Effective August 2022
Instructional Leaet IL0131183EN
Vertical adapter kit for fixed and
withdrawal IZM low voltage
circuit breakers
m WARNING
(1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD
BE PERMITTED TO WORK ON THE EQUIPMENT
(2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY
CIRCUITS IF A CIRCUIT BREAKER CANNOT BE
REMOVED TO A SAFE WORK LOCATION
(3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED
(RACKED) OUT TO THE DISCONNECT POSITION.
(4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO
THE OFF POSITION AND MECHANISM SPRINGS
DISCHARGED.
FAILURE TO FOLLOW THESE STEPS FOR ALL
PROCEDURES DESCRIBED IN THIS INSTRUCTION
LEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR
PROPERTY DAMAGE.
m WARNING
THE INSTRUCTIONS CONTAINED IN THIS IL AND ON
PRODUCT LABELS MUST BE FOLLOWED. OBSERVE
THE FIVE SAFETY RULES.
• DISCONNECTING;
• ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY
RESTARTED;
• VERIFY ISOLATION FROM THE SUPPLY;
• EARTHING AND SHORT-CIRCUITING; AND;
• COVERING OR PROVIDING BARRIERS TO ADJACENT
LIVE PARTS.
DISCONNECT THE EQUIPMENT FROM THE SUPPLY.
USE ONLY AUTHORIZED SPARE PARTS IN THE REPAIR
OF THE EQUIPMENT. THE SPECIFIED MAINTENANCE
INTERVALS AS WELL AS THE INSTRUCTIONS FOR
REPAIR AND EXCHANGE MUST BE STRICTLY ADHERED
TO PREVENT INJURY TO PERSONNEL AND DAMAGE
TO THE SWITCHBOARD.
Section 1: General information
The vertical stab adapter kit provides a means
by which the primary terminal connections can
be mounted vertically. The instructions for this
kit apply to IZM32 (standard frame) and IZM63
(double frame) breakers.
Required tools
• Socket drive torque wrench
• 17 mm socket
• 17 mm wrench
Kit parts identification
Refer to Figure 1 for a visual parts reference
of hardware supplied in a kit.
(A) 90-degree adapter (six required for
three-pole installations, eight required for
four-pole installations)
(B) M10 x 60 hex bolt (18 required for
three-pole installations, 24 required for
four-pole installations)
(C) M10 hex nut (18 required for three-pole
installations, 24 required for four-pole installations)
(D) M10 conical spring washer (18 required
for three-pole installations, 24 required for
four-pole installations)
(E) M10 flat washer (36 required for
three-pole installations, 48 required for
four-pole installations)
ote: N Kit content quantities are doubled when ordering
adapter kits for double-wide frame IZM63 breakers.
Figure 1. Contents of Kit
ote: N Quantities for hardware items (B), (C), (D), and (E)
are for standard frames only.
ote: N A number of graphics in this instruction leaflet use
the standard frame (IZM32) circuit breaker for illustrative
purposes only. The double frame circuit breaker (IZM63)
is handled in a similar fashion. Some components, such
as the trip unit, are not shown for clarity.
(A)
(B)
(C)
(D)
(E)