions
Specifications
11
3.2 COMMON ELECTRICAL SPECIFICATIONS
Parameter
Min
Nominal
Max
AC
Input Voltage (V)
DSE9130 12V 5A
DSE9150 12V 2A
DSE9150 12V 3A
DSE9140 12V 10A
DSE9155 30V 2A
DSE9250 24V 3.7A (9250-001-xx)
DSE9250 24V 3.7A (9250-002-xx)
DSE9255 24V 5A
DSE9260 24V 10A
DSE9470 24V/12V 10A
DSE9472 24V 5A
DSE9480 12V/24V 10A
DSE9481 12V 5A
90V
90V
90V
90V
85V
90V
90V
90V
90V
95V
95V
95V
95V
110V-277V
110V-240V
110V-240V
110V-240V
110V-240V
110V-240V
110V-277V
110V-277V
110V-277V
110V-277V
110V-277V
110V-277V
110V-277V
304V
250V
265V
277V
265V
265V
305V
305V
305V
305V
305V
305V
305V
Operating
Temperature
DSE9100 Series
DSE9200 Series
DSE9400 Series
-30°C
-30°C
-30°C
55°C
55°C
85°C with de-ratings
Input F
requency (Hz)
48Hz 64Hz
Output Ripple and
Noise
DSE9100 Series
DSE9200 Series
DSE9400 Series
1% Vo
2% Vo
1% Vo
Load Regulation
DSE9100 Series
DSE9200 Series
DSE9400 Series
1% Vo
2% Vo
1% Vo
Line
R
egulation
<0.01% Vo
Output
V
oltage
O
vershoot %
<5%Vo
Transient Response Peak D
eviation (mV)
(at 50% to 100% load step)
<4% Vo
Warm Up V
oltage (V)
<1% Vo
Output Voltage
Rise Time (ms)
DSE9100 Series
DSE9200 Series
DSE9400 Series
<100ms
<100ms
<200ms
Short Circuit P
rotection
Hiccup
Switching
F
requency (k
H
z)
9130-001-xx (replaced with 9130-002-xx)
9250-001-xx (replaced with 9250-002-xx)
9130-002-xx
9250-002-xx
94xx-xxx-xx
All other chargers
100kHz
100kHz
67kHz
67kHz
67kHz
100kHz
Efficiency %
(See section entitled
output specifications
elsewhere in this
manual)
DSE9100 Series
DSE9200 Series
>80%
DSE9400 Series
>85%
Temperature Sensor
Input
DSE9400 Series
PT1000
NOTE: Check the DSE9400 Series de-rating curves which can be found else where in this
manual for more information.
Specifications
12
3.3 COMMUNICATION PORT USAGE
Communication
Specification
USB Port
(DSE9400 series
only)
USB2.0 Device for connection to PC running DSE Configuration Suite
Max distance 6m (20 feet)
RS485 Serial
Port
(DSE9400 series
only)
Isolated
Data connection 2 wire + common
Half Duplex
Data direction control for Transmit (by s/w protocol)
Max Baud Rate 19200
External termination required (120)
Max common mode offset 70V (on board protection transorb)
Max distance 1.2km (¾ mile)
3.3.1 USB CONNECTION
The USB port is provided to give a simple means of connection between a PC and the DSE9400
series battery charger. Using the DSE Configuration Suite Software, the operator is then configure
and monitor the state of the battery charger.
To connect a DSE9400 series battery charger to a PC by USB, the following items are required:
DSE9400 series battery charger
DSE Configuration Suite Software
(Supplied on configuration suite software CD or available from
www.deepseaplc.com).
USB cable Type A to Type B.
(This is the same cable as often used between a PC and a USB
printer)
DSE can supply this cable if required :
PC Configuration interface lead (USB type A – type B) DSE Part
No 016-125
NOTE: - Refer to DSE9400 Series Battery Charger PC Software Configuration Manual for
further details on configuring and monitoring.
Specifications
13
3.3.2 RS485
The RS485 port on the DSE9400 series battery chargers has two uses.
1) Supporting the DSE2541 remote battery charger display module (MKII only)
2) Support the Modbus RTU protocol for connection to a Modbus RTU Master device.
3.3.2.1 DSE2541 REMOTE BATTERY CHARGER DISPLAY MODULE
DSE2541 remote battery charger display modules
connects to the DSE9400 MKII Series battery
charger RS485 terminals.
This provides battery charger operating status, alarm
indication, instrumentation and control over the
DSE9400 MKII Series battery charger.
For further information please contact
sales@deepseaplc.com.
3.3.2.2 MODBUS RTU
RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices)
and allows for connection to PCs, PLCs and Building Management Systems (to name just a few
devices).
Using the DSE Configuration Suite PC Software, Configurable Gencomm is used to map
instrumentation to modbus registers.
One advantage of the RS485 interface is the large distance specification (1.2km) when using Belden
9841 (or equivalent) cable. This allows for a large distance between the DSE9400 series battery
charger and a PC running the DSE Configuration Suite software. The operator is then able to view the
various operating parameters.
NOTE: - For distances up to 6m (8yds) the USB connection method is more suitable and
provides for a lower cost alternative to RS485 (which is more suited to longer distance
connections).
Specifications
14
3.3.2.3 OPTIONS FOR CONNECTION TO PCS
Brainboxes PM154 PCMCIA RS485 card (for laptops PCs)
Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled
Brainboxes VX-023 ExpressCard 1 Port RS422/485 (for laptops and
nettop PCs)
Brainboxes UC320 PCI Velocity RS485 card (for desktop PCs)
Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled
Brainboxes PX-324 PCI Express 1 Port RS422/485 (for desktop PCs)
Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales: sales@brainboxes.com
Specifications
15
3.5 OUTPUT SPECIFICATIONS
3.5.1 DSE9130 12V 5A
Parameter
Min
Nominal
Max
Comments
Output Voltage (12 V DC battery) 12.5V 13.7V 15.0V Specify float voltage on ordering.
Output Charging Current (A) 0A 5A 5.5A
Current limit threshold (A) 5A 5.3A 5.5A
Recovery from current limit (A) 5A
Full load AC input current (A) 1.5A With output at 13.7V DC
AC Input Inrush (10ms) current (A) 20A
0.8
0.82
0.84
0.86
0.88
0.9
0.92
85 110 230 260
Efficiency (%)
Input Voltage (V)
DSE9130 Efficiency Curve at 5A
Specifications
16
3.5.2 DSE9140 12V 10A
Parameter
Min
Nominal
Max
Comments
Output Voltage (12 V DC Battery) 12V 13.7V 15V
Output Charging Current (A) 10A 10A 11A
Current limit threshold (A) 10A 11A
Recovery from current limit (A) 10A 11A
Full load AC input current (A) 3.1A At Vin=85V, Vo=13.7V, Io=10Amp
Full load AC input current (A) 1.3A At Vin=230V, Vo=13.7V Io=10Amp
AC Input Inrush (10ms) current (A) 60A
0.78
0.79
0.8
0.81
0.82
0.83
0.84
0.85
0.86
0.87
85
110
230
260
Efficiency (%)
Input Voltage (V)
DSE9140 Efficiency Curve at 10A
Specifications
17
3.5.3 DSE9150 12V 2A
NOTE: This device is no longer available, replaced by DSE9150 12V 3A. See overleaf for
updated specifications.
Parameter
Min
Nominal
Max
Comments
Output Voltage (12 V DC Battery) 12.5V 13.7V 13.7V Float voltage not adjustable
Output Charging Current (A) 0A 2A 2.5A
Current limit threshold (A) 2A 2.3A 2.5A
Recovery from current limit (A) 2A
Full load AC input current (A) 0.7A With output at 13.7V DC
AC Input Inrush (10ms) current (A) 10A
74
76
78
80
82
84
86
88
90
85 110 230 250
Efficiency (%)
Input Voltage (V)
DSE9150 Efficiency Curve at 2A
Specifications
18
3.5.4 DSE9150 12V 3A
NOTE: This device has replaced DSE9150 12V 2A. See previous page for specifications of
the earlier model.
Parameter
Min
Nominal
Max
Comments
Output Voltage (12 V DC Battery) 12.5V 13.7V 13.7V Float voltage not adjustable
Output Charging Current (A) 0A 3A 3.5A
Current limit threshold (A) 3A 3.2A 3.5A
Recovery from current limit (A) 3A
Full load AC input current (A) 0.7A With output at 13.7V DC
AC Input Inrush (10ms) current (A) 10A
0.79
0.80
0.81
0.82
0.83
0.84
0.85
0.86
0.87
110 230 265
Efficiency (%)
Input Voltage (V)
DSE9153 Efficiency Curve at 3A
/