3
Instructional Leaflet IL0131182EN
Effective May 2022
Neutral current sensor for
IZM air circuit breakers trip units
EATON www.eaton.com
Figure 2. Sensor Installation Information.
Figure 3. Neutral Current Sensor Application (IEC).
ote: N Since the ground fault circuit breakers derive their operating power
from the phase current and not from the neutral current, passing current
through the neutral sensor only will not properly test the ground fault feature.
Using a low voltage (0 - 24 V) high current AC source, apply a test
current of 125% of the ground fault pick-up setting through one
phase of the circuit breaker as displayed in Figure 4. This should
cause the breaker to trip in less than one second, and if an alarm
indicator is supplied, it should operate. Reset the breaker and the
alarm indicator. Repeat the test on the other two phases.
Bus Bars
3.594”
9,1 cm
5”
12,7 cm
Top of Bus Bar
5” or 4”
12,7 cm or
10,2 cm
4x ø 0.41”
1,04cm
0.25” at 5”/ 0,6 cm at 12,7 cm
0.375” at 4”/ 1,0 cm at 10,2 cm
Bus Bar
Details
Sensor Outline
Details
0.375”/ M10 Hardware as
Required for Installation in
the Field
0.5”/1,27cm
0.984”/2,5cm
0.984”/2,5cm
0.984”/2,5cm
0.5”/1,3 cm
1.227” at 5”/ 3,1 cm at 12,7 cm Bus Bar
0.227” at 4”/ 0,6 cm at 10,2 cm Bus Bar
X
X
NSource
L C R
Neutral Sensor
Load
11 12
For 2x External
N-conductors in
parallel check
Figure 7
If the system is a 4-wire system with a neutral current sensor, apply
the same current as described above through one phase of the
breaker, returning through the neutral sensor, as displayed in Figure
5. The breaker should not trip and the alarm indicator, if supplied,
should not operate. Repeat the test on the other two phases.
If the system is a 3-wire system with no neutral current sensor,
apply the same current as described above through any two phases
of the breaker with the connections as displayed in Figure 6. The
breaker should not trip and the alarm indicator, if supplied, should
not operate.
Repeat the test using the other two combinations of breaker
phases. Record the test results on the test form provided with the
equipment.
m CAUTION
FIELD TESTING SHOULD BE USED FOR FUNCTIONAL TESTING, NOT FOR
FIELD CALIBRATION. IF TEMPORARY CONNECTIONS WERE MADE FOR
THE PURPOSE OF CONDUCTING TESTS, RESTORE TO PROPER OPERATING
CONDITIONS BEFORE RETURNING THE BREAKER TO SERVICE.
m WARNING
ELECTRICAL SHOCK OR BURN INJURY CAN OCCUR WHEN WORKING
ON POWER SYSTEMS. ALWAYS TURN OFF POWER SUPPLYING CIRCUIT
BREAKER BEFORE CONDUCTING TESTS. TEST OUT OF THE CELL, IF
POSSIBLE.