Megger vf2 User manual

Type
User manual
GSAFETY WARNINGS
The VF3 Voltage detector may help in the indication of live AC circuits only, and
must not be used as verification of a de-energised circuit. This is not a safety test
lamp.
If damaged, do not use.
This instruction guide and markings on the detector provide information for
avoiding hazards and unsafe practices related to the use of this tool.
Observe all of the safety information provided.
F WARNING - ELECTRIC SHOCK HAZARD :
Contact with live circuits can result in severe injury or death
Do not use the unit if it is wet or damaged
Do not apply more than the rated voltage between the
probe tip and earth ground
Do not operate with the case open
CAUTION: Do not attempt to repair this unit, it contains no
user-serviceable parts
Do not expose the unit to extremes in temperature or
high humidity
CATIV - Measurement category IV: Equipment connected between the origin
of the low-voltage mains supply outside the building and the consumer unit.
CATIII - Measurement category III: Equipment connected between the
consumer unit and the electrical outlets.
CATII - Measurement category II: Equipment connected between the
electrical outlets and the user’s equipment.
t Equipment protected throughout by
double insulation (Class II).
Equipment complies with current EU directives.
End of life disposal
WEEE DIRECTIVE
The crossed out wheeled bin symbol on the instrument and on the batteries is a
reminder not to dispose of them with general waste at the end of their life.
Megger is registered in the UK as a Producer of Electrical and Electronic
equipment. The registration no is; WEE/DJ2235XR.
Users of Megger products in the UK may dispose of them at the end of their
useful life by contacting B2B Compliance at
www.b2bcompliance.org.uk or by telephone on 01691 676124.
Users of Megger products in other parts of the EU should contact their local
Megger company or distributor.
BATTERY DISPOSAL
Batteries in this product are classified as Portable Batteries under the Batteries
Directive. Please contact Megger Ltd for instructions on the safe disposal of
these batteries. For disposal of batteries in other parts of the EU contact your
local distributor.
Megger is registered in the UK as a producer of batteries.
The registration number is BPRN01235.
For Further information see www.megger.com
G Read and understand all instructions and safety
information in this guide before operating this
detector.
DESCRIPTION
The Megger VF3 voltage detector is intended to check for the presence of AC
voltage, signaled by a bright red LED situated within the white nylon tip and
an audible buzzer. The VF3 has the added advantage of a bright-white LED
flashlight for use in poor light.
FEATURES
Non-contact detection of AC voltage 100 V - 600 V
AC 50 Hz/60 Hz
Visual and audible warning of high voltage
Durable rubber over-moulded body
Built in bright-white LED flashlight
Low power consumption - many hours of flashlight illumination
from one set of alkaline batteries
Convenient pocket-size
The Megger VF3 is useful for identifying live conductors, finding a break in a
wire, verifying a blown fuse while in circuit, and detecting the presence of AC
voltage at
Socket outlets
Switches
Circuit breakers
Fuses
Wires and cables
Luminaires
GOOD PRACTICE:
Before each use the unit must be tested on a known live supply.
Place the probe tip on or near the circuit under test. The probe tip will glow
bright red and the buzzer will sound when an AC voltage between 90 V and
600 V is detected.
If the unit still fails to operate satisfactorily, return for repair.
If the unit does not function as expected , replace the batteries.
NOTE: The VF3 cannot detect voltage on armoured or sheathed cable, or on
cable in conduit, behind panels or in metallic enclosures.
FLASHLIGHT
Operate the black button alternately to turn the white LED ON and OFF.
BATTERY REPLACEMENT
Remove the unit from proximity of any live circuits
Turn off flashlight
Remove battery cap (1) by lifting clip (2) slightly and pulling
cap (1) off body (3)
Replace batteries, carefully observing correct type and polarity
Replace battery cap (1)
VF3
1
2
3
SPECIFICATIONS
INDICATORS: OPTICAL VIA LED AND ACOUSTICAL VIA BUZZER
Voltage range: 90 - 600 V AC 50/60 Hz
Operating temp: -10°C - 50°C
Humidity: Max. 90%
Safety: EN61010-1:2010
EMC: EN61326
Safety Rating: CAT IV 600 V
Battery: 2 x AAA / LR03
Size: 178 mm x 26 mm
Weight: 48 g (including batteries)
Megger Limited
Archcliffe Road, Dover
Kent CT17 9EN England
T +44 (0)1 304 502101
F +44 (0)1 304 207342
Megger
Z.A. Du Buisson de la Couldre
23 rue Eugène Henaff
78190 Trappes France
T +33 (0)1 30.16.08.90
F +33 (0)1 34.61.23.77
Megger
4271 Bronze Way, Dallas, TX
75237-1019 USA
T +1 800 723 2861
T +1 214 333 3201
F +1 214 331 7399
Sales@megger.com
Megger GmbH
Obere Zeil 2
61440 Oberursel
Deutschland
T 06171-92987-0
F 06171-92987-19
info@megger.de
Megger products are distributed in 146 countries worldwide.
This instrument is manufactured in China.
The company reserves the right to change the specification or design
without prior notice.
Megger is a registered trademark
VF3_UG_en-fr-de-es_V01 www.megger.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Megger vf2 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI