Shinko SEWx series User manual

Type
User manual
PLUG-IN TYPE
PROGRAMMABLE SIGNAL CONDITIONER
SEW SERIES
INSTRUCTION MANUAL
2
Preface
Thank you for purchasing the SEW series Programmable Signal Conditioner.
This manual contains instructions for the mounting, functions, operations and notes when
operating the SEW series. To ensure safe and correct use, thoroughly read and understand
this manual before using this unit. To prevent accidents arising from the misuse of this
instrument, please ensure the operator receives this manual.
Notes
This instrument should be used in accordance with the specifications described in the manual.
If it is not used according to the specifications, it may malfunction or cause a fire.
Be sure to follow the warnings, cautions and notices. If they are not observed, serious injury or
malfunction may occur.
Specifications of the SEW series and the contents of this instruction manual are subject to
change without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if there
are any doubts, mistakes or questions, please inform our sales department.
This instrument is designed to be installed on a DIN rail within a control panel. If it is not, measures must
be taken to ensure that the operator does not touch power terminals or other high voltage sections.
Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
Shinko Technos Co., Ltd. is not liable for any damages or secondary damages incurred as a result
of using this product, including any indirect damages.
SAFETY PRECAUTIONS (Be sure to read these precautions before using our products.)
The safety precautions are classified into categories: “Warning” and “Caution”.
Depending on the circumstances, procedures indicated by Caution may cause serious
results, so be sure to follow the directions for usage.
Warning
Warning
To prevent an electric shock or fire, only Shinko or other qualified service personnel may
handle the inner assembly.
To prevent an electric shock, fire or damage to the instrument, parts replacement may only
be undertaken by Shinko or other qualified service personnel.
Safety Precautions
To ensure safe and correct use, thoroughly read and understand this manual before using this
instrument.
This instrument is intended to be used for industrial machinery, machine tools and measuring
equipment. Verify correct usage after purpose-of-use consultation with our agency or main
office. (Never use this instrument for medical purposes with which human lives are involved.)
External protection devices such as protective equipment against excessive temperature rise, etc.
must be installed, as malfunction of this product could result in serious damage to the system or
injury to personnel. Also proper periodic maintenance is required.
This instrument must be used under the conditions and environment described in this manual.
Shinko Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring
due to the instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the
manufacture of weapons of mass destruction (i.e. military applications, military equipment,
etc.), please investigate the end users and the final use of this instrument.
In the case of resale, ensure that this instrument is not illegally exported.
Caution
Procedures which may lead to dangerous conditions and cause
death or serious injury, if not carried out properly.
Procedures which may lead to dan
gerous conditions and cause
superficial to medium injury or physical damage or may degrade or
damage the product, if not carried out properly.
3
1
1
.
.
I
I
n
n
s
s
t
t
a
a
l
l
l
l
a
a
t
t
i
i
o
o
n
n
P
P
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of -5 to 55 (23 to 131 )
that does not change rapidly, and no icing
• An ambient non-condensing humidity of 35 to 85 %RH
• No large capacity electromagnetic switches or cables through which large current is flowing
No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit
When installing this unit within a control panel, take note that the ambient temperature
of this unit not the ambient temperature of the control panel - must not exceed 55
(131 ), otherwise the life of the electronic components (especially electrolytic
capacitors) of the unit will be shortened.
Note: Avoid setting this instrument directly on or near flammable material even
though the case of this instrument is made of flame-resistant resin.
2
2
.
.
W
W
i
i
r
r
i
i
n
n
g
g
P
P
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
Do not leave wire remnants in the instrument, because they could cause a fire and/or a
malfunction.
• When wiring terminals, use a solderless terminal with an insulation sleeve in which an
M3 screw fits.
• Tighten the terminal screw using the specified torque.
If excessive force is applied to the screw when tightening, the screw may be damaged.
• This instrument has no built-in power switch, circuit breaker or fuse.
Be sure to install a built-in power switch, circuit breaker or fuse near the instrument.
(Recommended fuse: Time-lag fuse, rated voltage 250 V AC, rated current 2 A)
• For wiring of AC power source, be sure to use exclusive terminals as described in this
manual. If AC power source is connected to incorrect terminals, the unit will burn out.
• For a 24 V DC power source, do not confuse polarity.
• Do not apply a commercial power source to the sensor connected to the input terminal
nor allow the power source to come into contact with the sensor.
• Use a thermocouple, compensating lead wire and 3-wire RTD according to the sensor
input specifications of this unit.
When using DC voltage and current input, do not confuse polarity when wiring.
Keep the input/output wires and power line separate.
3
3
.
.
O
O
p
p
e
e
r
r
a
a
t
t
i
i
o
o
n
n
a
a
n
n
d
d
M
M
a
a
i
i
n
n
t
t
e
e
n
n
a
a
n
n
c
c
e
e
P
P
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
• Do not touch live terminals. This may cause electric shock or problems in operation.
Turn the power supply to the instrument OFF when retightening the terminal and
cleaning. Working on or touching the terminal with the power switched ON may result
in severe injury or death due to electric shock.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may tarnish or deface the unit.)
As the display section is vulnerable, do not strike or scratch it with a hard object or
put pressure on it.
4
Model Explanation
Model names included in this manual are indicated below.
An individual model name will be used for individual explanations.
For common explanations, the model name SEW will be used.
Indication Model
SEW SEWU, SEWE, SEWR, SEWA, SEWV, SEWD, SEWD-F
Characters Used in This Manual
Indication
Number, / -1 0 1 2 3 4 5 6 7 8 9
Indication
Alphabet A B C D E F G H I J K L M
Indication
Alphabet N O P Q R S T U V W X Y Z
means that no character is indicated (unlit) on the display.
5
--- CONTENTS ---
1. Model Page
1.1 Model ---------------------------------------------------------------------------- 6
1.2 How to Read the Model Label --------------------------------------------- 6
2. Name and Functions of Sections ------------------------------------------- 7
3. Mounting
3.1 External Dimensions (Scale: mm) ---------------------------------------- 8
3.2 Mounting to a DIN Rail ------------------------------------------------------ 8
3.3 Removal from a DIN Rail -------------------------------------------------- 10
4. Wiring
4.1 Lead Wire Solderless Terminal ------------------------------------------ 12
4.2 Terminal Arrangement, Circuit Configuration ------------------------ 13
4.3 Wiring of Terminals
4.3.1 Power Source Wiring -------------------------------------------------- 14
4.3.2 Output Wiring ------------------------------------------------------------ 14
4.3.3 Input Wiring -------------------------------------------------------------- 15
5. Key Operation Flowchart ---------------------------------------------------- 16
6. Setup ------------------------------------------------------------------------------- 18
6.1 Indication after Power-on ------------------------------------------------- 19
6.2 Basic Operation of Setup ------------------------------------------------- 19
6.3 Setup
6.3.1 Input 1/Output 1 Function Group ----------------------------------- 21
6.3.2 Output 2 Function Group --------------------------------------------- 23
6.3.3 Special Function Group ---------------------------------------------- 24
6.3.4 Using This Unit as a Standard Signal Conditioner ------------ 25
6.3.5 Using the Reverse Function ---------------------------------------- 25
6.3.6 Using the First Order Lag Filter Function ------------------------ 25
7. Adjustment
7.1 Basic Operation of Adjustment ------------------------------------------ 26
7.2 Adjustment
7.2.1 Output 1 Adjustment Group ----------------------------------------- 27
7.2.2 Output 2 Adjustment Group ----------------------------------------- 28
8. Operation
8.1 Indication after Power-on ------------------------------------------------- 28
8.2 Unit Operation --------------------------------------------------------------- 28
9. Specifications ------------------------------------------------------------------- 31
10. Troubleshooting
10.1 Indication -------------------------------------------------------------------- 34
10.2 Key Operation -------------------------------------------------------------- 34
10.3 Operation -------------------------------------------------------------------- 34
11. Character Table ----------------------------------------------------------------- 35
6
1. Model
1.1 Model
SEW Series
S E - -
W U 2-output Universal (*1) (*2)
W E 2-output Thermocouple
W R 2-output RTD
W A 2-output Direct current (*2)
W V 2-output DC voltage
W D 2-output Current Loop Supply
Signal
Conditioner
Type
W D F
2-output Current Loop Supply
(Suitable for Field communicator usage)
1
Finger-safe, Screw fall prevention
(Only Y-type terminal usable)
Socket
2 Ring-type terminal usable
0 100 to 240 V AC
Power supply
1 24 V AC/DC
(*1) SEWU accepts universal (all types of) inputs and outputs.
Types other than SEWU accept universal outputs only.
Input: Thermocouple, RTD, Direct current, DC voltage
Output: Direct current, DC voltage
(*2) For Direct current input, a shunt resistor (sold separately) is required.
(e.g.) SEWU-1-0
Type: 2-output Universal transmitter
Socket: Finger-safe, Screw fall prevention (Only Y-type terminal usable)
Power supply: 100 to 240 V AC
Factory default: Input: 1 to 5 V DC
Output 1: 4 to 20 mA DC
Output 2: 4 to 20 mA DC
1.2 How to Read the Model Label
The model label is attached to the left side of the case.
(Fig. 1.2-1)
Model (e.g. SEWU-1-0)
Input: Enter a range selected in [Input range].
Output 1: Enter a type selected in [Output type].
Output 2: Enter a type selected in [Output type].
Serial number
7
2. Name and Functions of Sections
(Fig. 2-1)
(1) Power indicator (Green): Lights when the power to the instrument is turned ON.
(2) Input Display (Red): Indicates the input value in RUN mode.
Indicates Output 1 value when ‘Output 1/Output 2 value’ is selected in [Display selection].
Indicates setting item characters in Setup mode.
Indicates adjustment item characters in Adjustment mode.
(3) Output Display (Red): Indicates Output 1 value (%) in RUN mode.
Indicates Output 2 value when ‘Output 1/Output 2 value’ is selected in [Display selection].
Indicates the set value in Setup mode.
Indicates the adjustment value in Adjustment mode.
(4) UP Key ( ): Increases the numeric value, or switches the selection items.
(5) DOWN Key ( ): Decreases the numeric value, or switches the selection items.
(6) MODE Key ( ): Selects or switches groups, and registers the set value.
(7) SUB-MODE Key
Turns the displays ON again while they are in OFF status. (The UP, DOWN or MODE Key
also turns the displays ON again while they are in OFF status.)
(8) Console connector
By connecting to the USB communication cable (CMB-001, sold separately), the following
operations can be conducted from an external computer using the SWS-SE001M Console
software: Reading/setting of various set values, Reading of input values and action status
(9) Light sensor
Automatically measures and controls brightness of the Input and Output Displays.
Notice
When setting the specifications and functions of this instrument, connect mains power
cable to terminals 13 and 14 first, then set them referring to “5. Key Operation Flowchart”
and “6. Setup” before performing “3. Mounting” and “4. Wiring”.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
8
3. Mounting
3.1 External Dimensions (Scale: mm)
(Fig. 3.1-1)
3.2 Mounting to a DIN Rail
(1) Hook the upper part of the socket on the DIN rail, and mount it.
(A clicking sound is heard.)
(Fig. 3.2-1)
Caution
Wire the instrument before inserting the unit into the socket.
For wiring, refer to Section “4. Wiring”.
Hook the upper part of the
socket on the DIN rail.
30
79
108
3.3
DIN rail
85
(29)
Socket
3
9
(2) Confirm that the Lock Release is lowered.
(Fig. 3.2-2)
(3) Insert the SEW series into the socket.
(Fig. 3.2-3)
When inserting, be careful
about the position of pins
and slots.
Lock Release
10
(4) Fix the SEW series and the socket by pushing the Lock Release up.
(Fig. 3.2-4)
3.3. Removal from a DIN Rail
(1) Turn the power supply to the unit OFF.
(2) Pull the Lock Release down, and release the SEW series from the socket.
(Fig. 3.3-1)
Lock Release
Check that the SEW series
and the socket are locked by
pushing the Lock Release up.
Lock Release
Check that the SEW series
and the socket are unlocked by
pulling the Lock Release down.
11
(3) Separate the SEW series from the socket.
(Fig. 3.3-2)
(4) Remove the socket from the DIN rail by pulling the Socket Lock Release
(at the bottom of the socket) down.
(Fig. 3.3-3)
12
4. Wiring
Warning
Turn the power supply to the instrument off before wiring.
Working on or touching the terminal with the power switched ON may result
in severe injury or death due to electric shock.
4.1 Lead Wire Solderless Terminal
Use a solderless terminal with an insulation sleeve in which an M3 screw fits as follows.
For the sockets with finger-safe & screw fall prevention functions, the ring-type terminals
are unusable.
The torque should be 0.63 N•m.
Solderless
Terminal
Manufacturer Model
Y-type Nichifu Terminal Industries CO., LTD. TMEV1.25Y-3S
Nichifu Terminal Industries CO., LTD. TMEV 1.25-3
Ring-type
Japan Solderless Terminal MFG CO., LTD. V1.25-3
(Scale: mm)
(Fig. 4.1-1)
13
-
+
-
+
CPU
13
14
9
10
11
12
+
+
-
-
50
1
2
3
4
6
8
5
7
-
+
Power
supply
Output 1
Output 2
Output
circuit
Output
circuit
Power
circuit
Insulation circuit
Insulation circuit
24V DC
Power
circuit
Input
circuit
Display/Setting
key circuit
Power supply for
2-wire transmitter
mA DC
+
T C
+
1
2
3
4
5
6
7
8
CPU
13
14
9
10
11
12
-
+
-
+
-
-
A
B
B
RTD
-
mA DC
+
-
(
1V)
-
+
V DC (
10V)
Insulation circuit
Insulation circuit
Output
circuit
Output 1
Power supply
Power
circuit
Display/Setting
key circuit
Input
circuit
Output
circuit
Output 2
+
mV DC
4.2 Terminal Arrangement, Circuit Configuration
SEWU, SEWE, SEWR, SEWA, SEWV
DC voltage input:
mV DC( 1 V): 0 to 10 mV DC, -10 to 10 mV DC, 0 to 50 mV DC, 0 to 60 mV DC,
0 to 100 mV DC, 0 to 1 V DC
V DC( 10 V) : 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC
(Fig. 4.2-1)
SEWD
(Fig. 4.2-2)
14
SEWD-F
(Fig. 4.2-3)
4.3 Wiring of Terminals
Warning
• For 100 to 240 V AC, if AC power source is connected to incorrect terminals,
this instrument will burn out.
• For a 24 V DC power source, do not confuse polarity when wiring.
4.3.1 Power Source Wiring
Use terminals 13 (+) and 14 (-) for the power supply to the instrument.
4.3.2 Output Wiring
Use terminals 9 (+) and 10 (-) for Output 1 wiring.
Use terminals 11 (+) and 12 (-) for Output 2 wiring.
24V DC
CPU
1
2
3
4
5
6
7
8
13
14
9
10
12
11
50
240
+
-
+
+
+
+
-
-
-
-
mA DC
Input circuit
Power circuit
Output circuit
Output circuit
Insulation circuit
Insulation circuit
Power circuit
Output 1
Output 2
Power supply
Display/Setting
key circuit
Power supply for
2-wire transmitter
15
+
-
50
1
2
3
4
+
-
+
Input
circuit
2-wire
transmitter
24V DC
power
circuit
+
-
Input
50
1
2
3
4
Input
circuit
24V DC
power
circuit
+
-
50
240
1
2
3
4
+
-
+
Input
circuit
24V DC
power
circuit
2-wire
transmitter
+
-
50
240
1
2
3
4
Input
Input
circuit
24V DC
power
circuit
4.3.3 Input Wiring
SEWU (thermocouple, RTD, DC voltage inputs), SEWE, SEWR, SEWV:
Terminals for wiring differ depending on the input specifications.
See (Fig. 4.2-1, p.13).
SEWU (Direct current input), SEWA:
Use terminals 1 (+), 2 (-) for input wiring and shunt resistor connection.
See (Table 4.3.3-1). (Shunt resistor: Sold separately)
(Table 4.3.3-1)
Shunt Resistor
Input
Model
(Y-type terminal)
Model
(Ring-type terminal)
Specification
4 to 20 mA DC
0 to 20 mA DC
0 to 16 mA DC
RES-S06-050 RES-S01-050 50 0.1%
2 to 10 mA DC
0 to 10 mA DC
RES-S06-100 RES-S01-100 100 0.1%
1 to 5 mA DC RES-S06-200 RES-S01-200 200 0.1%
0 to 1 mA DC RES-S06-01K RES-S01-01K 1 k 0.1%
SEWD, SEWD-F: When using as a Current Loop Supply or as an Isolator, be sure
to wire the unit as follows. See (Fig. 4.3.3-1) to (Fig. 4.3.3-4).
SEWD
As a Current Loop Supply As an Isolator
(Fig. 4.3.3-1) (Fig. 4.3.3-2)
SEWD-F
As a Current Loop Supply As an Isolator
(Fig. 4.3.3-3) (Fig. 4.3.3-4)
16
5. Key Operation Flowchart
POWER ON
The Input Display indicates input type, and the Output Display indicates the Output 1
type for 3 sec after power is turned ON. See (Tables 5-1, 5-2).
RUN Mode
Output 1 Adjust- Output 2 Adjust- Input 1/ Output 1
ment Group ment Group Function Group
Output zero adjust Output zero adjust Input type (*1)
-5.00 to 5.00% -5.00 to 5.00% : Thermocouple
: RTD
Output span adjust Output span adjust : Direct current
-5.00 to 5.00% -5.00 to 5.00% : DC voltage
Input range (*2)
See (Table 5-1).
Decimal point place (*3)
: No decimal point
: 1 digit after point
: 2 digits after point
: 3 digits after point
Output 0% value
Input range low limit to
Output 100% value
DC input: -1999 to
Output 100% value
Output 100% value
Output 0% value to
Input range high limit
DC input:
Output 0% value to 9999
Filter time constant
0.0 to 10.0 seconds
Sensor correction
-100.0 to 100.0 ( )
-1000 to 1000 (DC input)
Output type
See (Table 5-2).
Output Normal/Reverse
: Normal
: Reverse
Burnout (*4)
: Upscale
: Downscale
(Table 5-1)
Item Input Type & Range Item Input Type & Range
K -200 to 1370 K -328 to 2498
K -200 to 200 (*) K -328 to 392 (*)
K 0 to 400 (*) K 32 to 752 (*)
J -200 to 1000 J -328 to 1832
J -200 to 200 (*) J -328 to 392 (*)
J 0 to 400 (*) J 32 to 752 (*)
R -50 to 1760 R -58 to 3200
S -50 to 1760 S -58 to 3200
B 0 to 1820 B 32 to 3308
E -200 to 800 E -328 to 1472
T -200 to 400 (*) T -328 to 752 (*)
N -200 to 1300 N -328 to 2372
PL- 0 to 1390 PL- 32 to 2534
W5Re/W26Re 0 to 2315 W5Re/W26Re 32 to 4199
W3Re/W25Re 0 to 2315 W3Re/W25Re 32 to 4199
Pt100 -200 to 850 Pt100 -328 to 1562
Pt100 -100 to 100 (*) Pt100 -148 to 212 (*)
JPt100 -200 to 500 JPt100 -328 to 932
4 to 20 mA DC -1999 to 9999 0 to 10 mV DC -1999 to 9999
0 to 20 mA DC -1999 to 9999 -10 to 10 mV DC -1999 to 9999
0 to 16 mA DC -1999 to 9999 0 to 50 mV DC -1999 to 9999
2 to 10 mA DC -1999 to 9999 0 to 60 mV DC -1999 to 9999
0 to 10 mA DC -1999 to 9999 0 to 100 mV DC -1999 to 9999
1 to 5 mA DC -1999 to 9999 0 to 1 V DC -1999 to 9999
0 to 1 mA DC -1999 to 9999 0 to 5 V DC -1999 to 9999
1 to 5 V DC -1999 to 9999
0 to 10 V DC -1999 to 9999
(*) No decimal point’ or ‘1 digit after decimal point’ can be selected in
[Decimal point place].
(Table 5-2)
Item Output Type Item Output Type
4 to 20 mA DC 0 to 1 V DC
0 to 20 mA DC 0 to 5 V DC
0 to 12 mA DC 1 to 5 V DC
0 to 10 mA DC 0 to 10 V DC
1 to 5 mA DC
17
Output 2 Function Group Special Function Group
Output 0% value (*4) Set value lock
Input range low limit to : Unlock
Output 100% value : Lock
Output 100% value (*4) Input sampling period (Response time)
Output 0% value to : 25 ms [65 ms(typ.)(090%)]
Input range high limit : 125 ms [225 ms(typ.)(090%)]
: 250 ms [425 ms(typ.)(090%)]
Output type
See (Table 5-2). Auto-light function
: Disabled
Output Normal/Reverse : Enabled
: Normal
: Reverse Display Selection
[Input Display] [Output Display]
: Input value Output 1 value
: Input value No indication
: Output 1 value Output 2 value
: No indication No indication
Indication Time
00.00 (Remains lit)
00.01 to 60.00 (Minutes.Seconds)
[About Setting Items]
Output zero adjust
-5.00 to 5.00%
• Upper left (Input Display): Shows setting or
adjustment characters.
Lower left (Output Display): Shows factory default.
• Upper right: Shows setting or adjustment items.
Lower right: Shows setting range, selection items
.
• Depending on the model, some items do not appear.
(*1) Available for the SEWU only.
(*2) Not available for the SEWD, SEWD-F.
(*3) Available if DC voltage or current is selected
in [Input type] or if (*) range for thermocouple
or RTD (Table 5-1) is selected.
(*4) Available for the thermocouple or RTD input.
[Key Operation]
, : This means that if the or key is
pressed, the unit proceeds to the next setting
mode.
• The or key sets the setting (or adjust-
ment) items, and the key registers the value.
• By pressing the key for 3 sec, it is possible
to return to RUN mode from any setting (or adjust
-
ment) mode.
18
6. Setup
Setup [setting the Input type (SEWU), Input range, Output 0% value, Output 100% value,
Output type, etc.] should be done before using this unit, according to the user’s conditions.
Setup is performed in the Input 1/Output 1 function group, Output 2 function group and
Special function group.
If the user’s specifications are the same as the factory default of the instrument, or if setup
has already been completed, it is not necessary to set up the instrument. Proceed to Section
“7. Adjustment”.
Refer to factory defaults on (Tables 6-1, 6-2, 6-3).
(Table 6-1) Input 1/Output 1 Function Group
Setting Item Factory Default
Input type DC voltage (Available for the SEWU only)
1 to 5 V DC -1999 to 9999 (SEWU, SEWV)
4 to 20 mA DC -1999 to 9999 (SEWA)
K -200 to 1370 (SEWE)
Input range (*)
Pt100 -200 to 850 (SEWR)
Decimal point place No decimal point
-1999 (SEWU, SEWA, SEWV, SEWD, SEWD-F)
Output 0% value
-200 (SEWE, SEWR)
9999 (SEWU, SEWA, SEWV, SEWD, SEWD-F)
1370 (SEWE)
Output 100% value
850 (SEWR)
Filter time constant 0.0 sec
0 (SEWU, SEWA, SEWV, SEWD, SEWD-F)
Sensor correction
0.0 (SEWE, SEWR)
Output type 4 to 20 mA DC
Output Normal/Reverse
Normal
Burnout Upscale (SEWE, SEWR)
(*) Not available for the SEWD, SEWD-F.
(Table 6-2) Output 2 Function Group
Setting Item Factory Default
Output 0% value -200 (SEWE, SEWR)
1370 (SEWE)
Output 100% value
850 (SEWR)
Output type 4 to 20 mA DC
Output Normal/Reverse Normal
(Table 6-3) Special Function Group
Setting Item Factory Default
Set value lock Unlock
Input sampling period
(Response time)
250 ms [425 ms (typ.) (0 90%)]
Auto-light function Disabled
Display selection Input value/Output 1 value
Indication time 00.00 (Remains lit)
19
6.1 Indication after Power-on
After power-on, the unit moves to warm-up status for approx. 3 sec as shown below
(Fig. 6.1-1).
(Fig. 6.1-1)
After that, the unit switches to RUN mode as shown below (Fig. 6.1-2).
(Fig. 6.1-2)
6.2 Basic Operation of Setup
Setup is conducted in the Input 1/Output 1 function group, Output 2 function group and
Special function group.
(e.g.) For the SEWU, to enter the Input 1/Output 1 function group:
(1) In RUN mode, press the key 3 times. (Fig. 6.2-1, p.20)
(2) Press the key while Input 1/Output 1 function group characters are indicated.
(Fig. 6.2-2, p.20)
(3) The unit moves to the [Input type] item in the Input 1/Output 1 function group.
To set (or select) each item, use the or key, and register the value
with the key. (Fig. 6.2-3, p.20)
If the key is pressed at the last setting item, the unit will revert to RUN mode.
Indicates the input type.
Indicates for 1 to 5 V DC factory
default.
Indicates Output 1 type.
Indicates for 4 to 20 mA DC
factory
.
Lights when
power-on.
Lights when
power
-
on.
Indicates the input value.
Indicates Output 1 value as a percentage
(%), corresponding to input value.
Output
value
Input
value
20
O
utput
value
Input
value
(1) RUN Mode
(Fig. 6.2-1)
(2) Input 1/Output 1 Function Group
(Fig. 6.2-2)
(3) Selecting Input Type
(Fig. 6.2-3)
To set (or select)
each item, use
these keys.
Press the key while Input 1/
Output 1 function group characters
are indicated.
To proceed to each setting item or
to register the set (or selected) value,
use this key.
In RUN mode, press the key
3 times.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Shinko SEWx series User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI