  • Hello! I am an AI chatbot trained to assist you with the Emerson Network Power User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Submittal for SiteI/O 10/0E
Liebert Corporation Page 1 of 4 Rev. 4; 10/03
DESCRIPTION: The SiteI/O 10/0E is part of the SiteI/O-Line and is intended to be used with
SiteScan Web systems specifically. It is a 32 bit microprocessor-based device designed to monitor up to
ten thermistors, and/or dry contact type signals. Logically the device, sits on the Ethernet network,
providing the interface to SiteScan Web. This effectively creates a device that is a router / gateway and
I/O module in one device. Screw terminal blocks are provided to terminate power, communication, and
input signal wiring.
DIMENSIONS: Module: 7 1/8" H x 6 1/4" W X 1 5/8” D
18.10cm H x 15.88cm W X 4.13cm D
Enclosure: 12”H x 14.25" W x 2.85" D
(painted steel) 419.1mm x 301.3mm x 78.6mm
POWER: 24 VAC ±10%, 50-60 Hz, 7.2 VA.
ENVIRONMENTAL
OPERATING RANGE:0 to 130°F (-17.8 to 54.4°C); 10 to 90% relative humidity, non-condensing.
For UUKL Smoke Control Systems, 32°-120.2°F (0°-49°C); 10 to 85% relative
humidity, non-condensing.
COMMUNICATIONS: One (1) Ethernet 10BaseT RJ-45 port
MEMORY: 1 MB flash, 1 MB RAM.
BATTERY: Seven-year lithium battery provides a minimum of 10,000 hours of data retention
during power outages.
FAULT DETECTION:Hardware watchdog timer.
PROTECTION: Built-in surge and transient protection circuitry.
Submittal for SiteI/O 10/0E
Liebert Corporation Page 2 of 4 Rev. 4; 10/03
MODULE DIMENSIONS AND LAYOUT
POWER WIRING DIAGRAMS
Submittal for SiteI/O 10/0E
Liebert Corporation Page 3 of 4 Rev. 4; 10/03
ENCLOSURE DIMENSIONS
Submittal for SiteI/O 10/0E
Liebert Corporation Page 4 of 4 Rev. 4; 10/03
Enclosure Wall Mounting
Enclosure Floor Mounting
/