4. DALI Commissioning
4
Following the physical installation and wiring of the DALI ECGs and lights
and the electronic commissioning, the connected ECGs need to be
learnt-in.
Before opening DCA for scanning, you need to give the KNX address first.
After assigning the address and downloading the database to DLC-02-
KN, the first DALI scan can be started, otherwise the error message as
shown in the figure below will appear.
Note:
(1)Use the "Scan" button to start searching devices and addressing.
During the process, all ECGs are automatically recognized and each ECG
is assigned a short address from 0~63. Depending on the size of the
connected DALI segments, the process may take a few minutes.
After downloading the database, please open the DCA communication
interface
or
During the first time installation, "Scan" and "Reinstall" make a
no difference in searching devices and addressing. After an
installation, the "Scan" button carries out a search for previously
addressed and unaddressed devices. Addressing for previously
addressed devices will remain unchanged. The next available
address is then assigned to devices which have been recently added,
whereas "Reinstall" removes all addresses and then re-addresses
them.