11
Error code
Diagnosis for models
YIFFXC025BAEFA YIFFXC030BAEFA YIFFXC036BAEFA YIFFXC036BANFA YIFFXC040BANFA
YIFFXC040BAEFB
Wired
controller
display
Possible reasons
LED flash
times of signal
receiver board
1
Malfunction of indoor unit ambient
temperature sensor
Malfunction of indoor unit piping
temperature sensor
Compressor overcurrent / phase
sequence wrong
Abnormal communication between
wired controller and indoor unit
Malfunction of drain system
Indoor coil temperature too high in
cooling mode
2
5
9
10
14
Contents of Malfunction
E1
E2
E5
E8
E0
FC
Sensor disconected,or broken, or at wrong position,
or short circuit
Sensor disconected, or broken, or at wrong position,
or short circuit
Overcurrent after compressor running or power suppl
phase sequence wrong before compressor running.It
occurs 3 times in 1 hour, comfirm the failure, the former
twice will not alarm.
Wrong connection or wired controller broken, or PCB
faulty
Pump motor disconnected or at wrong position,or
the float switch disconnected, or at wrong position,
or the short circuit bridge disconne ted
Refrigerant leakage or indoor coil sensor falling off
Wired
controller
display
Possible reasons
LED flash
times of signal
receiver board
0
Malfunction of indoor unit ambient
temperature sensor
0
0
0
0
Contents of Malfunction
01
02
04
07
/
Sensor disconected,or broken, or at wrong position,
or short circuit
1
2
4
7
8
Malfunction of indoor unit ambient
temperature sensor
Sensor disconected,or broken, or at wrong position,
or short circuit
EEPROM wrong of indoor PCB
EEPROM chip disconected or broken or wrong
programmed, or PCB broken
Abnormal communication between
indoor and outdoor units.
Wrong connection,or the wires be disconected or wrong
adress setting of indoor unit or faulty power supply or
faulty PCB or slave unit malfunction in MAXI system.
Abnormal communication between
wired controller and indoor unit
Wrong connection or wired controller broken, or PCB
faulty
00C12
00D13
01016
Malfunction of drain system
Pump motor disconnected or at wrong position,or
the float switch disconnected, or at wrong position,
or the short circuit bridge disconne ted
Zero cross sigal wrong Zero cross sigal detected wrong
Indoor abnormal mode operation Different from outdoor unit mode
Note:
1. The outdoor failure can also be indicated by the indoor unit, the checking method as follows: LED4 flash times stands
for tens digit, and LED3 flash times stands for units digit, use this bidigitate figure minus 20, then will get the outdoor
error code. For example, if the outdoor error code is 15, LED4 will flash 3 times firstly, two seconds later, LED3 will flash
5 times, and four seconds later the process will repeat again.
2. LED4 is a yellow one on the indoor PCB, LED3 is a green one.
3. To get much more details about the out door unit failure, please refer to the outdoor unit trouble shooting list.