Chromalox CMX Installation guide

Type
Installation guide
i
Installation & Operation Manual
Circulating Water
Temperature Control System
PQ450-1
161-123417-036
January 2020
ii
Table of Contents
Contents Page Number
Section 1 Getting Started ...................................................................................................................................... 1
Section 2 Installation .............................................................................................................................................. 4
Section 3 Temperature Control Operation ........................................................................................................... 9
Section 4 System Operation ................................................................................................................................ 10
Section 5 Diagnostics .......................................................................................................................................... 11
Section 6 Maintenance ........................................................................................................................................ 12
Section 7 Troubleshooting ................................................................................................................................... 17
Section 8 Specifications ...................................................................................................................................... 18
Appendix A CMX Closed Loop to Open Loop Cooling Conversion ................................................................. 19
Appendix B CMX Open Loop to Closed Loop Cooling Conversion ................................................................. 20
Appendix C CMX 2104 Controller Information .................................................................................................. 23
1
Section 1 – Getting Started
Installation Instructions
Read and understand all instructions in this
user’s manual and the associated temperature
control instruction manual before attempting
to install or operate system.
Introduction
Congratulations on purchasing the Chromalox CMX
Series microTHERM™ Temperature Control System.
This system has been thoroughly engineered, carefully
built, and fully tested to assure years of service.
The CMX can be operated at a maximum tempera-
ture of 250°F at a minimum pressure of 30psi. CMX-
180 models do not require minimum pressure. Water
temperature is maintained by a microprocessor-based
temperature controller which applies heating and cool-
ing as needed. Heat is applied by a long-life, INCOLY
®
sheathed heater. Cooling is either via direct injection, in
an open loop, or through a closed loop heat exchanger.
Every system is equipped with an automatic vent that
removes unwanted air from the system during opera-
tion, and an ASME pressure relief valve that is factory-
set to 125 psi (150 psi with 7.5 hp motor.) A pressure
switch ensures adequate water pressure in the system
to help prevent pump cavitation and steam buildup on
the heater elements, which can shorten the lives of the
heater and pump. The switch is factory-set to 20 psi.
This switch is not included on CMX-180 models.
Electrical and hydraulic components are located in
distinctly separate areas in the system to better man-
age heat buildup and prevent component damage.
The pump housing, heater, and cooling chambers are
single cast pieces, designed to drastically reduce the
chance of leaks and provide ease of service and main-
tenance. Standard casters make it easy to move the
system from machine to machine.
Power requirements for the system are 240 or 480
volts, 3 phase, 60 cycle, and 4.5 to 24 kW. See the sys-
tem nameplate for the appropriate voltage and wattage
ratings.
The System Photo and Control Panel Illustrations, on
the following pages, show the CMX and identifies all
key components.
2
Figure 1.1 System Photo (Side View)
Operating temperatures of 50° to 250°F
for a wide variety of applications.
ASME pressure relief valve opens if sys-
tem pressure exceeds 125 psi, ensuring
safe operation.
High watt density, INCOLOY
®
sheath
Chromalox
®
heating elements.
Integral solenoid valve for pre-
cise temperature control and
optimum flow.
Internal system configuration separates
electronics from mechanical systems,
reducing heat buildup and providing
a safer operating system.
Pump overload circuit protects
systems from damage in event
of excessive current draw in
the motor.
Long-life mercury contactor switches
heater power for millions of cycles and
quiet, trouble-free operation.
Compact, rugged cabinet fits into tight
spaces. Rolling casters allow easy
transfer between locations.
Low pressure switch disables system when
supply pressure is low, preventing cavitation in
pump and protecting the system.
Custom cast pump for optimum flow,
minimum leakage and long life.
Cabinet design allows
access to all compo-
nents without removing
a single fastener.
Standard 3.8 sq. ft. heat ex-
changer (closed loop cool-
ing)
Automatic air purge cycle
removes accumulated air
from water lines.
3
Dual pressure gauges simplify monitoring of both
to process and from process pressures.
Chromalox’s Temperature and Process Controller
features separate PID algorithms for heat and
cool control modes, dual display of setpoint and
process temperatures, and simple configuration
parameters with alphanumeric cues. Optional
digital communications expand microTHERM’s
application flexibility. (Controller model supplied
may vary from picture)
Diagnostic Indicators allow you to constantly
monitor microTHERM’s performance, giving you
early detection of potential problems before they
occur and simplifying maintenance.
Figure 1.2 Control Panel
Ordering Information
Pump START/STOP Pushbuttons
kW Volts Ph.
Pump
Motor
HP
Dimensions
(In.)
Cooling Type Model Stock Part Number
Wt.
(Lbs)H W D
4.5 240 3 3/4 29 15 25 Open Loop CMX-250-4 NS 307418-032 200
4.5 480 3 3/4 29 15 25 Open Loop CMX-250-4 NS 307418-033 200
4.5 240 3 3/4 29 15 25 Closed Loop CMX-250-4C NS 307418-042 215
4.5 480 3 3/4 29 15 25 Closed Loop CMX-250-4C NS 307418-043 215
9 240 3 3/4 29 15 25 Open Loop CMX-250-9 NS 307418-034 200
9 480 3 3/4 29 15 25 Open Loop CMX-250-9 S 307418-035 200
9 240 3 3/4 29 15 25 Closed Loop CMX-250-9C NS 307418-044 215
9 480 3 3/4 29 15 25 Closed Loop CMX-250-9C S 307418-045 215
12 240 3 3/4 29 15 25 Open Loop CMX-250-12 NS 307418-036 200
12 480 3 3/4 29 15 25 Open Loop CMX-250-12 S 307418-037 200
12 240 3 3/4 29 15 25 Closed Loop CMX-250-12C NS 307418-046 215
12 480 3 3/4 29 15 25 Closed Loop CMX-250-12C S 307418-047 215
18 240 3 3/4 29 15 25 Open Loop CMX-250-18 NS 307418-038 200
18 480 3 3/4 29 15 25 Open Loop CMX-250-18 S 307418-039 200
18 240 3 3/4 29 15 25 Closed Loop CMX-250-18C NS 307418-048 215
18 480 3 3/4 29 15 25 Closed Loop CMX-250-18C S 307418-049 215
24 240 3 3/4 29 15 25 Open Loop CMX-250-24 NS 307418-040 200
24 480 3 3/4 29 15 25 Open Loop CMX-250-24 S 307418-041 200
24 240 3 3/4 29 15 25 Closed Loop CMX-250-24C NS 307418-050 215
24 480 3 3/4 29 15 25 Closed Loop CMX-250-24C S 307418-051 215
36 480 3 3/4 29 15 25 N/A CMX-250-36H NS 307418-052 215
48 480 3 3/4 29 15 25 N/A CMX-250-48H S 307418-053 215
4
Section 2 – Installation
Before Open-Loop Hydraulic Installation:
Before proceeding with the installation of the open-
loop system, please take note of the following impor-
tant information:
1. Reduced diameter fittings may be used if they do
not reduce flow rate and increase pressure drop
significantly. Galvanized steel unions are recom-
mended at all connections.
2. If water pressure falls below 20 psi, a pressure
switch will interrupt pump motor and heater op-
eration. Use an external water pressure regulator
and back pressure relief valve or regulator, set at
maximum 125 psi (150 psi with 7.5 hp motor) con-
nected in the external fill line, to reduce excessive
water pressure. Not provided on CMX-180 models.
HAZARD OF EXPLOSION, FIRE AND SCALDING
BURNS.
The water feed line on both open and closed
loop systems must not have any obstructions
which could prevent expanding water from
backing up into the feed line.
Do not use oils or other synthetic heat trans-
fer fluids. This system is for use with water or
ethylene glycol and water mixture for freeze
protection only as the heat transfer fluid.
When installing system, allow sufficient room
to remove the heater element and other ser-
viceable items when necessary. 18 inches
clearance on sides of unit recommended.
If the water source is a potable water source,
a back flow preventer and back pressure relief
valve/regulator should be installed and may be
required by local code. Do not install a check
valve only on the fill line. The inability of the
system to flow back into the fill line can lead
to excessive pressure. Back pressure relief is
required.
To avoid excessive pressures, do not connect
any valves or obstructions which could prevent
free discharge from relief valve in a safe man-
ner. Route line so water drains completely. Do
not allow drain to freeze or corrode shut.
Hydraulic Installation, Open Loop:
1. Locate the unit as close as possible to the con-
trolled process in order to minimize pressure
drops. Make sure the unit is sitting on a solid, level
foundation.
2. Using 1-1/2” NPT or larger schedule 40 pipe (flex-
ible hose suitable for 150 psi and 250°F minimum
service conditions can be used), connect the
1-1/2” NPT “FROM PROCESS” and “TO PRO-
CESS” ports to the mold, mold manifold, or other
process.
3. Pipe the entire system to minimize air pockets.
Provide air bleed valves at high points and drains
at low points.
4. Connect the plant water supply (30 psi to 80 psi)
to the unit’s 1” NPT “WATER SUPPLY/COOLING
INLET” port with suitable pipe or hose.
HAZARD OF EXPLOSION, FIRE AND SCALDING
BURNS.
Connect the 1/4” NPT port identified as “DRAIN
COOLING OUTLET” to an open or plant drain
that contains no valves or obstructions that
could impede discharge. Review the condition
of potential hot water or steam going down a
plant drain. Verify that local codes and materi-
als are acceptable for this service.
Locate floor drain under unit. The air bleed and
relief valve may discharge hot water or steam
from the bottom of the unit. Do not locate ma-
terials that could be damaged by hot water or
steam adjacent to the unit.
Temperature Controller
Drain/Cooling
Outlet
(1/4 NPT)
From Process
(1-1/2 NPT)
Water Supply/
Cooling Inlet
(1 NPT)
Pump and
Motor
Pressure
Relief
Valve
Auto
Air Bleed
Heater
Therocouple
Probe
To Process
(1-1/2 NPT)
Heater
Cooling
Valve
Temperature Controller
Cooling Outlet
(1/2 NPT)
From Process
(1-1/2 NPT)
Water Supply/
Cooling Inlet
(1/2 NPT)
Auto
Air Bleed
Pressure
Relief
Valve
Therocouple
Probe
To Process
(1-1/2 NPT)
Solenoid
Valve
Pump and
Motor
Figure 2.1 Open-Loop System Piping
5
Figure 2.2 Open-Loop Cooling Piping Connections
Note: Dimensions are nominal ± 3/8”
Rear View
Chromalox
®
DRAIN/
COOLING OUTLET
FROM PROCESS
TO
PROCESS
1-7/8”
6"
6"
4"
7"
15"
WATER SUPPLY/
COOLING INLET
12-5/16”
28-1/2”
6
Before proceeding with the installation of the Closed-
loop system, please take note of the following informa-
tion:
1. Reduced diameter fittings may be used if they do
not reduce flow rate and increase pressure drop
significantly. Galvanized steel unions are recom-
mended at all connections.
2. If water pressure falls below 20 psi, a pressure
switch will interrupt pump motor and heater op-
eration. Use an external water pressure regulator
and back pressure relief valve or regulator set at
maximum 125 psi (150 psi with 7.5 hp motor) con-
nected in the external fill line, to reduce excessive
water pressure. Not provided with CMX-180 mod-
els.
HAZARD OF EXPLOSION, FIRE AND SCALDING
BURNS. To avoid excessive pressures, do not
connect any valves or obstructions which could
prevent free discharge from relief valve in a
safe manner. Route line so water drains com-
pletely. Do not allow drain to freeze or corrode
shut.
Do not install a check valve on the fill line. The
inability of the system to flow back into the
fill line can lead to excessive pressure. If back
flow preventer or check valve is required, in-
stall back pressure regulator rated for 250°F
water with a pressure setting of 30 to 80 psi.
Back pressure regulator setting must be ap-
proximately 10 psi above water supply pres-
sure to minimize water flow directly from sup-
ply to drain.
Hydraulic Installation Closed-Loop
1. Locate the unit as close as possible to the con-
trolled process in order to minimize pressure
drops. Make sure the unit is sitting on a solid, level
foundation.
2. Using 1-1/2” NPT or larger schedule 40 pipe (flex-
ible hose suitable for 150 psi and 250°F minimum
service conditions can be used), connect the
1-1/2” NPT “FROM PROCESS” and “TO PRO-
CESS” ports to the mold, mold manifold, or other
process.
3. Pipe the entire system to minimize air pockets.
Provide air bleed valves at high points and drains
at low points.
4. Connect the cooling water supply (30 psi to 80 psi)
to the unit’s 1/2” NPT “WATER SUPPLY/COOLING
INLET” port with suitable pipe or hose.
5. Connect the 1/4” NPT port identified as “COOL-
ING OUTLET” to a cooling water return line or plant
drain that contains no valves or obstructions that
could impede discharge. Review the condition of
potential hot water going down a plant drain. Verify
that local codes and materials are acceptable for
this service. Temperature of discharge water could
reach 250°F and create steam at atmospheric
pressure.
Temperature Controller
Drain/Cooling
Outlet
(1/4 NPT)
From Process
(1-1/2 NPT)
Water Supply/
Cooling Inlet
(1 NPT)
Pump and
Motor
Pressure
Relief
Valve
Auto
Air Bleed
Heater
Therocouple
Probe
To Process
(1-1/2 NPT)
Heater
Cooling
Valve
Temperature Controller
Cooling Outlet
(1/2 NPT)
From Process
(1-1/2 NPT)
Water Supply/
Cooling Inlet
(1/2 NPT)
Auto
Air Bleed
Pressure
Relief
Valve
Therocouple
Probe
To Process
(1-1/2 NPT)
Solenoid
Valve
Pump and
Motor
Figure 2.3 Closed-Loop System Piping
Before Closed-Loop Hydraulic Installation
7
Figure 2.4 Closed-Loop Cooling Piping Connections
Chromalox
®
COOLING OUTLET
WATER SUPPLY/
COOLING INLET
FROM PROCESS
TO
PROCESS
1-7/8”
6"
6"
4"
7"
15"
12-5/16”
28-1/2”
Rear View
Note: Dimensions are nominal ± 3/8”
8
HAZARD OF ELECTRIC SHOCK. The heat trans-
fer system must be grounded using grounding
means provided in control box and employing
wiring by a qualified electrician in accordance
with National Electric Code. Failure to comply
can result in electrical shock or electrocution.
HAZARD OF ELECTRIC SHOCK. Disconnect all
power before servicing the heat transfer sys-
tem. Failure to comply can result in electrical
shock or electrocution.
Fusing or other over-current protection must be sup-
plied to the system by the user.
The unit is completely wired when shipped. The only
wiring necessary is to the blue colored terminals L1,
L2, L3, and the green and yellow colored ground. To
make these connections:
Figure 2.5 Power Connection Terminals
1. Loosen the screw on the front electrical enclosure
door to unlock the latch.
2. Open the front electrical enclosure door. Using
90°C wire sized per National and local codes, run
each leg of the three phase supply power and
ground to the appropriate terminals as shown in
Figure 2.5.
3. A separate fused disconnect is required. Locate
this fused disconnect near the equipment. Codes
may require the location of disconnect in sight of
operation standing next to the equipment. Consult
applicable codes for details.
4. Pump Rotation Check: With power off, check the
wiring connections by tugging on the lines. Tighten
all terminals in the control area. These can loosen
due to vibration in shipping.
5. Close the front electrical enclosure door. Pull the
top cover off of the heat transfer system and locate
the top of the pump motor.
6. With the supply water connected, and adequate
pressure present, Press the
ST
ART STOP
and
START
STOP
but-
tons in quick succession. Watch the rotation on the
pump motor to insure it matches the label on its
top.
7. If rotation is incorrect, disconnect power to the
system and swap any two of the supply lines. Re-
peat rotation check.
Close the front electrical enclosure door and
retighten the locking screw. This must be done
to limit access to high voltage components.
Failure to comply could lead to electric shock
or electrocution.
Control Voltage Fusing
Terminal block #1 (see Figure 2.5) contains a 120V fuse
for the control circuitry. This fuse protects the control
transformer and circuitry.
1. Should the fuse blow, an indicator will light on the
terminal block.
2. Disconnect power from the system.
3. Determine the cause of the blown fuse.
4. Replace with an equivalent fuse.
5. Reconnect power.
Electrical Installation
9
Section 3 – Temperature Control Operations
Figure 3.1 Control Panel Layout
Status and Diagnostic Indicators
System shuts down if any red diagnostic indicator is
illuminated.
Low Water Pressure:
System water pressure is below 20 psi.
(Disabled on CMX-180 models)
Pump Overload:
Pump has drawn too much current.
Over Temperature:
System temperature has exceeded 260°F.
Most CMX units shipped from 1995 through 2018 will
have been equipped with a Chromalox model 2104
temperature controller. For these units, please refer-
ence the 2104 Quick Info Manual or Instruction Manual
0037-75276 for complete technical details.
For specific controller Set-up Parameters, please refer
Chromalox Manual PQ445-5
Most CMX units shipped from 2019 and onward will
have been equipped with a Chromalox model 4081
(standard controller) or 4082 (advanced controller). For
these units, please reference the 4081 & 4082 Quick
Start Manual, Document PK531 (0037-75563) or In-
struction manual PK532-1 (0037-75562) for complete
technical details.
Below is a list of the most common controller setups,
with additional details available in Appendix C
CMX-250, Contactor – Dwg. 223-123625-053
CMX-275, Contactor – Dwg. 223-123625-052
CMX-250, SCR – Dwg. 223-123625-055
CMX-275, SCR – Dwg. 223-123625-058
CMX-250, Heat-Only – Dwg. 223-123625-057
CMX-275, Heat-Only – Dwg. 223-123625-059
START/STOP Pushbuttons
Press
ST
ART
STOP
to start the
pump.
Indicator will illuminate while
pump is running. Press
START
STOP
to stop the pump.
Temperature Control
Actual controller supplied may vary from picture.
10
On both open Closed-loop systems, turn on wa-
ter and insure the water supply lines are free
of obstructions BEFORE energizing the heater.
Such obstructions could prevent the thermal
expansion of water from backing up into this
line, thereby increasing system pressure until
the relief valve opens.
Note: This system is equipped with an ASME
safety pressure relief valve (factory preset at
125 psi or 150 psi with 7.5 hp motor).
1. Apply power to the system via the remote discon-
nect. The temperature controller and “LOW WATER
PRESSURE” diagnostics light should illuminate.
2. Open supply-water line and process valving to al-
low system to fill. Auto air bleed will remove air from
the system. Any remote air bleed valves should be
opened to remove air from process and associated
piping.
3. “LOW WATER PRESSURE” diagnostic light should
go out when the system is filled and has reached
20 psi. The system will not start when light is illumi-
nated.
4. Adjust the temperature setpoint to the desired lev-
el.
5. Assure that Pump Rotation Check was performed
per instructions on page 12.
6. Start the pump by pressing on the front panel. The
pump indicator light will illuminate.
7. Once temperature has stabilized at the setpoint
level, review controllability of the system. If the
temperature is fluctuating at an unacceptable level,
consult the temperature control instruction manual
for details on tuning the controller.
8. If the system temperature is below the current set-
point, heat will be applied by the controller to the
heater elements. If the temperature is above the
setpoint, the cooling solenoid will open (open and
closed loop) to reduce the system temperature.
Operating systems at temperatures above
140°F will create surface temperatures on
pipes that can cause burns. Precautions should
be taken to prevent operator contact with hot
pipes. Also, bleed valves should be locked
down to prevent release of hot fluid.
Note: This is a PID type controller and cycling of the
heat and cool can be expected below and above set-
point.
9. For system shutdown, lower the setpoint to 90°F or
lower, Allow the system to cool to this temperature
level.
10. Press to de-energize the pump and disable the
system.
11. Disconnect power to the unit.
Do not leave system unattended in a HOT elec-
trical condition; and do not leave system unat-
tended in HOT environmental conditions.
Section 4 – Operation
11
Section 5 – Diagnostics
Figure 5.1 Diagnostic Indicators
Diagnostic Functions
All diagnostic functions will shut down the system and
require the operator to remedy the problem before it
can be restarted.
Low Water Pressure Indicators
The pump, heater, and cooling will not operate while
the pressure is low. The Low Water Pressure Indica-
tor will illuminate when the system pressure is below
20 psi. This warning system is designed to reduce the
possibility of pump cavitation and boiling on the heater
element at higher operating temperatures. Disabled on
CMX-180 models.
Pump Overload Indicator
The Pump Overload Indicator will illuminate when the
pump draws too much current. Low line voltage, single
phase power input, and a seized pump motor are all
possible causes for pump overload.
HAZARD OF ELECTRIC SHOCK. Disconnect
system power, if the Pump Overload Indicator
is illuminated. Hazard of electric shock or elec-
trocution. Disconnect all power and piping to
the system.
After the system power is disconnected, solve the
electrical current problem. To put the pump back on-
line, open the front electrical enclosure and press the
pump reset switch (See Figure 5.2, Overload Switch).
Figure 5.2 Pump Reset Switch
Close the front electrical enclosure door and
retighten the locking screw. This must be done
to limit access to high voltage components.
Failure to comply could lead to electric shock
or electrocution.
Over Temperature Indicator
If the system temperature exceeds 260°F (127°C), the
Over Temperature Indicator will illuminate. When the
system temperature drops below 260°F*, press RE-
SET on the controller face. The controller will not reset
until the temperature is below 260°F*.
*
190°F on CMX-180 model(s)
12
ELECTRIC SHOCK AND BURN HAZARD. Discon-
nect all power before servicing or performing
maintenance to the system. Do not attempt to
service system while it is operating or while
hot. Failure to comply can result in:
a. Electric shock.
b. Burns from hot heating elements, piping,
and hot oil or water.
c. Injury from operating or rotating pump and
motor.
Maintenance is to be performed by qualified
personnel only. Thoroughly read and under-
stand these instructions. Consult the factory if
you have any questions.
Shut Down
To take the unit out of service, the following steps must
be done in sequence:
1. Set the temperature controller setpoint to 90°F or
lower. Allow to cool.
2. Turn off power to the unit. The controller will turn
off.
3. Turn off the water supply to the unit.
4. Disconnect electrical supply to the unit.
5. Carefully bleed pressure from the system by loos-
ening a pipe fitting.
System may be pressurized. Use extreme care
while removing piping. Disconnect water sup-
ply, drain and process connections.
6. Drain all water from the system.
Draining
Drain the unit before taking it out of service for a pe-
riod of time, or if it is exposed to freezing temperatures
while out of service.
1. To drain the unit completely, move it to an inclined
position with the front of the system raised.
2. Remove the lower plugs on cast chambers (see
Figure 6.1, Chamber Photo).
Figure 6.1 Chamber Photo
Remove these
plugs
Section 6 – Maintenance
13
Heater Removal/Replacement
HAZARD OF ELECTRIC SHOCK. Disconnect all
power and piping to system.
1. Disconnect all power to the system.
2. Bleed pressure and drain all water from the sys-
tem.
3. Remove top panel.
4. Remove red top cover on the heater (see Figure
6.2, Heater/Chamber Photo).
5. Note location of wires on the heater, then remove
wires (L1, L2, L3).
6. Loosen compression fitting on the heater power
supply cable.
7. Remove cable from the heater.
8. Unbolt the heater (4 bolts) and remove.
9. Remove Bussing from old heater and re-install on
replacement heater, using the same orientation.
10. Replace heater and reverse procedure.
Close the front electrical enclosure door and
retighten the locking screw. This must be done
to limit access to high voltage components.
Failure to comply could lead to electric shock
or electrocution.
Figure 6.2 Heater/Chamber Photo
Remove Top Cover
on Heater
Remove Top Panel
14
Pump Removal/Replacement
HAZARD OF ELECTRIC SHOCK. Disconnect all
power and piping to system.
1. Disconnect all power to the system.
2. Bleed pressure and drain all water from the sys-
tem.
3. Remove top and side panels.
4. Remove pump motor wiring cover panel (2 screws).
5. Note location of pump motor wires and remove.
6. Loosen and remove vent line (see Figure 6.3, Motor
Vent Line).
7. Remove bolts holding pump motor to the casting
(4 bolts), and lift motor out of casting.
8. Remove impeller and install new mechanical seal
and impeller on the new motor.
9. Place new motor in system and bolt down.
10. Replace vent line and tighten.
11. Reconnect wires and replace wiring cover and side
panels.
12. Reconnect the system.
13. Perform Pump Rotation Check (see Section 2,
page 12).
14. Replace top panel.
Close the front electrical enclosure door and
retighten the locking screw. This must be done
to limit access to high voltage components.
Failure to comply could lead to electric shock
or electrocution.
Pump /Motor Vent Line
Heater Element
Housing
Motor
Pump Housing
Figure 6.3 Motor Vent Line
Heat Exchanger Removal/Replacement
(Closed loop system)
1. Disconnect all power to the system.
2. Bleed pressure and drain all water from the system.
3. Remove top panel.
4. Remove cover on the cooling solenoid (see Figure
6.4, Heat Exchanger).
5. Disconnect “COOLING INLET” and “COOLING
OUTLET” piping.
6. Disconnect copper tubing connected to the heat
exchanger.
7. Unbolt the heat exchanger and remove (4 bolts).
8. Place new heat exchanger in system and bolt
down.
9. Reconnect “COOLING INLET” and “COOLING
OUTLET” piping.
10. Reconnect wires to the cooling solenoid.
11. Reconnect copper tubing.
12. Replace cover on cooling solenoid and top panel.
13. Replace system water and reconnect the system.
Close the front electrical enclosure door and
retighten the locking screw. This must be done
to limit access to high voltage components.
Failure to comply could lead to electric shock
or electrocution.
Top Panel
Cooling Solenoid
Heat Exchanger
Figure 6.4 Heat Exchanger
15
Replacement Heating Elements and Contactors
MicroTHERM Model Replacement Parts
Open Loop Closed Loop Voltage Heating Element Heater Contactor
CMX-4 CMX-4C 240 155-554807-523 072-057576-050
CMX-4 CMX-4C 480 155-554807-523 072-057576-050
CMX-9 CMX-9C 240 155-554807-512 072-057576-050
CMX-9 CMX-9C 480 155-554807-512 072-057576-050
CMX-12 CMX-12C 240 155-554807-524 072-057576-050
CMX-12 CMX-12C 480 155-554807-524 072-057576-050
CMX-18 CMX-18C 240 155-554807-519 072-057576-051
CMX-18 CMX-18C 480 155-554807-519 072-057576-050
CMX-24 CMX-24C 240 155-554807-515 072-057576-051
CMX-24 CMX-24C 480 155-554807-515 072-057576-050
Replacement Parts Common to All Models
Identification # Part Name Part Number
1 3/4 HP Motor 240V/480V 193-121843-227
2 Solenoid Valve 344-121780-012
3 Pressure Relief Valve 344-048419-004
4 Automatic Air vent 344-053181-001
5 Pressure Gauge 130-118661-021
6 Pressure Switch 292-121927-028
7 Pump Mechanical Seal 251-121946-019
8 Heat Exchanger Bundle (Closed Loop) 353-123367-002
9 Heater/Cooling Gasket (2 total) 132-146012-020
10 Thermocouple 309-121759-063
11 Switch, Start/Stop
Switch Indicator Bulb
292-122882-043
213-122066-034
12 Diagnostic Indicator Light (3 total) 213-122066-041
13 Motor Contactor 240/480V 072-123534-064
14 Auxillary Motor Contact Block 071-122886-055
15 Motor Thermal Overload 240V
Motor Thermal Overload 480V
359-122078-096
359-122078-095
16 Transformer 240/480V 315-303786-001
17 Caster (4 total) 375-123425-003
18 Control Voltage Fuse 128-123445-005
19 Heater Contactor See table above
These parts may vary for non-catalog items.
Please consult your local Chromalox representative. (800-443-2640 or www.chromalox.com)
16
Figure 6.6 Replacement Parts Identification
From Process
To Process
5
12
13
5
START
ST
OP
Pump
System Diagnostics
Low Water Pressure
Pump Overload
Over Temperature
RESETAUX
PAGE
PAGE
HEAT
COOL
OUT3
OUT4
F
C
AUX
PV
SP
Chromalox
®
CMX Series
Temperature Control System
HEATER
CONTACTOR
1C
20
17
TRANSFORMER
AUX. CONTACT BLOCK
15
19
FUSE
1F
CONNECT
_____VOLT
SUPPLY
HERE
MOTOR CONTACTOR
14
MOTOR THERMAL
OVERLOAD
16
1M
Chromalox
®
17
Section 7 – Troubleshooting
Troubleshooting Guide - For qualified personnel only. See warnings in earlier sections.
Symptom Probable Cause Correction
Unit will not start, control
display does not light.
1. Unit not wired correctly. 1. Check wiring.
2. Disconnect switch OFF. 2. Turn disconnect ON.
3. Blown fuse. 3. Check customer disconnect fuses and
120V fuse on terminal block (blown fuse indi-
cator will light if fuse is blown).
4. Wrong voltage. 4.
Check supply voltage & unit’s rated voltage.
Control display lights, unit
will not start
1. Cooling water off, or below 20
psi. (CMX-250 models only)
1. Open cooling water valve, check to assure
pressure is above 30psi
2. Pump Motor Overload 2. Determine problem and press pump reset.
3. System above temperature
limit of 260°F. (190˚F on CMX-
180 Models)
3. Allow unit to cool below 260°F and press
RESET.
Unit stops while running
1. Cooling water drops below 20
psi
1. Check cooling water valve, check to as-
sure above 30 psi
2. Pump motor overload 2. Determine problem and press pump reset.
3. System exceeds temperature
limit of 260˚F (190˚F on CMX-180
Models)
3. Allow unit to cool below 260°F and press
RESET.
Low Water Pressure
Indicator Illuminated
1. Cooling water drops below 20
psi (CMX-180 models)
1. Check that pressure is above 30 psi
Pump Overload Indicator
illuminated
1. Pump motor overload 1. Determine the problem and press pump
reset button
Over Temperature
Indicator illuminated
1. System above temperature
limit of 600°F.
1. Allow unit to cool below 550°F and press
reset on over temperature controller inside
the panel. See Section 5.
Unit runs but fails to
pump.
1. Incoming phase reversed on
pump motor.
1. Swap any two legs on the incoming power.
Unit will not heat to
setpoint.
1. Cooling valve stuck open. 1. Check for cooling water flow during heat
cycle.
2. Heater element failure. 2. Check current at heater contactor during
heating.
3. Heater output insufficient. 3. Excessive losses in process or incorrectly
sized unit for application.
4. Controller needs to be tuned. 4. Check factory MENU settings, Section 3 of
this manual. Refer to 2104 Controller Techni-
cal Manual, page 35, for further information.
Unit will not cool to
setpoint.
1. Inadequate cooling water flow. 1. Open cooling water supply line more and
assure adequate pressure.
2. Cooling outlet obstructed. 2. Check cooling outlet for obstructions
3. Heater contactor fused
closed.
3. Check voltage across contactor during
cooling cycle.
4. Controller needs to be tuned. 4. Check factory MENU settings, Section 3 of
this manual. Refer to 2104 Controller Techni-
cal manual, page 35, for further information.
If you continue to have problems with the system after review of the above issues, please contact Chromalox
Product Service at 800-443-2640.
18
Section 8 – Specifications
Optional Pump Sizes
Optional Pump Sizes (HP) Nominal Flow (gpm)
1.5 40
3 50
5 60
7.5 80
Optional Options
Alternate Voltages: 208, 380, 575 VAC, 3 phase
Expanded Open Loop Cooling: increased cooling
water flow
Expanded Closed Loop Cooling: 6.3 sq. ft. heat
exchanger
Solid State Power Control: SCR heater switching
Surge Reduction valve: reduces water pressure
spikes
Door Interlock: prevents operation with service
door open
Digital Communications: for interface with Chro-
maSoft or remote PC/PLC systems
IEC Style Contactor: for dry contact power switch-
ing
Isolation Valve Kit: 1” ball valve for system isolation
Figure 8.1 - Pump Capacity
Pump Capacity
PSI
78
69
61
52
43
35
26
17
9
Ft.
180
160
140
120
100
80
60
40
20
020406080 100 120
U.S. Gallons Per Minute
3/4 HP
1.5 HP
3 HP
5 HP
7.5 HP
Five Pump sizes are available for the flow rate
appropriate to your process application.
kW Volts Ph.
Pump
Motor
HP
Dimensions
(In.)
Cooling Type Model Stock Part Number
Wt.
(Lbs)H W D
4.5 240 3 3/4 29 15 25 Open Loop CMX-250-4 NS 307418-032 200
4.5 480 3 3/4 29 15 25 Open Loop CMX-250-4 NS 307418-033 200
4.5 240 3 3/4 29 15 25 Closed Loop CMX-250-4C NS 307418-042 215
4.5 480 3 3/4 29 15 25 Closed Loop CMX-250-4C NS 307418-043 215
9 240 3 3/4 29 15 25 Open Loop CMX-250-9 NS 307418-034 200
9 480 3 3/4 29 15 25 Open Loop CMX-250-9 S 307418-035 200
9 240 3 3/4 29 15 25 Closed Loop CMX-250-9C NS 307418-044 215
9 480 3 3/4 29 15 25 Closed Loop CMX-250-9C S 307418-045 215
12 240 3 3/4 29 15 25 Open Loop CMX-250-12 NS 307418-036 200
12 480 3 3/4 29 15 25 Open Loop CMX-250-12 S 307418-037 200
12 240 3 3/4 29 15 25 Closed Loop CMX-250-12C NS 307418-046 215
12 480 3 3/4 29 15 25 Closed Loop CMX-250-12C S 307418-047 215
18 240 3 3/4 29 15 25 Open Loop CMX-250-18 NS 307418-038 200
18 480 3 3/4 29 15 25 Open Loop CMX-250-18 S 307418-039 200
18 240 3 3/4 29 15 25 Closed Loop CMX-250-18C NS 307418-048 215
18 480 3 3/4 29 15 25 Closed Loop CMX-250-18C S 307418-049 215
24 240 3 3/4 29 15 25 Open Loop CMX-250-24 NS 307418-040 200
24 480 3 3/4 29 15 25 Open Loop CMX-250-24 S 307418-041 200
24 240 3 3/4 29 15 25 Closed Loop CMX-250-24C NS 307418-050 215
24 480 3 3/4 29 15 25 Closed Loop CMX-250-24C S 307418-051 215
36 480 3 3/4 29 15 25 N/A CMX-250-36H NS 307418-052 215
48 480 3 3/4 29 15 25 N/A CMX-250-48H S 307418-053 215
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30

Chromalox CMX Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI