FEATURES
1. All sizes have been UL/FM certified and rated
to 300 psi.
2. All valves have an integral pre-wired
supervisory tamper switch assembly. The
tamper switch signals movement of the valve
disc from the full open position, when
correctly wired.
3. Switch rating: 10 Amps/115 VAC-60Hz
0.5 Amps/28 VDC
4. All vlaves are furnished with tamper switch
assemblies for indoor and outdoor use.
5. A 1/4 turn valve with slow closing and
opening will prevent water hammer and
shock from damaging the fire protection
system.
MODEL LPBT LPBG
TYPE Threaded end Grooved end
RATING 300 PSI
PN20 2065KPa
300 PSI
PN20 2065KPa
SIZE
1”, 1-1/4”,
1-1/2”, 2”,
2-1/2”
1-1/4”, 1-1/2”,
2”, 2-1/2”
INSTALLATION
1. The valve can be installed in any orientation
in a piping system with standard ASME
B1.20.1 NPT or standard roll or cut grooved
pipe.
2. When threading to pipe, apply adequate
pipe sealants, use a wrench to clamp on the
hexagon end of the valve.
3. The tamper has two switches: switch-1 has
dual leads on the terminals. This switch is
used for connection of the supervisory circuit
of a listed fire alarm control panel.
Switch 2 has a single lead and used for
connection of auxiliary equipment. All the
unused wires need to be capped with lead
nuts and tucked into a jucntion box. All
connections need to be reviewed and
approved by the AHJ.
4. A No.14 green wire is fixed inside the switch
housing. It is provided as a ground for the
housing.
5. Installation must comply with NFPA 13 and
NFPA 72.
6. The valves are intended for use with ANSI
B36.10 Schedule 40 and/or Schedule 80 pipe,
sizes 1”, 1-1/4”, 1-1/2”, 2” and 2-1/2”
IMO
REV1
-
510
Installation, Maintenance
& Operating Instructions
POWERBALL 300
LPBT & LPBG SERIES
1” ~ 2 1/2”, THREADED
1 1/4”~2 1/2” GROOVED
www.Breccocorp.com
2
MAIN DIMENSIONS
UNIT:INCHES
MATERIAL LIST
LPBT (Threaded Ends)
NO.
NAME MATERIAL
SIZE 1” 1-1/4
1-1/2
2” 2-1/2
1 BODY BRONZE ASTM 584 C83600
A 2.13 2.63 2.87 3.25 4.49 2 DISC SS304
H 4.94 5.13 5.59 6.13 6.58 3 HANDWHEEL ASTM A216 WCB
L 1.56 1.94 2.19 2.76 3.41 4 SEAT ASTM D2000 VITON
M 1.75 2.17 2.37 3.11 3.78 5 INDICATOR POWDER METAL FD0205 95HT
LPBG (Grooved Ends)
6 HOUSING BRASS ASTM B16 C36000
SIZE 1” 1-1/4
1-1/2
2” 2-1/2
7 COVER BRASS ASTM B16 C36000
A 3.86 4.02 4.09 4.49
H 5.20 5.47 6.07 6.58
P 0.63 0.63 0.63 0.63
O 0.31 0.31 0.31 0.31
M 1.54 1.78 2.25 2.72
L 1.67 1.90 2.37 2.87
NOTE:
Grooved ends to AWWA C606 for steel pipe.
Packing Gland with Adjustable Glands shall be accessible for
tightening stem seals without the disassembly of the valve or
operator parts U.S. Patented 6629.683.B2
3
WIRING DIAGRAM
SWITCH SHOWN POSITION WITH VALVE IN FULL OPEN
SWITCH 1 : DUAL LEADS SOLDERED TO SWITCH TABS
SWITCH 2 : SINGLE LEADS SOLDERED TO SWITCH TABS
Green wire is provided as ground for the switch housing.
Switch rating: 10 Amps/ 115 VAC-60Hz, 0.5 Amps/28 VDC
Installation must comply with NFPA 13 and NFPA 72.
Cap unused leads with wire nuts and tuck into a jucntion box (not provided).
Agent:
4
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Lansdale LPBT Series Installation, Maintenance & Operating Instructions

Category
Fire protection
Type
Installation, Maintenance & Operating Instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI